background image

Installing the Device

2.3.1 Mounting the Device on a DIN Rail

Forced airflow is not required. However, any increase in airflow will result in a reduc-

tion of ambient temperature and improve the long-term reliability of all equipment

mounted in the rack space.

Note

For detailed dimensions of the device with either rack, DIN rail or panel hardware in-

stalled, refer to 

"Dimension Drawings (Page 29)"

.

2.3.1

Mounting the Device on a DIN Rail

The RUGGEDCOM RS400F can be ordered with panel/DIN rail adapters preinstalled on

each side of the chassis. Use the adapters to mount the device to a standard 35 mm

(1.4 in) IEC/EN 60715 or TS35 DIN rail.

Mounting the Device

To mount the device to a DIN rail, do the following:
1. Hook the top teeth of the adapters onto the DIN rail.

2

2

2

3

1

1

     1    

Panel/DIN Rail Adapter

     2    

DIN Rail

     3    

Screw

Figure 2.1

Mounting the Device to a DIN Rail

2. Install one of the supplied #8-32 lock screws on either side of the device to se-

cure the adapters to the DIN rails.

RUGGEDCOM RS400F

Installation Manual, 02/2020, C79000-G8976-1341-04

9

Содержание SIMATIC NET RUGGEDCOM RS400F

Страница 1: ...Edition 02 2020 Installation Manual SIMATIC NET Rugged Ethernet Switches RUGGEDCOM RS400F https www siemens com ...

Страница 2: ...ed Ethernet Switches RUGGEDCOM RS400F Installation Manual Preface Introduction 1 Installing the Device 2 Device Management 3 Communication Ports 4 Technical Specifications 5 Certification 6 02 2020 C79000 G8976 1341 04 ...

Страница 3: ... personnel are those who based on their training and experience are capable of identify ing risks and avoiding potential hazards when working with these products systems Proper Use of Siemens Products Note the following WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation If products and components from other manufactur...

Страница 4: ...lling the Device 7 2 1 General Procedure 7 2 2 Unpacking the Device 8 2 3 Mounting the Device 8 2 3 1 Mounting the Device on a DIN Rail 9 2 3 2 Mounting the Device to a Rack 10 2 3 3 Mounting the Device to a Panel 11 2 4 Connecting the Failsafe Alarm Relay 12 2 5 Grounding the Device 13 2 6 Connecting Power 13 2 6 1 Connecting AC Power 14 2 6 2 Connecting DC Power 15 3 Device Management 17 3 1 Con...

Страница 5: ...fe Alarm Relay Specifications 27 5 3 Copper Ethernet Port Specifications 27 5 4 Fiber Optic Ethernet Port Specifications 28 5 5 Serial Port Specifications 29 5 6 Operating Environment 29 5 7 Mechanical Specifications 29 5 8 Dimension Drawings 29 6 Certification 33 6 1 Approvals 33 6 1 1 CSA 33 6 1 2 European Union EU 33 6 1 3 FCC 34 6 1 4 FDA CDRH 34 6 1 5 ISED 34 6 1 6 RoHS 35 6 1 7 Other Approva...

Страница 6: ...ilable online at https support industry siemens com To request or inquire about a user document con tact Siemens Customer Support Disclaimer of Liability Siemens has verified the contents of this document against the hardware and or soft ware described However deviations between the product and the documentation may exist Siemens shall not be liable for any errors or omissions contained herein or ...

Страница 7: ...on about training services and course availability visit https www siemens com or contact a Siemens Sales representative Customer Support Customer support is available 24 hours 7 days a week for all Siemens customers For technical support or general information contact Siemens Customer Support through any of the following methods Online Visit http www siemens com automation support request to subm...

Страница 8: ...try Sector 300 Applewood Crescent Concord Ontario Canada L4K 5C7 Telephone Toll free 1 888 264 0006 Tel 1 905 856 5288 Fax 1 905 856 1995 E Mail ruggedcom info i ia siemens com Web https www siemens com RUGGEDCOM RS400F Installation Manual 02 2020 C79000 G8976 1341 04 vii ...

Страница 9: ...Preface Contacting Siemens viii RUGGEDCOM RS400F Installation Manual 02 2020 C79000 G8976 1341 04 ...

Страница 10: ...d NEMA TS 2 The RUGGEDCOM RS400F also features a wide operating temperature range of 40 to 85 C 40 to 185 F allowing it to be installed in virtually any location The RUGGEDCOM RS400F also includes an industrially rated integrated power sup ply that can support a wide range of power supply options suitable for multiple in dustries and for worldwide operability Options include 24 VDC 48 VDC 88 300 V...

Страница 11: ...ore and forward switching 10 100Base TX 10Base FL 100Base FX options Remote Dial Up Access Integrated V 90 modem and PPP server Provides remote access to serial devices and Ethernet LAN Rated for Reliability in Harsh Environments Immunity to EMI and heavy electrical surges Fully independent 2 kV RMS isolated serial ports 40 to 85 C 40 to 185 F operating temperature no fans 18 AWG galvanized steel ...

Страница 12: ...pply Terminal Block Figure 1 1 RUGGEDCOM RS400F Modules POWER LED Illuminates when power is being supplied to the device ALARM LED Illuminates when an alarm condition exists RESET Button Shuts down and restarts the device Ethernet Port Status LEDs Indicate the status of the associated Ethernet port LED State Meaning Solid Link established Blinking Link activity LINK Off No link detected RUGGEDCOM ...

Страница 13: ...erial console port refer to Connect ing to the Device Page 17 Failsafe Alarm Relay Latches to default state when a power disruption or other alarm condition occurs For more information refer to Connecting the Failsafe Alarm Relay Page 12 Failsafe Alarm Relay Specifications Page 27 Power Supply Terminal Block A pluggable terminal block For more information refer to Con necting Power Page 13 and Pow...

Страница 14: ...SIMATIC NET industrial Ethernet shielded cables for all Ethernet ports 1 5 1 Protection On Twisted Pair Data Ports All copper Ethernet ports on RUGGEDCOM products include transient suppression circuitry to protect against damage from electrical transients and conform with IEC 61850 3 and IEEE 1613 Class 1 standards This means that during a transient electri cal event communications errors or inter...

Страница 15: ...m Cable Type Wavelength nm Modal Band width MHz km 100Base FX 1000Base SX 10GBase SR 850 1500 550 300 OM3 50 125 a 1300 500 2000 850 3500 550 400 OM4 50 125 a 1300 500 2000 a Laser optimized 6 RUGGEDCOM RS400F Installation Manual 02 2020 C79000 G8976 1341 04 ...

Страница 16: ...rsonnel shall render all warranties null and void Changes or modifications not expressly approved by Siemens AG could invalidate specifications test results and agency approvals and void the user s authority to operate the equipment IMPORTANT This product should be installed in a restricted access location where access can only be gained by authorized personnel who have been informed of the restri...

Страница 17: ... network For more information refer to Communication Ports Page 19 7 Configure the device For more information refer to Configuring the Device Page 18 2 2 Unpacking the Device When unpacking the device do the following 1 Inspect the package for damage before opening it 2 Visually inspect each item in the package for any physical damage 3 Verify all items are included NOTICE If any item is missing ...

Страница 18: ...a DIN Rail The RUGGEDCOM RS400F can be ordered with panel DIN rail adapters preinstalled on each side of the chassis Use the adapters to mount the device to a standard 35 mm 1 4 in IEC EN 60715 or TS35 DIN rail Mounting the Device To mount the device to a DIN rail do the following 1 Hook the top teeth of the adapters onto the DIN rail 2 2 2 3 1 1 1 Panel DIN Rail Adapter 2 DIN Rail 3 Screw Figure ...

Страница 19: ...allations the RUGGEDCOM RS400F can be equipped with rack mount adapters pre installed at the front or rear of the chassis Additional adapters are provided to further secure the device in high vibration or seismically active loca tions To secure the device to a standard 48 cm 19 in rack do the following Note The device can be ordered with the communication ports located at the front or rear of the ...

Страница 20: ...nnelled to the enclosure it is recommended that 1 rack unit of space or 44 mm 1 75 in be kept empty above the device This allows a small amount of convectional airflow Forced airflow is not required However any increase in airflow will result in a reduction of ambient temperature and improve the long term reliability of all equipment mounted in the rack space 4 Secure the adapters to the rack usin...

Страница 21: ...itions The NO Normally Open contact is closed when the unit is powered and there are no ac tive alarms If the device is not powered or if an active alarm is configured the relay opens the NO contact and closes the NC Normally Closed contact Note Control of the failsafe relay output is configurable through RUGGEDCOM RS400F One common application for this relay is to signal an alarm if a power failu...

Страница 22: ... connection with a 6 ring lug and torque it to 1 7 N m 15 lbf in 2 1 3 1 Stainless Steel Stud 2 6 32 Screw 3 6 Ring Lug Figure 2 6 Chassis Ground Connection 2 6 Connecting Power The RUGGEDCOM RS400F supports a single integrated high AC DC or low DC power supply Note For 88 300 VDC rated equipment an appropriately rated circuit breaker must be installed RUGGEDCOM RS400F Installation Manual 02 2020 ...

Страница 23: ...o the device do the following NOTICE Electrical hazard risk of damage to equipment Before testing the dielectric strength HIPOT in the field remove the braided ground cable connected to the surge ground terminal and chassis ground This cable connects transient suppression circuitry to chassis ground and must be removed in order to avoid damage to transient suppression circuitry during testing 1 Co...

Страница 24: ...Connecting DC Power To connect a high or low DC power supply to the device do the following NOTICE Electrical hazard risk of damage to equipment Before testing the dielectric strength HIPOT in the field remove the braided ground cable connected to the surge ground terminal and chassis ground This cable connects transient suppression circuitry to chassis ground and must be removed in order to avoid...

Страница 25: ... the surge ground terminal to the chassis ground connection The surge ground terminal is used as the ground conductor for all surge and transient suppression circuitry in ternal to the unit 4 Connect the ground terminal on the power source to the chassis ground termi nal on the device For more information refer to Grounding the Device Page 13 16 RUGGEDCOM RS400F Installation Manual 02 2020 C79000 ...

Страница 26: ...eshooting The serial console port implements RS232 DCE Data Communication Equipment on a DB9 connector The following is the pin out for the port 1 5 9 6 Figure 3 1 Serial DB9 Console Port Pin Name Description 1 a Reserved Do Not Connect 2 TX Transmit Data 3 RX Receive Data 4 a Reserved Do Not Connect 5 GND Signal Ground 6 a Reserved Do Not Connect 7 b Reserved Do Not Connect 8 b Reserved Do Not Co...

Страница 27: ... the network it must be configured All configuration management is done via the RUGGEDCOM ROS interface For more in formation about configuring the device refer to the RUGGEDCOM ROS Configura tion Manual associated with the installed software release 18 RUGGEDCOM RS400F Installation Manual 02 2020 C79000 G8976 1341 04 ...

Страница 28: ... Each communication port type has a specific place in the RUGGEDCOM RS400F chas sis 3 2 1 1 Copper or Fiber Ethernet Ports 2 Serial Ports 3 Modem Port Optional Figure 4 1 Port Assignment 4 1 Copper Ethernet Ports The RUGGEDCOM RS400F supports several 10 100Base TX Ethernet ports that al low connection to standard Category 5 CAT 5 unshielded twisted pair UTP cables with RJ45 male connectors The RJ4...

Страница 29: ... at max imum speed Yellow Solid Link established Yellow Blinking Link activity Link Off No link detected Pin Out Description The following is the pin out for the RJ45 male connectors 1 8 Figure 4 2 RJ45 Ethernet Port Pin Config uration Pin Name Description 1 RX Receive Data 2 RX Receive Data 3 TX Transmit Data 4 Reserved Do Not Connect 5 Reserved Do Not Connect 6 TX Transmit Data 7 Reserved Do Not...

Страница 30: ...ns For specifications on the available fiber optic Ethernet ports refer to Fiber Optic Eth ernet Port Specifications Page 28 4 3 Modem Port The RUGGEDCOM RS400F can optionally be equipped with a V 90 Modem connec tion for PPP Point to Point Protocol connections For information about how to con figure and operate the modem refer to the RUGGEDCOM ROS Configuration Manual for the RUGGEDCOM RS400F WAR...

Страница 31: ...d five 4 4 Serial Ports The RUGGEDCOM RS400F supports RJ45 or DB9 serial ports which can be run in RS232 RS485 or RS422 mode Note On power up all serial ports default to RS485 mode Each port can be individually set to RS232 RS485 or RS422 mode through RUGGEDCOM RS400F For more infor mation refer to the RUGGEDCOM ROS Configuration Manual for the RUGGEDCOM RS400F All serial ports feature an LED that...

Страница 32: ...422 DB9 Ports The RUGGEDCOM RS400F can be equipped with serial RS232 RS485 RS422 DB9 ports Each port can be set individually through the RUGGEDCOM RS400F operating system to operate in RS232 RS485 or RS422 mode For more information refer to the RUGGEDCOM ROS Configuration Manual for the RUGGEDCOM RS400F The following is the pin out description for the RS232 RS485 RS422 DB9 ports 1 5 9 6 Figure 4 9...

Страница 33: ...scription for the RS232 RS485 RS422 RJ45 ports 1 8 Figure 4 10 RS232 RS485 RS422 RJ45 Ser ial Console Port Name Pin a RS232 Mode RS485 Mode RS422 Mode 1 DSR b RX 2 DCD b 3 DTR b 4 Common Isolated Ground 5 RXD c RX 6 TXD c TX RX TX 7 CTS 8 RTS TX RX TX Shield Chassis Ground a No internal termination is provided b The DSR DCD and DTR pins are connected together internally c In RS232 mode the RJ45 po...

Страница 34: ...ex For reliable continuous communication adhere to the following guidelines To minimize the effects of ambient electrical noise use shielded cabling The correct polarity must be observed throughout a single sequence or ring The number of devices wired should not exceed 32 and total distance should be less than 1219 m 4000 ft at 100 kbps The Common terminals should be connected to the common wire i...

Страница 35: ...120Ω 10nF 120Ω 10nF 1 2 3 5 5 6 4 1 RUGGEDCOM RS400F 2 Common Isolated Ground 3 Negative 4 Positive 5 Shield to Earth Connected At a Single Point 6 RS485 Devices 32 Total Figure 4 12 Recommended RS485 Wiring 26 RUGGEDCOM RS400F Installation Manual 02 2020 C79000 G8976 1341 04 ...

Страница 36: ...th AC and DC 5 2 Failsafe Alarm Relay Specifications Max Switching Volt age 30 VAC 80 VDC 125 VAC 250 VAC Rated Switching Cur rent 0 3 A 30 VAC 1 A 30 VDC 0 3 A 80 VDC 0 2 A 250 VAC 0 6 A 125 VAC 5 3 Copper Ethernet Port Specifications The following details the specifications for copper Ethernet ports that can be ordered with the RUGGEDCOM RS400F Speed a Connector Duplex a Cable Type b Wiring Stan...

Страница 37: ... nm b Minimum Maximum Rx Sen sitivity dBm Av erage a Rx Satura tion dBm Peak a Distance km c Pow er Bud get dB MM LC 62 5 125 1310 20 14 31 14 2 11 MM ST 62 5 125 1300 19 14 33 9 14 2 11 4 MM ST 50 125 1300 22 5 14 33 9 14 2 14 9 MM ST 62 5 125 1300 19 14 30 14 2 5 11 MM SC 62 5 125 1300 19 14 33 9 14 2 14 9 MM SC 50 125 1300 22 5 14 33 9 14 2 14 9 MM LC 62 5 125 1310 19 14 32 14 2 13 MM MTRJ 62 5...

Страница 38: ...M RS400F is rated to operate under the following environmental con ditions Ambient Operating Tempera ture a 40 to 85 C 40 to 185 F Ambient Storage Temperature 40 to 85 C 40 to 185 F Ambient Relative Humidity b 5 to 95 Maximum Altitude 2000 m 6562 ft a Measured from a 30 cm 12 in radius surrounding the center of the enclosure b Non condensing 5 7 Mechanical Specifications Weight 2 2 kg 4 8 lb Ingre...

Страница 39: ... 0 25 4 5 3 44 2 291 3 174 0 56 6 47 2 Figure 5 1 Overall Dimensions 22 9 33 5 45 7 2 5 11 4 22 9 34 5 13 7 135 9 132 6 4 1 4 1 202 2 31 8 466 6 481 3 Figure 5 2 Rack Mount Dimensions 30 RUGGEDCOM RS400F Installation Manual 02 2020 C79000 G8976 1341 04 ...

Страница 40: ...ical Specifications 5 8 Dimension Drawings 159 5 25 2 56 1 12 7 6 35 R 2 0 R8 1 335 0 324 9 Figure 5 3 Panel and Din Rail Mount Dimensions RUGGEDCOM RS400F Installation Manual 02 2020 C79000 G8976 1341 04 31 ...

Страница 41: ...Technical Specifications 5 8 Dimension Drawings 32 RUGGEDCOM RS400F Installation Manual 02 2020 C79000 G8976 1341 04 ...

Страница 42: ... UL 60950 1 UL 60950 1 Information Technology Equipment Safety Part 1 General Requirements 6 1 2 European Union EU This device is declared by Siemens AG to comply with essential requirements and other relevant provisions of the following EU directives EN 60950 1 Information Technology Equipment Safety Part 1 General Requirements EN 61000 6 2 Electromagnetic Compatibility EMC Part 6 2 Generic Stand...

Страница 43: ...rated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference on his own e...

Страница 44: ...ntal and Testing Requirements for Communications Networking Devices in Electric Power Substations IEC 61850 3 Communications Networks and Systems for Power Utility Automation Part 3 General Requirements IEC 61000 6 2 Electromagnetic Compatibility EMC Part 6 2 Generic Standards Immunity for Industrial Environments 6 2 EMC and Environmental Type Tests The RUGGEDCOM RS400F has passed the following EM...

Страница 45: ... dif ferential mode at 1 MHz 3 DC Power Ports 2 5 kV common 1 kV dif ferential mode at 1 MHz 3 IEC 61000 4 12 Damped Oscillatory AC Power Ports 2 5 kV common 1 kV dif ferential mode at 1 MHz 3 Signal Ports 30 V Continuous 300 V for 1 s 4 IEC 61000 4 16 Mains Frequen cy Voltage DC Power Ports 30 V Continuous 300 V for 1 s 4 IEC 61000 4 17 Ripple on DC Power Supply DC Power Ports 10 3 Signal Ports 2...

Страница 46: ...de at 1 MHz Signal Ports 2 kVAC DC Power Ports 1 5 kVDC Dielectric Strength AC Power Ports 2 kVAC Signal Ports 5 kV Failsafe Relay DC Power Ports 5 kV HV Impulse AC Power Ports 5 kV Environmental Type Tests Test Description Test Levels IEC 60068 2 1 Cold Temperature Test Ad 40 C 40 F 16 Hours IEC 60068 2 2 Dry Heat Test Bd 85 C 185 F 16 Hours IEC 60068 2 30 Humidity Damp Heat Cyclic Test Db 95 non...

Страница 47: ...Certification 6 2 EMC and Environmental Type Tests 38 RUGGEDCOM RS400F Installation Manual 02 2020 C79000 G8976 1341 04 ...

Страница 48: ...ttps www siemens com ruggedcom Industry Online Support service and support https support industry siemens com Industry Mall https mall industry siemens com Siemens AG Digital Industry Process Automation Postfach 48 48 90026 NÜRNBERG GERMANY ...

Отзывы: