Wiring
ET 200iS Distributed I/O Station
6-4
A5E00087831-02
Reliable Electrical Isolation
Reliable electrical isolation is required with modules that are powered with voltages
≤
DC 60 V or
≤
AC 25 V, in other words, the power supply of the ET 200iS must be
reliably electrically isolated.
Setting up the ET 200iS with a Grounded Reference Potential
When the ET 200iS distributed I/O station is configured with a grounded reference
potential, any interference currents are diverted to the grounding conductor.
ET 200iS within the Entire System
The following schematic shows the ET 200iS distributed I/O station within the entire
system in zone 1 (power supply and grounding concept) when powered from a TN-
S system.
AC
DC
Ground bus
(1)
(2)
L1
L2
L3
N
PE
Low voltage distribution, e.g.
TN-S system (3x400V)
ET200iS
FE
FE
FE
FE
FE
FE
FE: Functional earth for direct
diversion of noise levels on
the DIN rail over spring contacts
DIN rail
1L+
2L+
1M
2M
1PA
2PA
Enclosure EEx e
Hazardous area zone 1
Safe
area
Shield contact element for
contacting cable shields
Figure 6-1 Operating the ET 200iS with a Grounded Reference Potential
Содержание SIMATIC ET 200iS
Страница 20: ...Preface ET 200iS Distributed I O Station 1 6 A5E00087831 02 ...
Страница 34: ...Product Overview ET 200iS Distributed I O Station 2 14 A5E00087831 02 ...
Страница 84: ...Installation ET 200iS Distributed I O Station 5 18 A5E00087831 02 ...
Страница 168: ...Maintenance ET 200iS Distributed I O Station 8 6 A5E00087831 02 ...
Страница 184: ...Terminal Modules ET 200iS Distributed I O Station 10 8 A5E00087831 02 ...
Страница 188: ...Power Supply Module ET 200iS Distributed I O Station 11 4 A5E00087831 02 ...
Страница 320: ...Dimension Drawings ET 200iS Distributed I O Station 17 4 A5E00087831 02 ...
Страница 330: ......
Страница 332: ...Certifications ET 200iS Distributed I O Station 20 2 A5E00087831 02 ...
Страница 333: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 3 ...
Страница 334: ...Certifications ET 200iS Distributed I O Station 20 4 A5E00087831 02 ...
Страница 335: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 5 20 1 2 Interface module IM151 2 ...
Страница 336: ...Certifications ET 200iS Distributed I O Station 20 6 A5E00087831 02 ...
Страница 337: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 7 20 1 3 Power supply PS ...
Страница 338: ...Certifications ET 200iS Distributed I O Station 20 8 A5E00087831 02 ...
Страница 339: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 9 20 1 4 4DI NAMUR ...
Страница 340: ...Certifications ET 200iS Distributed I O Station 20 10 A5E00087831 02 ...
Страница 341: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 11 ...
Страница 342: ...Certifications ET 200iS Distributed I O Station 20 12 A5E00087831 02 20 1 5 2DO DC25V 25mA ...
Страница 343: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 13 ...
Страница 344: ...Certifications ET 200iS Distributed I O Station 20 14 A5E00087831 02 20 1 6 2AI I 2WIRE 2AI I 2WIRE HART ...
Страница 345: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 15 o 1 1 P r e f a c e 1 1 1 ...
Страница 346: ...Certifications ET 200iS Distributed I O Station 20 16 A5E00087831 02 20 1 7 2AI I 4WIRE 2AI I 4WIRE HART ...
Страница 347: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 17 ...
Страница 348: ...Certifications ET 200iS Distributed I O Station 20 18 A5E00087831 02 20 1 8 2AI RTD ...
Страница 349: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 19 ...
Страница 350: ...Certifications ET 200iS Distributed I O Station 20 20 A5E00087831 02 20 1 9 2AI TC ...
Страница 351: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 21 ...
Страница 352: ...Certifications ET 200iS Distributed I O Station 20 22 A5E00087831 02 20 1 10 2AO I 2AO I HART ...
Страница 353: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 23 ...
Страница 355: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 25 20 2 3 Power supply PS 20 2 4 4DI NAMUR ...
Страница 357: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 27 20 2 7 2AI I 4WIRE 2AI I 4WIRE HART 20 2 8 2AI RTD ...
Страница 358: ...Certifications ET 200iS Distributed I O Station 20 28 A5E00087831 02 20 2 9 2AI TC 20 2 10 2AO I 2AO I HART ...
Страница 366: ...Marking ET 200iS Distributed I O Station 21 8 A5E00087831 02 ...
Страница 390: ...12 Product Information to the manual Distributed I O device ET 200iS Version 10 2001 A5E00163808 02 ...
Страница 416: ...26 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Страница 417: ...27 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Страница 418: ...28 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Страница 419: ...28 Produktinformation RS 485 IS Koppler 6ES7 972 0AC80 0XA0 A5E00207082 01 ...
Страница 420: ...28 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 02 ...