Mounting and connecting the device
3.4 Connecting the device
SIMATIC IPC477D, IPC477D PRO
Operating Instructions, 11/2016, A5E31347228-AF
91
3.4.3.2
connecting the PE conductor
The connection for the protective conductor is labeled with the following symbol:
Requirements
●
The device is installed.
●
1 protective conductor with minimum core cross-section of 2.5 mm
2
●
1 T20 screwdriver
●
1 cable lug for M4
Procedure
1. Clamp the cable lug onto the protective conductor.
2. Connect the cable lug to the screw at the
designated protective conductor connec-
tion.
Tighten the M4 screw with a torque of
max. 1.5 Nm.
3. Connect the protective conductor to the protective conductor connection of the control
cabinet from which the PRO device is supplied.