Installing the Device
2.4 Connecting Power
more information, refer to the "RUGGEDCOM RS8000A Configuration Manual" for the
RUGGEDCOM RS8000A.
The following shows the proper relay connections.
1
2
3
1
Normally Closed
2
Common
3
Normally Open
Figure 2.5
Failsafe Alarm Relay Wiring
2.4
Connecting Power
The RUGGEDCOM RS8000A supports a single integrated high AC/DC or low DC power
supply
IMPORTANT
• For 88-300 VDC rated equipment, an appropriately rated circuit breaker must be
installed.
• For 100-240 VAC rated equipment, an appropriately rated circuit breaker must
be installed.
• Use minimum #16 gage wiring when connecting terminal blocks.
• A circuit breaker is not required for 12, 24 or 48 VDC rated equipment.
• Power input terminals have reverse polarity protection for 12, 24 and 48 VDC
rated equipment.
• Equipment must be installed according to applicable local wiring codes and
standards.
RUGGEDCOM RS8000A
Installation Manual, 12/2021, C79000-G8976-1021-06