Step
What?
5
Editing the hardware configuration of the PC stations on the ES (Page 62)
6
Setting the access point on the BOX PC (Page 63)
7
Configuring NetPro for external engineering (Page 64)
8
Configuring the Station Configuration Editor (Page 66)
9
Configuring and downloading the BOX PC (Page 67)
10
Opening the operator panel of the CPU (Page 68)
11
Compiling and downloading the AS data and OS data (Page 69)
12
Setting the CPU to RUN mode (Page 71)
Perform the configuration steps listed above in the order they are described.
7.4.2
How to select the network adapter in SIMATIC Shell
Introduction
The following describes how to select the network adapter adapter (communication module)
to be used to configure the PC stations.
Note
Perform the following steps on the engineering station and the SIMATIC PCS 7 BOX station.
Procedure
1. Double-click on the PC station (workstation) in the tree view of the Windows Explorer.
2. Select the "SIMATIC Shell" folder.
3. Select the Settings... command from the shortcut menu.
The "Select Terminal Bus" dialog box opens.
4. Select the network adapter you wish to use for the communication with the engineering
station.
Note
You can find additional information about the defaults of the Ethernet interface in the product
information for the BOX PC.
5. Click "OK" to apply your settings.
Note
When you confirm the next dialog box, the network connection to this PC station is
interrupted briefly.
6. Confirm the next dialog box.
The network adapter is reinitialized.
Commissioning and configuration of SIMATIC PCS 7 BOX RTX
7.4 Configuring SIMATIC PCS 7 BOX RTX with external engineering
BOX (V8.1)
58
Function Manual, 03/2015, A5E32711362-AC
Содержание SIMATIC PCS 7 BOX
Страница 6: ...Table of contents BOX V8 1 6 Function Manual 03 2015 A5E32711362 AC ...
Страница 8: ...Security information BOX V8 1 8 Function Manual 03 2015 A5E32711362 AC ...
Страница 14: ...Preface BOX V8 1 14 Function Manual 03 2015 A5E32711362 AC ...
Страница 24: ...WinAC RTX BOX V8 1 24 Function Manual 03 2015 A5E32711362 AC ...
Страница 26: ...Web Option for OS with SIMATIC PCS 7 BOX BOX V8 1 26 Function Manual 03 2015 A5E32711362 AC ...
Страница 126: ...Establishing the factory state BOX V8 1 126 Function Manual 03 2015 A5E32711362 AC ...