The sections below describe topics related to hardware updates:
● Adjustments after a hardware change (Page 35)
● Updating a SIMATIC S7 CPU (Page 35)
● Updating an interface module IM xxx (Page 39)
● Updating a CP xxx (Page 43)
● Working with GSD files (Page 49)
3.3.2
How to make adjustments after a hardware change
Basic procedure
A change to the hardware always requires a change to the software. You configure the changed
hardware in HW Config. Compile the changes and then download the data to the CPU. You
can then physically replace, remove or add the modified hardware.
Procedure
1. Open the project (the AS) in HW Config.
2. Drag the object (such as the CPU: Type, Firmware Version x.x) from the hardware catalog
and drop it into the appropriate slot in the AS configuration table.
The following message appears: "Do you want to exchange component ... with
component ...?"
3. After verification, click "Yes" to confirm.
4. Select the menu command Station > Save/Compile.
You can also perform the compiling during the subsequent work.
3.3.3
Updating the CPU
Preparation
Compare the type and manufacture date of the modules you are using with the information in
the document
PCS 7 Released Modules.
If replacement of the CPU is required, contact your Siemens representative.
Changing the quantity structure of the CPU for a SIMATIC S7-410
You can find information about this in the section "Upgrade of the System Expansion Card for
Ensuring Availability
3.3 Hardware update
Service Support and Diagnostics (V8.2)
Service Manual, 03/2016, A5E36200111-AA