Wiring rules for ...
TM-PS-A/ TM‑PS-A UC,
TM-PS-B/ TM-PS-B UC
TM-IM/EM, TM-EM/EM
(spring and screw termi‐
nals)
With insulation collar 0.25
to 1.5 mm
Form E, up to 12 mm long Form E, up to 12 mm long
Tightening torque
0.5 - 0.7 Nm
5.4.2
Wiring Terminal Modules with Screw Terminals
Properties
● In terminal modules with screw terminals, the individual wires are screwed into the terminal.
● Wire-end ferrules are not necessary.
Prerequisites
Observe the wiring rules.
Required tool
3.5 mm screwdriver
Procedure
1. Strip insulation from the wires.
2. Insert the individual wires into the terminal.
3. Tighten the screw. Result: The wire is clamped into the terminal module.
5.4.3
Wiring terminal modules with spring terminals
Properties
In terminal modules with spring terminals, the individual wires are affixed by inserting them
into the terminal.
Requirements
Observe the wiring rules.
Required tools
3.5 mm screwdriver
Wiring
5.4 Wiring the ET 200iSP
ET 200iSP
110
Operating Instructions, 11/2017, A5E00247483-07
Содержание SIMATIC ET 200iSP
Страница 82: ...Configuration options 3 18 Redundancy with IM 152 ET 200iSP 82 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 184: ...Commissioning and Diagnostics 6 8 Diagnostics with STEP 7 ET 200iSP 184 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 194: ...Maintenance 7 7 Reading service data ET 200iSP 194 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 220: ...Terminal modules 9 6 Terminal module TM RM RM ET 200iSP 220 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 372: ...Glossary ET 200iSP 372 Operating Instructions 11 2017 A5E00247483 07 ...
Страница 384: ...Index ET 200iSP 384 Operating Instructions 11 2017 A5E00247483 07 ...