Mode of Functioning
5-2
EM 148-FC
Frequency Converter
A5E00065321-03
5.1
Operating procedure following voltage recovery
No
Only at initial commissioning or
reparameterization:
Configure and parameterize the
Frequency Converter
Set permissives:
Ctrl. word = 0000 1100 0111 0110
+
Specify setpoint value for motor
frequency
St. word = 0000 1011 0011 x001
St. bit 3 = 1?
Set operating condition
Ctrl. bit 0 = 1
Acknowledge fault
Ctrl. bit 7 = 1
Yes
Ready for operation
St. bit 1 = 1
Enable operation
Ctrl. bit 3 = 1
Yes
St. bit 2 = 1?
No
Ramp up
= Reaction of the
Frequency Converter
Ctrl. word
= Control word
Ctrl. bit
= Control bit
St. word
= Status word
St. bit
= Status bit
See Section 5.3 for further steps
Figure 5-1
Operating procedure following voltage recovery