Digital Input/Output Module ET 200C; DI 16/DO 16
DC 24V/2A
(6ES7 143-0BL00-0XB0 and 6ES7
143-0BL10-0XB0)
Technical Specifications
Baud rates
9.6/19.2/93.75/187.5/500/
1500/3000
1
/6000
1
/
12000
1
kbaud
Mains buffering
(without sensor and load
voltage supply)
typ. 20 ms
Insulation rating
to VDE 0160
Nominal insulation voltage
(L+ against PE)
Test voltage
60 V AC (75 V DC)
500 V DC
Electrical isolation to
SINEC L2-DP bus
500 V
Power loss
typ. 4.1 W
Weight
Dimensions (W
H
D)
approx. 3700 g
260
167
83
Diagnostic Functions
Voltage monitoring
green LED ”RUN”
SINEC L2-DP bus
monitoring
red LED ”BF”
Status of inputs or outputs
red LED ”DIA” for
diagnosing groups of 4
inputs/outputs
2
green LED for status of
inputs
Supply Voltage for Outputs, Load Voltage Supply
and Internal Logic
Nominal value (L+)
Permissible range
(incl. ripple = max. 3.6 V)
Value at t < 0,5 s
24 V DC
20.4 ... 30.2 V
35 V
Short-circuit capability
Yes
Current consumption
Logic
Load
Short-circuit current
typ. 90 mA
typ. 40 mA
max. 6.3 A
1
This baud rate is only relevant in conjunction with the
IM 308-C.
2
If a short-circuit occurs in the sensor supply of an input,
the sensor supply for all of the inputs in the group of 4
will be interrupted.
Inputs
Number of inputs
16
Connection
6ES7 143-0BL00-0XB0
via 5-pin circular connec-
tor (4-wire connection)
6ES7 143-0BL10-0XB0
via cable gland and con-
duit thread
(4-wire connection)
Electrical isolation
No
Supply voltage for sensors
Permissible total current
per channel
(L+) – 0.8 V
max. 4 A
max. 250 mA
Input voltage
Nominal value
for “0” signal
for “1” signal
24 V DC
–30 ... 5 V
13 ... 30 V
Input current for “1” signal typ. 4.5 mA at 24 V
Short-circuit current
limitation
2.3 A for each group of 4
Delay of inputs
typ. 1.8 ms (0
³
1)
typ. 1 ms (1
³
0)
Connection of 2-wire
BERO
Quiescent input
current
Possible
v
1.5 mA
Cable length of the inputs
max. 50 m
Outputs
Number of outputs
in groups of
16
8
Connection with
6ES7 143-0BL00-0XB0
6ES7 143-0BL10-0XB0
via 5-pin circular
connector
(3-wire connection)
via cable gland and
conduit thread
(3-wire connection)
Digital Modules
Содержание SIMATIC ET 200C
Страница 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Страница 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Страница 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Страница 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Страница 122: ...4 54 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Mechanical and Electrical Installation ...
Страница 136: ...5 14 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Address Assignment and Parameterization with COM ET 200 ...
Страница 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Страница 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Страница 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Страница 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Страница 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Страница 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Страница 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...