Operating system and configuration
6.2 Windows CE Control Panel
TP 270, OP 270, MP 270B (WinCC flexible)
6-10
Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
Saving the registration settings or RAM file system
1. Open the "Persistent Storage" tab in the "OP Properties" dialog.
Figure 6-5
"OP Properties" dialog, "Persistent Storage" tab
2. Press the Save Registry button to start the storage process.
The current registration settings are stored in the Flash memory.
3. Press the Save Files button to start copying the files in the RAM file system to the Flash
memory.
Following a restart, these saved files will be copied back to the file system.
4. In the case of the touch panel, close the dialog using the "OK" button. In the case of the
keyboard unit, move the focus to the tab heading by pressing
TAB
and press
ENTER
to
close the dialog.