Technical specifications and approvals
8.2 Approvals
Power Line Booster
Operating Instructions, 11/2019, A5E36203125A-AG
127
8.1.4
MTBF
Mean Time Between Failures
FIT
MTBF
PLB BM
2532
394,944 h or 45.1 years
PLB MM
1185
843,881 h or 96.2 years
BA 2xRJ45 [BA 2xFC]
917.6 years [1,024 years]
Power Line Booster (PLB BM, PLB MM, BA
2xRJ45)
3319
301,296h or 34.4 years
8.1.5
Climate
You can operate all devices at ambient temperatures of 0 .. +60 °C in standard mounting
position (DIN rail mounting horizontal on a vertical mounting surface). If you want to install
the Power Line Booster on a vertical DIN rail on a vertical mounting surface or on a
horizontal mounting surface, the maximum ambient temperature is reduced to +50 °C.
Distance to adjacent devices: 60 mm above and below the PLB.
The storage temperature is -40 °C … +70 °C.
Max. operation altitude: 2000 m above sea level
All components are designed for continuous operation (24 h/7 d).
8.2
Approvals
8.2.1
CE conformity
The PLB modules
●
PLB BM,
●
PLB MM and
●
PLB TC
in the version sold by us conforms with the directives of the following European guidelines:
2014/30/EC Directive of the European Parliament and of the Council of 26 February 2014 on
the approximation of the laws of the Member States relating to electromagnetic compatibility
2011/65/EC Directive of the European Parliament and Council of 8 June 2011 on the
harmonization of the laws of the Member States relating to electrical equipment designed for
use within certain voltage limits.
Содержание SIMATIC Power Line Booster