Setting the TCP/IP protocol on the plant bus
If you want to use the TCP/IP protocol on the plant bus, perform the following steps for the
network adapter connected to the plant bus:
1. In the Windows taskbar, select the menu command Start > Settings > Network Connections.
The "Network Connections" dialog box opens.
2. In the detail window select the network connection over which communication is performed
on the plant bus.
3. Select the menu command File > Properties.
4. Select the entry "Internet Protocol TCP/IP" from the list.
5. Click "Properties".
6. Set the TCP/IP address:
Activate the "Use the following IP address" check box and enter the "IP address" and
"Subnet mask".
7. Click "OK" twice to apply the settings.
The TCP/IP address is set.
7.4.8
How to configure NetPro on the external engineering station
Introduction
You assign the modules you are using to networks and create connections in NetPro on the
engineering station.
Using SIMATIC PDM
For the "SIMATIC PCS 7 BOX with external engineering" configuration, you can access
intelligent field devices connected to PROFIBUS DP from SIMATIC PDM via the external
engineering station.
Note
Observe the permissible cable lengths. For long transfer distances, we recommend using fiber-
optic cables as connectors.
Access to OS and CPU within the SIMATIC PCS 7 BOX station
You download the OS and user program from the engineering station via the combination plant/
terminal bus.
Commissioning and configuration of SIMATIC PCS 7 BOX RTX
7.4 Configuring SIMATIC PCS 7 BOX RTX with external engineering
BOX (V8.1)
64
Function Manual, 03/2015, A5E32711362-AC
Содержание SIMATIC PCS 7 BOX
Страница 6: ...Table of contents BOX V8 1 6 Function Manual 03 2015 A5E32711362 AC ...
Страница 8: ...Security information BOX V8 1 8 Function Manual 03 2015 A5E32711362 AC ...
Страница 14: ...Preface BOX V8 1 14 Function Manual 03 2015 A5E32711362 AC ...
Страница 24: ...WinAC RTX BOX V8 1 24 Function Manual 03 2015 A5E32711362 AC ...
Страница 26: ...Web Option for OS with SIMATIC PCS 7 BOX BOX V8 1 26 Function Manual 03 2015 A5E32711362 AC ...
Страница 126: ...Establishing the factory state BOX V8 1 126 Function Manual 03 2015 A5E32711362 AC ...