Installing and connecting the device
3.2 Installing the device
SIMATIC IPC347E
Operating Instructions, 09/2018, A5E41134132-AE
29
●
The device is approved for indoor operation only.
●
When the device is used in the area of Industrial Control Equipment in accordance with
UL61010-2-201, the device is classified as "Open equipment".
Open equipment must be installed within an enclosure which protects you from hazards,
including mechanical hazards, electrical shock and spread of fire.
●
Install the device only in one of the described permitted mounting positions.
●
For installation of control cabinet, observe the country-specific regulations.
●
Provide adequate volume in the switchgear cabinet for air circulation and heat transport.
Keep at least 10 cm between the device and the switchgear cabinet.
●
Do not cover the vent slots of the device.
●
Ensure that the maximum air intake temperature, measured 5 cm before the air intake
opening, does not exceed 40° C. The maximum air intake temperature must be
accounted for especially when sizing closed switchgear cabinets.
●
The minimum distance between the device and the housing is 10 cm on the air output
end.
●
Ensure that the installed device does not pose a danger, for example, hit someone by
falling over.
●
All the external circuit of the device must be SELV circuit.
3.2.2
Mounting location and position
Optional mounting locations
The device can be mounted horizontally in control desks and 19" rack systems.
Содержание SIMATIC IPC347E
Страница 8: ...Table of contents SIMATIC IPC347E 8 Operating Instructions 09 2018 A5E41134132 AE ...
Страница 24: ...Safety instructions 2 4 Notes on use SIMATIC IPC347E 24 Operating Instructions 09 2018 A5E41134132 AE ...
Страница 82: ...Technical specifications 7 5 BIOS description SIMATIC IPC347E 82 Operating Instructions 09 2018 A5E41134132 AE ...
Страница 100: ...Appendix Motherboard A 4 Installing drivers SIMATIC IPC347E 100 Operating Instructions 09 2018 A5E41134132 AE ...
Страница 126: ...Appendix Technical support D 2 Problem solving SIMATIC IPC347E 126 Operating Instructions 09 2018 A5E41134132 AE ...
Страница 132: ...Appendix List of abbreviations SIMATIC IPC347E 132 Operating Instructions 09 2018 A5E41134132 AE ...
Страница 148: ...Index SIMATIC IPC347E 148 Operating Instructions 09 2018 A5E41134132 AE ...