SIMATIC HMI
KTP700F Mobile HW, KTP700F Mobile HW/OR - Quick Install Guide
Product Information
A5E45501235
Validity
This product information is valid for the HMI devices KTP700F Mobile HW and KTP700F Mobile HW/OR with the article numbers listed under "Required system components".
This product information describes the general commissioning of the HMI devices. Before setting up and commissioning the system, refer to the "Mobile Panels 2nd Generation" operating
instructions for a description of the safety functions of fail-safe HMI devices and other information. You can find the operating instructions on the supplied DVD and on the Internet
https://support.industry.siemens.com/cs/ww/en/ps/14746/man
Required system components
HMI device
KTP700F Mobile HW, KTP700F Mobile HW/OR
KTP Mobile connecting cable
Connection box compact, connection box standard or connection box advanced
Article numbers 6AV2145-8GB0.-0AA0
Article numbers 6AV2181-5AF..-0AX0
Article number 6AV2125-2AE03-0AX0, 6AV2125-2AE13-0AX0 or 6AV2125-2AE23-0AX0
You can find ordering information for accessories on the Internet (
https://mall.industry.siemens.com
Installing connection boxes
Use the product information provided for the connection box.
1.
Mount the connection box.
2.
Set a unique box ID.
3.
Connect the protective conductor.
4.
If you are installing a hard-wired F-system, connect the cables for the EMERGENCY STOP button and acknowledgment button with
your processing unit.
5.
Connect the connection box with PROFINET (LAN).
6.
Connect the cables for the power supply.
Connecting the connecting cable to the Mobile Panel
1. Insert a
SIMATIC HMI
memory card
if required.
2. Connect the
connector of the
cable to the X1 and
X80 interfaces in
the connection
compartment.
3. Close the
connection
compartment.
The maximum
permissible
torque is 0.2 Nm.
Connecting the Mobile Panel
Repeat steps 1 to 3 for each connection box you operate with the fail-safe HMI device.
Transferring a project
Note
Configure the PROFIsafe address of the HMI device in the Control Panel before the project transfer. The PROFIsafe address in the Control Panel must correspond to the PROFIsafe address
of the HMI device in the project.
1.
Connect the configuration PC with the LAN.
2.
To transfer the project, proceed according to the description in the "Mobile Panels 2nd Generation" operating instructions or in the online help for WinCC (TIA Portal).