2.4
Installing the terminal block
Properties
The terminal block connects the ET 200eco PN and supplies the I/O device with power.
The terminal block
• can be installed separately,
• or be screwed on to each I/O device.
Requirements
Note that you must wire the terminal block before you install it.
Tools required
Recessed head screwdriver, medium size
Installing the terminal block separately
You install the terminal block separately.
Remove the screws and then screw them in again at the bottom of the housing.
0FDSIRU,3
Figure 2-5 Installing the terminal block separately
Installing the terminal block on an I/O device
Install the terminal block vertically on a housing of 30 mm width, or horizontally on a housing
of 60 mm width.
An M12 cap is attached to the bottom of the terminal block to implement the corresponding
degree of protection. Make sure that the M12 cap is not attached to the terminal block
25
Installing
2.4 Installing the terminal block
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN