Installing and connecting the device
3.2 Preparing for installation
Comfort Panels INOX, ITC INOX
16
Compact Operating Instructions, 08/2022, A5E33472156-AP
3.2.4
Checking clearances
The following clearances are required around the HMI device to ensure sufficient self-
ventilation:
•
At least 23 mm to the right and to the left of the mounting cutout (in the x direction) for
mounting the clamping frame during installation
•
At least 50 mm above and 50 mm below the mounting cutout (in the y direction) for
ventilation
•
At least 10 mm behind the rear panel of the HMI device (in the z direction)
The following figure shows the clearances during mounting of the HMI devices in horizontal
and vertical formats:
①
Clearance for installation in landscape format
②
Clearance for installation in portrait format
x
Distance from wall at least 23 cm.
y
At least 50 mm distance
z
At least 10 mm distance
Note
Ensure that the maximum ambient temperature is not exceeded when mounting the device
in a cabinet and especially in a closed enclosure.