x*5W = basic power loss of power supply (x = 1 for standard configuration, x = 2 for redundant
configuration)
1.2*∑
PV_Type_I/O
= typical power loss of input and output modules, including the resulting P
V
in
the power supply.
3.7
Maximum configuration of the ET 200iSP
Number of ET 200iSP Stations
You may operate up to 31 ET 200iSP stations on one segment of
PROFIBUS RS 485-IS (via RS 485-IS Coupler).
Power consumption of ET 200iSP with full configuration
Refer to technical specifications Power supply PS 24 VDC (Page 221) and technical
specifications Power supply PS 120/230 VAC (Page 224).
Width of ET 200iSP
The maximum configuration width ET 200iSP (power interface 32 electronic
m terminating module) is:
● 1.095 m (with one power supply and one IM 152)
● 1.185 m (with two power supplies and two IM 152)
Address space
The interface module supports maximum 244 input and 244 output bytes. There are DP
masters that do not control the entire address space.
Configuration options
3.7 Maximum configuration of the ET 200iSP
ET 200iSP
56
Operating Instructions, 11/2017, A5E00247483-07
Содержание SIMATIC ET 200iSP
Страница 82: ...Configuration options 3 18 Redundancy with IM 152 ET 200iSP 82 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 184: ...Commissioning and Diagnostics 6 8 Diagnostics with STEP 7 ET 200iSP 184 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 194: ...Maintenance 7 7 Reading service data ET 200iSP 194 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 220: ...Terminal modules 9 6 Terminal module TM RM RM ET 200iSP 220 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 372: ...Glossary ET 200iSP 372 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 384: ...Index ET 200iSP 384 Operating Instructions 11 2017 A5E00247483 07 ...