CPU 1515SP PC2 (F/T/TF) 

42

 

Operating Instructions, 09/2018, A5E42603425-AA 

 

Commissioning 

8.1

 

Notes on commissioning 

 

 

WARNING 

Improper commissioning in hazardous areas 
Device failure or risk of explosion in hazardous areas. 

 

Do not commission the device unless it is fully mounted and connected according to the 

specifications in the section Wiring (Page 36). 

 

Before commissioning, please consider the effects on other devices in the plant. 

 

 

NOTICE 
Condensation in the device  
Damage to the device due to condensation if the temperature between transport or storage 

and the installation point differs. 
Before commissioning the device, leave it to stand until it is dry. 

 

 

NOTICE 
Data loss  
Data loss may occur if write filters are used incorrectly. 
Therefore, note the information on write filters. 
The following configurable write filter is available under Windows 10: 

 

Unified Write Filter (UWF) (Page 57) 

 

Содержание SIMATIC CPU 1515SP PC2 F

Страница 1: ......

Страница 2: ...__________ ___________________ ___________________ SIMATIC ET 200SP Open Controller CPU 1515SP PC2 F T TF Operating Instructions 09 2018 A5E42603425 AA Introduction 1 Safety information 2 Areas of application 3 Product overview 4 Application planning 5 Installation 6 Wiring 7 Commissioning 8 Interrupt error and system messages 9 Functions 10 Maintenance 11 Technical specifications 12 Dimension dra...

Страница 3: ...ly by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens prod...

Страница 4: ... of fail safe CPUs 17 3 2 Areas of application of technology CPUs 17 4 Product overview 18 4 1 Field of application 18 4 2 Characteristics 19 4 3 Sample configuration 20 4 4 Components 22 4 5 Operator controls and connection elements 24 4 6 Scope of delivery 27 5 Application planning 28 5 1 Basics 28 5 2 Unpacking the device 29 5 3 Identification data 30 5 4 Installation location 31 5 5 Hardware c...

Страница 5: ...en Controller on off 50 9 Interrupt error and system messages 51 9 1 Status and error display 51 10 Functions 54 10 1 Monitoring functions 54 10 1 1 Requirements 54 10 1 2 Temperature monitoring 55 10 1 3 Monitoring drives 55 10 1 4 Operating hours counter 55 10 2 Retentive memory NVRAM 55 10 3 BIOS setup 56 10 4 Power options 56 10 5 Unified Write Filter UWF write filter 57 11 Maintenance 58 11 1...

Страница 6: ...Technical specifications of CPU 1515SP PC2 HMI 2048PT 93 12 7 6 Technical specifications of CPU 1515SP PC2 F 97 12 7 7 Technical specifications of CPU 1515SP PC2 F HMI 128PT 101 12 7 8 Technical specifications of CPU 1515SP PC2 F HMI 512PT 105 12 7 9 Technical specifications of CPU 1515SP PC2 F HMI 2018PT 109 12 7 10 Technical specifications of CPU 1515SP PC2 T 113 12 7 11 Technical specifications...

Страница 7: ...ls supports you in commissioning the CPU 1515SP PC2 Basic knowledge required The system must be operated and used by qualified staff only The following knowledge is required Installation guideline for SIMATIC ET 200SP Totally Integrated Automation Portal in particular Hardware configuration with hardware and network editor Communication between CPUs PC based automation with an S7 1500 software con...

Страница 8: ...e A note contains important information on the product described in the documentation on the handling of the product or on the section of the documentation to which particular attention should be paid Scope of validity of the documentation This documentation is valid for the following products ET 200SP Open Controller Article number Standard CPU CPU 1515SP PC2 basic device 6ES7677 2DB40 0AA0 CPU 1...

Страница 9: ...nual https support industry siemens com cs ww en view 109755202 ET 200SP distributed I O system manual http support automation siemens com WW view en 58649293 ET 200SP server module manual http support automation siemens com WW view en 63257531 SIMATIC Safety Configuring and Programming http support automation siemens com WW view en 54110126 SIMATIC S7 1200 S7 1500 F CPUs http support automation s...

Страница 10: ...e product information free of charge from the Internet https support industry siemens com cs us en view 73021864 Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I O system gathered together in one file You can find the Manual Collection on the Internet http support automation siemens com WW view en 84133942 mySupport With myS...

Страница 11: ... application examples support you with various tools and examples for solving your automation tasks Solutions are shown in interplay with multiple components in the system separated from the focus in individual products You can find the application examples on the Internet https support industry siemens com sc ww en sc 2054 TIA Selection Tool With the TIA Selection Tool you can select configure an...

Страница 12: ...verted to UTC time to the module Program download to CPU Operating mode switchover RUN STOP Localization of the CPU by means of LED flashing Reading out CPU error information Reading the CPU diagnostic buffer Reset to factory settings Updating the firmware of the CPU and connected modules You can find the SIMATIC Automation Tool on the Internet https support industry siemens com cs ww en view 9816...

Страница 13: ...ssioning through importing and simulation of existing STEP 7 projects Efficiency through securing existing investments in the long term and optimal exploitation of resources You can find SINETPLAN on the Internet 1 2 Information about third party software updates This product contains third party software Siemens accepts liability with respect to updates patches for the third party software only w...

Страница 14: ...onents should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures e g firewalls and or network segmentation are in place For additional information on industrial security measures that may be implemented please visit https www siemens com industrialsecurity Siemens products and solutions undergo ...

Страница 15: ...nt NOTICE Protective measures To ensure safe operation of a plant you have to take suitable IT security measures for example network segmentation Seal the cover to protect the CFast card with the operating system of the CPU 1515SP PC2 from unauthorized access For more information on Industrial Security refer to the Internet http www siemens com industrialsecurity If you have questions about whethe...

Страница 16: ... when handling modules which are sensitive to ESD Before working with modules with ESD you need to ensure that you are free of electrostatic charge e g by touching a grounded object All devices and tools must be free of static charge Always pull the mains connector and disconnect the battery before installing or removing modules which are sensitive to ESD Handle modules fitted with ESDs only by th...

Страница 17: ...hich can be established by performing a functional test on the plant This allows errors in programming parameter assignment and wiring to be detected Documentation of the test results which can be entered if required into the relevant safety certificates NOTICE Ambient conditions Ambient conditions for which the device is not suitable can lead to faults or damage the device Note the following Only...

Страница 18: ...industry siemens com cs ww en view 109478599 3 2 Areas of application of technology CPUs Areas of application Areas of application of T CPUs are motion control applications such as gearing and camming as well as control of kinematics Due to the supported technology functions the S7 1500T CPUs are suitable for controlling packaging machines converting applications assembly automation etc You can op...

Страница 19: ...number The article number depends on the pre installed S7 1500 Software Controller and HMI Runtime You can find an overview of the article numbers in the section Scope of validity of the documentation Page 6 View of the module The following figure shows the CPU 1515SP PC2 Figure 4 1 CPU 1515SP PC2 with supplied accessories ...

Страница 20: ...An interface for the exchangeable ET 200SP BusAdapters for connection of PROFINET IO 2 ports Accessories spare parts Page 123 An interface for connecting devices using Industrial Ethernet Gigabit Ethernet 4 interfaces for USB devices 2 x USB 3 0 and 2 x USB 2 0 A DisplayPort interface DPP for a monitor A sealable slot for the CFast card A slot for an SD MMC card as additional optional drive Supply...

Страница 21: ... is formed with ET 200SP modules in the central rack You can also expand the CPU 1515SP PC2 with fail safe I O modules You can use the CPU 1515SP PC2 as PROFINET IO controller The PROFINET IO devices are connected via the ports of the X1 PN LAN interface using a SIMATIC BusAdapter Devices can be connected via Industrial Ethernet using the integrated interface X2 PN IE LAN The connection to PROFIBU...

Страница 22: ...Adapter ET 200AL modules with ET Connection Flat Panel Wide Screen Display USB devices Keyboard mouse printer Industrial Thin Client ITC SCALANCE W786 Field PG PROFINET IO device Camera PC Programming device Figure 4 2 Configuration example with the CPU 1515SP PC2 Reference You can find more information about configuring the ET 200AL modules in the system manual ET 200AL distributed I O system htt...

Страница 23: ...f the CPU 1515SP PC2 The following table provides an overview of the components of the CPU 1515SP PC2 Table 4 1 Components of the CPU 1515SP PC2 Component Function Figure Mounting rail in accordance with EN 60715 The mounting rail is the rack for the CPU 1515SP PC2 CPU 1515SP PC2 CPU with strain relief and white refer ence labels ...

Страница 24: ...nector BA SCRJ RJ45 As media converter for POF PCF fiber optic cable direct connec tion of the bus cable BA SCRJ FC For glass fiber optic cable BA 2xLC As media converter for glass fiber optic cable standard RJ45 con nector BA LC RJ45 As media converter for glass fiber optic cable direct connection of the bus cable BA LC FC For mixed configuration with an ET 200AL you require the BusAdapter BA Sen...

Страница 25: ...ing strips LEDs for the current operating state and diagnostic status of the CPU 1505SP Power LED Server module X50 Slot for the CFast card flash memory sealable Mode selector X51 Slot for an optional SD MMC card X80 Connector for 24 V DC supply voltage Cooling fins X1 PROFINET LAN Slot for BusAdapter for connection of PROFINET IO Status display for PROFINET X2 PN IE LAN GbE Ethernet connection wi...

Страница 26: ...DXC up to 2 TB USB connections 2 x USB 3 0 with Imax 1 A per interface 2 x USB 2 0 with Imax 0 5 A per interface MAC addresses The MAC address consists of a 3 byte manufacturer ID and a 3 byte device ID consecutive number Each device is already assigned four MAC addresses in the factory The front of the CPU 1515SP PC2 is lasered with the MAC address 1 and 4 With the MAC addresses 2 and 3 the conse...

Страница 27: ...the mode selector to set the CPU operating mode Table 4 3 Mode selector positions Position Meaning Description RUN Operating mode RUN1 The CPU is processing the user program STOP Operating mode STOP1 The CPU is not processing the user program The outputs are set to a safe state MRES Memory reset For active S7 1500 software controller2 only CPU memory reset 1 RUN and STOP indicate the selected oper...

Страница 28: ...ery of the CPUs CPU 1515SP PC2 basic device Strain relief with fixing screws Server module CFast card with the following pre installations Windows 10 IOT Enterprise operating system 64 bit S7 1500 Software Controller CPU 1505SP Optional only for CPU 1515SP PC2 CPU 1515SP PC2 F WinCC RT Advanced as of V15 Restore USB stick for image restore Windows Certificate of Authenticity CoA Certificate of Lic...

Страница 29: ...e control cabinet with at least IP54 degree of protection according to EN 60529 and take into consideration the ambient conditions for operating the devices Installation position You can install the ET 200SP distributed I O system in any position The preferred mounting position is horizontal mounting on a vertical wall Depending on the mounting position restrictions on ambient temperature and maxi...

Страница 30: ...age to the device during transport and storage If a device is transported or stored without packaging it is unprotected from shocks vibrations pressure and moisture Damaged packaging indicates that environmental conditions have already had a significant impact on the device The device might be damaged Do not dispose of the original packaging Pack the device for transport and storage NOTICE Damage ...

Страница 31: ...keep it locked up Have the device repaired without delay 5 3 Identification data The identification data can be used to clearly identify the device when a repair is necessary Note the following data Printed on the nameplate of the device please find the following information Article number Serial number The first and the last MAC address Depending on the scope of delivery the Certificate of Licens...

Страница 32: ... If the ET 200SP distributed I O system is exposed to vibration and shock loads both ends of the ET 200SP system assembly must be mechanically fixed to the mounting rail e g using 8WA1010 1PH01 ground terminals This measure prevents the ET 200SP from shifting to the side Note If the ET 200SP distributed I O system is exposed to high vibration and shock load we recommend that you screw the mounting...

Страница 33: ...SP PC2 there is a BaseUnit BU D with incoming supply voltage L light colored terminal box This is followed by BaseUnits BU B with dark colored terminal box The respective corresponding I O modules can be connected to the BaseUnits Suitable combinations of BaseUnits and I O modules can be found in the ET 200SP System Manual http support automation siemens com WW view en 84133942 The server module c...

Страница 34: ...onsumption of the components supplied via these I O modules The maximum current carrying capability of the terminals on the BaseUnit L ground is 10 A USB load When using the CPU 1515SP PC2 with the maximum configuration the USB load must also be considered Horizontal mounting Ambient temperature of 0 to 60 C with maximum 32 I O modules and 4 x low current 500 mA USB load Ambient temperature of 0 t...

Страница 35: ...e the BusAdapter Fixing strain relief Fix the strain relief to the top and bottom of the left hand side of the CPU 1515SP PC2 with the supplied screws Installing the CPU 1515SP PC2 1 Install the CPU on the mounting rail 2 Swivel the CPU back until you hear the mounting rail release click into place 3 To check that the CPU has correctly clicked into place pull on the underside of the enclosure Figu...

Страница 36: ...ff the supply voltage on the CPU 2 Press the mounting rail release button on the first BaseUnit and at the same time move the CPU parallel to the left until it comes off the rest of the module group Note The mounting rail release button is located above the CPU 3 While pressing the mounting rail release button on the CPU swivel the CPU out of the mounting rail Note It is not necessary to remove th...

Страница 37: ...gning interference free controllers function manual http support automation siemens com WW view en 59193566 NOTICE Risk of hazardous system states If you remove and insert I O devices with the supply voltage switched on this can result in hazardous system states Injury to persons and damage to the machine or plant could result Therefore I O devices can only be inserted and removed when the supply ...

Страница 38: ... 1 Backplane bus interface P2 PROFINET interface X1 Port 2 Internal supply voltage L 24 V DC supply voltage Mode selector M Ground X50 CFast card LK1 LK2 LED Link TX RX X51 SD MMC card LK3 LED Link X60 X61 USB 3 0 interfaces max 0 9 A R S RUN STOP LED yellow green X62 X63 USB 2 0 interfaces max 0 5 A ER ERROR LED red X70 DPP interface MT MAINT LED yellow X80 24 V DC Infeed of supply voltage PWR PO...

Страница 39: ...515SP PC2 F T TF 38 Operating Instructions 09 2018 A5E42603425 AA 7 3 Electrical configuration Non isolated configuration Note Unlike the ET 200SP distributed I O system the CPU 1515SP PC2 can only be operated with a non isolated configuration ...

Страница 40: ... there is a fixed connection between the ground infeed terminal and the contact springs to the mounting rail You must ground the mounting rail separately in the control cabinet Master switch Short circuit and overload protection Load current supply galvanic isolation This connection is established automatically with the CPU 1515SP PC2 The represented layout of the power connections does not corres...

Страница 41: ...E LAN 10 100 1000 Mbps for communication and data exchange with automation devices for example SIMATIC S7 Only ASCII characters are permitted in the name of the X2 PN IE LAN interface in the TIA Portal e g PROFINET_2 You need suitable software to do this STEP 7 WinCC SIMATIC NET Note Use a Category 5e Ethernet cable Cat 5e cable for operation with 1000 Mbps PROFINET PROFINET operation is possible ...

Страница 42: ...the scope of delivery WARNING Flying sparks due to loose cables Risk of explosion in hazardous areas USB cables and PROFINET connectors may detach from the device in the case of strong oscillation and high vibrating loads Attach these cables to the strain relief of the device using cable ties Requirements The strain relief is fixed to the CPU The CPU is installed Procedure Secure the USB and PROFI...

Страница 43: ...ing Page 36 Before commissioning please consider the effects on other devices in the plant NOTICE Condensation in the device Damage to the device due to condensation if the temperature between transport or storage and the installation point differs Before commissioning the device leave it to stand until it is dry NOTICE Data loss Data loss may occur if write filters are used incorrectly Therefore ...

Страница 44: ...ing commissioning Procedure When the requirements are met proceed as follows with the commissioning 1 Connect a monitor using a DisplayPort cable 2 Connect a keyboard and a mouse to the CPU via USB Result The Open Controller is prepared for commissioning 8 2 3 Commissioning procedure When you start up your CPU 1515SP PC2 for the first time basic settings and the administrator password are queried ...

Страница 45: ...will be prompted to restart the device NOTICE Faulty installation If you change the device during the installation the installation will be disrupted and the operating system will not be installed correctly The operational reliability of the device and the plant is endangered Do not switch off the device during the entire installation process Information on users user groups in Windows A user Oper...

Страница 46: ... Initial commissioning an open controller Step Execution Section 1 Creating the configuration of the Open Controller 8 3 1 Page 45 2 Setting the IP address 8 3 2 Page 46 3 Changing the properties of the Software Control ler 8 3 3 Page 46 4 Establishing the HMI connection 8 3 4 Page 47 5 Downloading a project to the target system 8 3 5 Page 47 6 Transferring the license key 8 3 6 Page 48 7 Switchin...

Страница 47: ...w CPU 1515SP PC2 CPU 1515SP PC2 F T TF CPU 1505SP F T TF Software Controller CPU 1515SP PC2 HMI CPU 1515SP PC2 F HMI CPU 1505SP F Software Controller and WinCC Runtime Advanced 7 Insert the server module from the hardware catalog The server module forms the termination of the CPU with the I O modules If no server module is configured the server module is added automatically during compiling 8 3 2 ...

Страница 48: ...is established between the two devices Reference You can find additional information on configuring an HMI connection in the TIA Portal online help or in the STEP 7 and WinCC Engineering V15 https support industry siemens com cs ww en view 109755202 system manual 8 3 5 Downloading a project to the target system Key statement To set up your automation system you need to download the project data yo...

Страница 49: ...d and compile the project The hardware configuration and the first download are now completed Reference Additional information on the possible options for downloading is available in the online help of the TIA Portal 8 3 6 Transferring license keys Licensing the software For the following products you need to transfer the product specific license key with the Automation License Manager ALM before ...

Страница 50: ...s transfer from local computer is disabled on the source computer drag the license keys from the USB stick to the system partition C of the CPU 1515SP PC2 Backing up license keys for restore and repair Note Loss of license keys A SIMATIC license key cannot be copied or duplicated No more license key copies exist on the USB stick once you have dragged the license keys from the USB stick to your CPU...

Страница 51: ...DOS starts 2 Select the mode in which the CPU 1515SP PC2 should start Default with the Windows operating system and the S7 1500 software controller Only with the Windows operating system e g with updates Switching off the CPU 1515SP PC2 Proceed as follows to switch off the CPU 1515SP PC2 1 Use the Windows function Start Power Shut down to switch off The PWR LED changes from green to yellow The Win...

Страница 52: ...errupt error and system messages 9 9 1 Status and error display LED display The following figure shows the LED displays of the CPU 1515SP PC2 RUN STOP LED yellow green LED ERROR LED red LED MAINT LED yellow LED POWER LED yellow green LED Figure 9 1 LEDs of the CPU 1515SP PC2 ...

Страница 53: ... Starting of the CPU 1515 SP PC2 in Windows only mode No power supply Software Controller of the CPU 1515SP PC2 is not downloaded is in the operating state Power OFF Use of the hardware LEDs was disabled con figuration via TIA Portal LED off LED flashes red LED off An error has occurred LED green LED off LED off Software Controller of the CPU 1515SP PC2 is in RUN mode LED green LED flashes red LED...

Страница 54: ... activities during STOP e g ramp up after STOP Loading the user program LED flashes yellow green LED off LED off Startup transition from STOP RUN LED flashes yellow green LED flashes red LED flashes yellow Startup CPU booting Test of LEDs during startup inserting a module LED flashing test LED flashes green LED flashes red LED flashes red CPU defective POWER LED Table 9 2 POWER LED POWER LED Meani...

Страница 55: ...ftware is included in the scope of delivery of the CPU 1515SP PC2 Use the DiagBase Management Explorer application to obtain a clearer overview for monitoring The DiagBase Alarm Manager notifies you of individual alarms Note For additional information refer to the online help for the SIMATIC IPC DiagBase software SIMATIC IPC DiagMonitor The SIMATIC DiagMonitor software is provided on a CD You can ...

Страница 56: ... With this function different parameters are queried in order to detect possible defects at an early stage This information is shown to the user with corresponding software 10 1 4 Operating hours counter You can use an operating hours counter for a variety of applications For calculating the operating time of the CPU For calculating the operating time of controlled equipment You can find more info...

Страница 57: ...ation The device configuration is preset for working with the supplied software Only change the set values if you have made technical changes to your device 10 4 Power options A power plan with the name SIMATIC S7 is set as default on the CPU 1515SP PC2 This ensures that the CPU does not deviate from its maximum clock rate in order not to endanger the real time capability of the software controlle...

Страница 58: ...sons To prevent data loss the CFast card must therefore be provided with special protection Use the UWF write filter to extend the service life of the CFast card and to avoid a possible failure of the CPU 1515SP PC2 Note Write protection is deactivated in the delivery state Note that the work memory is reduced when UWF is activated NOTICE Risk of data loss when UWF is activated If UWF is activated...

Страница 59: ...your own image of your CFast card This contains the operating system the Runtime software and the complete project loaded from the TIA Portal We recommend the SIMATIC IPC Image Partition Creator V3 5 software tool to back up data under Windows It provides for easy backup and fast restore of the contents of the CFAST card and of individual partitions images Note Data can only be backed up to a netw...

Страница 60: ...Name 30 GB CFast card File system C SYSTEM 19 5 GB NTFS D DATA 8 GB NTFS 0 4 GB RAW WinCCMB 0 04 GB NTFS Note Partitions under Windows 10 IoT Enterprise 64 bit The partitions need to be set again if they are faulty or if the partitioning is to be changed NOTICE CPU volume for S7 1500 Software Controller 0 4 GB RAW Do not change the CPU volume for software controllers This is the only way to ensure...

Страница 61: ... panel because the Multitouch driver is not available until after the installation of the operating system Requirements To restore the original software of the CPU 1515SP PC2 the following is required the supplied CFast card the supplied restore USB stick NOTICE Data loss During restoration of the system to delivery state the CFast card is completely erased and re formatted and is then loaded with...

Страница 62: ...ted 6 Press Esc to start the Boot Manager 7 Select the list entry for the USB stick in the Boot Manager 8 After the prompt confirm the start by pressing any key The loading process is displayed Windows logo The SIMATIC Restore menu opens Select a language Select CPU 1515SP PC2 F T TF or CPU 1515SP PC2 F HMI Select the option Completely restore system drive The original software is restored on Part...

Страница 63: ...r operation You can download the current driver software from SIMATIC Product Support 11 5 Windows 10 IoT Enterprise 64 bit The Windows 10 IoT Enterprise operating system 64 bit is pre installed on the CPU 1515SP PC2 Windows language packs English and German are available as the basic language for the installation of the Windows operating system After initial commissioning of the CPU 1515SP PC2 ad...

Страница 64: ... card with free memory See section Partitions in the delivery state Page 59 Make sure that sufficient free memory space is available on your CFast card for the installation of updates 11 6 Sending the device to customer service Before sending Before you send in the CPU 1515SP PC2 for repair Create a backup of your data Back up your SIMATIC license keys on a USB stick Remove your SD MMC cards Remov...

Страница 65: ...disconnected from the power supply Procedure Removing the CFast card 1 Remove the seal 2 Open the cover using a screwdriver if necessary 3 Press onto the CFast card The card is pressed out of the slot 4 Pull the card out of the slot To do this grip the rib on the underside of the memory card Procedure Inserting the CFast card 1 Open the cover of the slot using a screwdriver if necessary 2 Insert t...

Страница 66: ...Instructions 09 2018 A5E42603425 AA 65 11 8 Recycling and disposal For ecologically sustainable recycling and disposal of your old device contact a certificated disposal service for electronic scrap or dispose of the device in accordance with the regulations in your country ...

Страница 67: ... valid markings and approvals are printed on the CPU 1515SP PC2 Safety information WARNING Risk of personal injury and damage to property In hazardous areas there is a risk of injury or damage if you disconnect any connectors while the CPU 1515SP PC2 is in operation Always de energize the CPU 1515SP PC2 operated in such areas before you disconnect the connectors WARNING Flying sparks due to loose ...

Страница 68: ...y EMC Directive 2014 34 EU Equipment and protective systems intended for use in potentially explosive atmospheres Explosion Protection Directive 2011 65 EU Restriction of the use of certain hazardous substances in electrical and electronic equipment RoHS Directive 2006 42 EC Machinery Directive for fail safe modules The conformity declaration certificates are available for the responsible authorit...

Страница 69: ... in Class I Division 2 Groups A B C D Class I Zone 2 Group IIC or non hazardous locations WARNING EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE SEALING PROPERTIES OF MATERIALS USED IN THE RELAY FM approval Factory Mutual Research FM according to Approval Standard Class Number 3611 3600 3810 ANSI ISA 82 02 01 CSA C22 2 No 213 CSA C22 2 No 61010 1 APPROVED for use in Class I Division 2 Group A B C D Tx...

Страница 70: ...n of conformity for Australia New Zealand CPU 1515SP PC2 meets the requirements of the standard EN 61000 6 4 2007 A1 2011 Korea Certificate KCC REM S49 ET200SP Note that this device corresponds to limit class A in terms of the emission of radio frequency interference This device can be used in all areas except residential areas 이 기기는 업무용 A급 전자파 적합기기로서 판매자 또는 사용자는 이 점을 주의하시기 바라며 가정 외의 지역에서 사용하는 것을 ...

Страница 71: ...tly impact on residents If you want to use the CPU 1515SP PC2 in mixed areas you must ensure that its radio frequency interference emission complies with the limit classes of the EN 61000 6 3 generic standard Suitable measures for observing these limits for use in a mixed area are for example Installation of the CPU 1515SP PC2 in grounded control cabinets Use of noise filters in the supply cables ...

Страница 72: ... following table shows the electromagnetic compatibility of the CPU 1515SP PC2 with regard to pulse shaped disturbances Table 12 1 Pulse shaped disturbance Pulse shaped disturbance Test voltage corresponds to degree of se verity Electrostatic discharge according to IEC 61000 4 2 Air discharge 8 kV Contact discharge 4 kV 3 3 Burst pulses high speed transient disturbance according to IEC 61000 4 4 2...

Страница 73: ... coupling Table 12 3 Sinusoidal disturbance variables with RF coupling RF coupling according to IEC 61000 4 6 corresponds to degree of severity 10 kHz 150 kHz to 80 MHz 3 10 Vrms unmodulated 80 AM 1 kHz 150 Ω source impedance Emission of radio interference Interference emission of electromagnetic fields in accordance with IEC61000 6 4 measured at a distance of 10 m Table 12 4 Interference emission...

Страница 74: ...pplies to modules that are shipped and or stored in their original packaging Table 12 6 Shipping and storage conditions for modules Type of condition Permissible range Free fall in shipping package 1 m Temperature From 40 C to 70 C Barometric pressure from 1140 hPa to 660 hPa corresponds to an altitude of 1000 m to 3500 m Relative humidity 5 to 95 without condensation Sinusoidal vibrations accordi...

Страница 75: ...installation with maximum 64 I O modules 0 to 50 C for vertical installation with maximum 32 I O modules Operating conditions The CPU 1515SP PC2 is suitable for use in weather proof fixed locations The operating conditions are based on the requirements of DIN IEC 60721 3 3 Class 3M3 mechanical requirements Class 3K3 climatic requirements Mechanical ambient conditions The table below shows the mech...

Страница 76: ...bration 10 frequency sweeps per axis in each of 3 vertically aligned axes Shock Shock tested accord ing to IEC 60068 2 27 Type of shock Half sine Shock intensity 150 m s2 peak value 11 ms duration Direction of shock 3 shocks in each direction at each of 3 vertically aligned axes Climatic ambient conditions You can use the CPU 1515SP PC2 under the following climatic ambient conditions Table 12 9 Cl...

Страница 77: ...Pollution degree overvoltage category according to IEC 61131 Pollution degree 2 Overvoltage category II Protection class in accordance with IEC 61131 2 2007 The distributed I O system ET 200SP fulfills protection class I and includes parts of protection class II and III The CPU 1515SP PC2 is a part of protection class III The grounding of the mounting rail must meet the requirements for functional...

Страница 78: ...lerances listed in the following table Table 12 10 Rated voltage for operation Rated voltage Tolerance range 24 V DC 19 2 to 28 8 V DC 1 1 Static value Creation as functional extra low voltage with safe electrical isolation in accordance with IEC 60364 4 41 12 6 Use of the ET 200SP in zone 2 potentially explosive atmospheres See product information Use of subassemblies modules in a Zone 2 Hazardou...

Страница 79: ...01 Firmware version V2 5 Engineering with STEP 7 TIA Portal configurable integrated as of version V15 with HSP 255 Installed software Visualization No Control No Control elements Mode selector switch 1 Supply voltage Type of supply voltage 24 V DC permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Mains buffering Mains voltage failure st...

Страница 80: ...nt temperature typically Deviation per day max 10 s Typ 2 s Interfaces Number of industrial Ethernet interfaces 2 Number of PROFINET interfaces 1 Number of PROFIBUS interfaces 1 Via CM DP module Number of RS 485 interfaces 1 Via CM DP module Number of USB interfaces 4 2x USB 2 0 2x USB 3 0 on front side Video interfaces Graphics interface 1x DisplayPort 1 Interface Interface types Number of ports ...

Страница 81: ... 55 C with max 64 ET 200SP modules and 2x max 500 mA and 1x max 100 mA USB load horizontal installation min 0 C horizontal installation max 60 C vertical installation min 0 C vertical installation max 50 C With max 32 ET 200SP modules and 3x 100 mA USB load Ambient temperature during stor age transportation min 40 C max 70 C Peripherals Options Peripherals SD card Optionally for additional mass st...

Страница 82: ...figurable integrated as of version V15 with HSP 269 Installed software Visualization No Control S7 1500 Software Controller CPU 1505SP Control elements Mode selector switch 1 Supply voltage Type of supply voltage 24 V DC permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Mains buffering Mains voltage failure stored energy time 5 ms Input...

Страница 83: ...th UPS Yes all memory areas declared retentive with non volatile memory Yes Hardware configuration Integrated power supply Yes Number of DP masters Via CM 1 Rack Modules per rack max 64 CPU 1515SP PC 64 modules server module Number of lines max 1 Time of day Clock Type Hardware clock Backup time 6 wk At 40 C ambient temperature typically Deviation per day max 10 s Typ 2 s Interfaces Number of indu...

Страница 84: ...000 Mbit s Industrial Ethernet status LED No 3 Interface Interface types RS 485 Yes RS 485 Transmission rate max 12 Mbit s Interrupts diagnostics status information Diagnostics indication LED RUN STOP LED Yes ERROR LED Yes MAINT LED Yes Ambient conditions Ambient temperature during operation min 0 C max Up to 60 C with max 32 ET 200SP modules and 3x 100 mA USB load up to 55 C with max 64 ET 200SP ...

Страница 85: ...6ES7677 2DB42 0GB0 Ambient temperature during stor age transportation min 40 C max 70 C Operating systems Operating systems Windows 10 IoT Enterprise LTSB 2016 64 bit MUI Peripherals Options Peripherals SD card Optionally for additional mass storage Dimensions Width 160 mm Height 117 mm Depth 75 mm Weights Weight approx 0 83 kg ...

Страница 86: ...gurable integrated as of version V15 with HSP 269 Installed software Visualization WinCC Runtime Advanced V15 Control S7 1500 Software Controller CPU 1505SP Control elements Mode selector switch 1 Supply voltage Type of supply voltage 24 V DC permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Mains buffering Mains voltage failure stored ...

Страница 87: ...th UPS Yes all memory areas declared retentive with non volatile memory Yes Hardware configuration Integrated power supply Yes Number of DP masters Via CM 1 Rack Modules per rack max 64 CPU 1515SP PC 64 modules server module Number of lines max 1 Time of day Clock Type Hardware clock Backup time 6 wk At 40 C ambient temperature typically Deviation per day max 10 s Typ 2 s Interfaces Number of indu...

Страница 88: ...us LED No 3 Interface Interface types RS 485 Yes RS 485 Transmission rate max 12 Mbit s Interrupts diagnostics status information Diagnostics indication LED RUN STOP LED Yes ERROR LED Yes MAINT LED Yes Ambient conditions Ambient temperature during operation min 0 C max Up to 60 C with max 32 ET 200SP modules and 3x 100 mA USB load up to 55 C with max 64 ET 200SP modules and 2x max 500 mA and 1x ma...

Страница 89: ...2018 A5E42603425 AA Article number 6ES7677 2DB42 0GK0 Operating systems Operating systems Windows 10 IoT Enterprise LTSB 2016 64 bit MUI Peripherals Options Peripherals SD card Optionally for additional mass storage Dimensions Width 160 mm Height 117 mm Depth 75 mm Weights Weight approx 0 83 kg ...

Страница 90: ...gurable integrated as of version V15 with HSP 269 Installed software Visualization WinCC Runtime Advanced V15 Control S7 1500 Software Controller CPU 1505SP Control elements Mode selector switch 1 Supply voltage Type of supply voltage 24 V DC permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Mains buffering Mains voltage failure stored ...

Страница 91: ...th UPS Yes all memory areas declared retentive with non volatile memory Yes Hardware configuration Integrated power supply Yes Number of DP masters Via CM 1 Rack Modules per rack max 64 CPU 1515SP PC 64 modules server module Number of lines max 1 Time of day Clock Type Hardware clock Backup time 6 wk At 40 C ambient temperature typically Deviation per day max 10 s Typ 2 s Interfaces Number of indu...

Страница 92: ...us LED No 3 Interface Interface types RS 485 Yes RS 485 Transmission rate max 12 Mbit s Interrupts diagnostics status information Diagnostics indication LED RUN STOP LED Yes ERROR LED Yes MAINT LED Yes Ambient conditions Ambient temperature during operation min 0 C max Up to 60 C with max 32 ET 200SP modules and 3x 100 mA USB load up to 55 C with max 64 ET 200SP modules and 2x max 500 mA and 1x ma...

Страница 93: ...2018 A5E42603425 AA Article number 6ES7677 2DB42 0GL0 Operating systems Operating systems Windows 10 IoT Enterprise LTSB 2016 64 bit MUI Peripherals Options Peripherals SD card Optionally for additional mass storage Dimensions Width 160 mm Height 117 mm Depth 75 mm Weights Weight approx 0 83 kg ...

Страница 94: ...igurable integrated as of version V15 with HSP 269 Installed software Visualization WinCC Runtime Advanced V15 Control S7 1500 Software Controller CPU 1505SP Control elements Mode selector switch 1 Supply voltage Type of supply voltage 24 V DC permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Mains buffering Mains voltage failure stored...

Страница 95: ...th UPS Yes all memory areas declared retentive with non volatile memory Yes Hardware configuration Integrated power supply Yes Number of DP masters Via CM 1 Rack Modules per rack max 64 CPU 1515SP PC 64 modules server module Number of lines max 1 Time of day Clock Type Hardware clock Backup time 6 wk At 40 C ambient temperature typically Deviation per day max 10 s Typ 2 s Interfaces Number of indu...

Страница 96: ...us LED No 3 Interface Interface types RS 485 Yes RS 485 Transmission rate max 12 Mbit s Interrupts diagnostics status information Diagnostics indication LED RUN STOP LED Yes ERROR LED Yes MAINT LED Yes Ambient conditions Ambient temperature during operation min 0 C max Up to 60 C with max 32 ET 200SP modules and 3x 100 mA USB load up to 55 C with max 64 ET 200SP modules and 2x max 500 mA and 1x ma...

Страница 97: ...2018 A5E42603425 AA Article number 6ES7677 2DB42 0GM0 Operating systems Operating systems Windows 10 IoT Enterprise LTSB 2016 64 bit MUI Peripherals Options Peripherals SD card Optionally for additional mass storage Dimensions Width 160 mm Height 117 mm Depth 75 mm Weights Weight approx 0 83 kg ...

Страница 98: ...onfigurable integrated as of version V15 with HSP 269 Installed software Visualization No Control S7 1500 Software Controller CPU 1505SP F Control elements Mode selector switch 1 Supply voltage Type of supply voltage 24 V DC permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Mains buffering Mains voltage failure stored energy time 5 ms I...

Страница 99: ...ith UPS Yes all memory areas declared retentive with non volatile memory Yes Hardware configuration Integrated power supply Yes Number of DP masters Via CM 1 Rack Modules per rack max 64 CPU 1515SP PC 64 modules server module Number of lines max 1 Time of day Clock Type Hardware clock Backup time 6 wk At 40 C ambient temperature typically Deviation per day max 10 s Typ 2 s Interfaces Number of ind...

Страница 100: ...us LED No 3 Interface Interface types RS 485 Yes RS 485 Transmission rate max 12 Mbit s Interrupts diagnostics status information Diagnostics indication LED RUN STOP LED Yes ERROR LED Yes MAINT LED Yes Ambient conditions Ambient temperature during operation min 0 C max Up to 60 C with max 32 ET 200SP modules and 3x 100 mA USB load up to 55 C with max 64 ET 200SP modules and 2x max 500 mA and 1x ma...

Страница 101: ...2018 A5E42603425 AA Article number 6ES7677 2SB42 0GB0 Operating systems Operating systems Windows 10 IoT Enterprise LTSB 2016 64 bit MUI Peripherals Options Peripherals SD card Optionally for additional mass storage Dimensions Width 160 mm Height 117 mm Depth 75 mm Weights Weight approx 0 83 kg ...

Страница 102: ...figurable integrated as of version V15 with HSP 269 Installed software Visualization WinCC Runtime Advanced V15 Control S7 1500 Software Controller CPU 1505SP F Control elements Mode selector switch 1 Supply voltage Type of supply voltage 24 V DC permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Mains buffering Mains voltage failure sto...

Страница 103: ...with UPS Yes all memory areas declared retentive with non volatile memory Yes Hardware configuration Integrated power supply Yes Number of DP masters Via CM 1 Rack Modules per rack max 64 CPU 1515SP PC 64 modules server module Number of lines max 1 Time of day Clock Type Hardware clock Backup time 6 wk At 40 C ambient temperature typically Deviation per day max 10 s Typ 2 s Interfaces Number of in...

Страница 104: ...tus LED No 3 Interface Interface types RS 485 Yes RS 485 Transmission rate max 12 Mbit s Interrupts diagnostics status information Diagnostics indication LED RUN STOP LED Yes ERROR LED Yes MAINT LED Yes Ambient conditions Ambient temperature during operation min 0 C max Up to 60 C with max 32 ET 200SP modules and 3x 100 mA USB load up to 55 C with max 64 ET 200SP modules and 2x max 500 mA and 1x m...

Страница 105: ...2018 A5E42603425 AA Article number 6ES7677 2SB42 0GK0 Operating systems Operating systems Windows 10 IoT Enterprise LTSB 2016 64 bit MUI Peripherals Options Peripherals SD card Optionally for additional mass storage Dimensions Width 160 mm Height 117 mm Depth 75 mm Weights Weight approx 0 83 kg ...

Страница 106: ...figurable integrated as of version V15 with HSP 269 Installed software Visualization WinCC Runtime Advanced V15 Control S7 1500 Software Controller CPU 1505SP F Control elements Mode selector switch 1 Supply voltage Type of supply voltage 24 V DC permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Mains buffering Mains voltage failure sto...

Страница 107: ...with UPS Yes all memory areas declared retentive with non volatile memory Yes Hardware configuration Integrated power supply Yes Number of DP masters Via CM 1 Rack Modules per rack max 64 CPU 1515SP PC 64 modules server module Number of lines max 1 Time of day Clock Type Hardware clock Backup time 6 wk At 40 C ambient temperature typically Deviation per day max 10 s Typ 2 s Interfaces Number of in...

Страница 108: ...tus LED No 3 Interface Interface types RS 485 Yes RS 485 Transmission rate max 12 Mbit s Interrupts diagnostics status information Diagnostics indication LED RUN STOP LED Yes ERROR LED Yes MAINT LED Yes Ambient conditions Ambient temperature during operation min 0 C max Up to 60 C with max 32 ET 200SP modules and 3x 100 mA USB load up to 55 C with max 64 ET 200SP modules and 2x max 500 mA and 1x m...

Страница 109: ...2018 A5E42603425 AA Article number 6ES7677 2SB42 0GL0 Operating systems Operating systems Windows 10 IoT Enterprise LTSB 2016 64 bit MUI Peripherals Options Peripherals SD card Optionally for additional mass storage Dimensions Width 160 mm Height 117 mm Depth 75 mm Weights Weight approx 0 83 kg ...

Страница 110: ...nfigurable integrated as of version V15 with HSP 269 Installed software Visualization WinCC Runtime Advanced V15 Control S7 1500 Software Controller CPU 1505SP F Control elements Mode selector switch 1 Supply voltage Type of supply voltage 24 V DC permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Mains buffering Mains voltage failure st...

Страница 111: ...with UPS Yes all memory areas declared retentive with non volatile memory Yes Hardware configuration Integrated power supply Yes Number of DP masters Via CM 1 Rack Modules per rack max 64 CPU 1515SP PC 64 modules server module Number of lines max 1 Time of day Clock Type Hardware clock Backup time 6 wk At 40 C ambient temperature typically Deviation per day max 10 s Typ 2 s Interfaces Number of in...

Страница 112: ...tus LED No 3 Interface Interface types RS 485 Yes RS 485 Transmission rate max 12 Mbit s Interrupts diagnostics status information Diagnostics indication LED RUN STOP LED Yes ERROR LED Yes MAINT LED Yes Ambient conditions Ambient temperature during operation min 0 C max Up to 60 C with max 32 ET 200SP modules and 3x 100 mA USB load up to 55 C with max 64 ET 200SP modules and 2x max 500 mA and 1x m...

Страница 113: ...2018 A5E42603425 AA Article number 6ES7677 2SB42 0GM0 Operating systems Operating systems Windows 10 IoT Enterprise LTSB 2016 64 bit MUI Peripherals Options Peripherals SD card Optionally for additional mass storage Dimensions Width 160 mm Height 117 mm Depth 75 mm Weights Weight approx 0 83 kg ...

Страница 114: ...configurable integrated as of version V15 with HSP 269 Installed software Visualization No Control S7 1500 Software Controller CPU 1505SP T Control elements Mode selector switch 1 Supply voltage Type of supply voltage 24 V DC permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Mains buffering Mains voltage failure stored energy time 5 ms ...

Страница 115: ...with UPS Yes all memory areas declared retentive with non volatile memory Yes Hardware configuration Integrated power supply Yes Number of DP masters Via CM 1 Rack Modules per rack max 64 CPU 1515SP PC 64 modules server module Number of lines max 1 Time of day Clock Type Hardware clock Backup time 6 wk At 40 C ambient temperature typically Deviation per day max 10 s Typ 2 s Interfaces Number of in...

Страница 116: ...tus LED No 3 Interface Interface types RS 485 Yes RS 485 Transmission rate max 12 Mbit s Interrupts diagnostics status information Diagnostics indication LED RUN STOP LED Yes ERROR LED Yes MAINT LED Yes Ambient conditions Ambient temperature during operation min 0 C max Up to 60 C with max 32 ET 200SP modules and 3x 100 mA USB load up to 55 C with max 64 ET 200SP modules and 2x max 500 mA and 1x m...

Страница 117: ...2018 A5E42603425 AA Article number 6ES7677 2VB42 0GB0 Operating systems Operating systems Windows 10 IoT Enterprise LTSB 2016 64 bit MUI Peripherals Options Peripherals SD card Optionally for additional mass storage Dimensions Width 160 mm Height 117 mm Depth 75 mm Weights Weight approx 0 83 kg ...

Страница 118: ... configurable integrated as of version V15 with HSP 269 Installed software Visualization No Control S7 1500 Software Controller CPU 1505SP TF Control elements Mode selector switch 1 Supply voltage Type of supply voltage 24 V DC permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Mains buffering Mains voltage failure stored energy time 5 m...

Страница 119: ...with UPS Yes all memory areas declared retentive with non volatile memory Yes Hardware configuration Integrated power supply Yes Number of DP masters Via CM 1 Rack Modules per rack max 64 CPU 1515SP PC 64 modules server module Number of lines max 1 Time of day Clock Type Hardware clock Backup time 6 wk At 40 C ambient temperature typically Deviation per day max 10 s Typ 2 s Interfaces Number of in...

Страница 120: ...000 Mbit s Industrial Ethernet status LED No 3 Interface Interface types RS 485 Yes RS 485 Transmission rate max 12 Mbit s Interrupts diagnostics status information Diagnostics indication LED RUN STOP LED Yes ERROR LED Yes MAINT LED Yes Ambient conditions Ambient temperature during operation min 0 C max Up to 60 C with max 32 ET 200SP modules and 3x 100 mA USB load up to 55 C with max 64 ET 200SP ...

Страница 121: ... TF please also note the information in the F product information https support industry siemens com cs ww en view 109478599 Technical specifications You can find technical specifications of CPU 1505SP with the article number 6ES7672 5DC11 0YA0 on the Internet under the following link https support industry siemens com cs ww en pv 6ES7672 5DC11 0YA0 td You can find technical specifications of CPU ...

Страница 122: ...n drawings 13 13 1 CPU 1515SP PC2 This section contains a dimension drawing of the module mounted on a mounting rail Always observe the specified dimensions for installation in cabinets Dimension drawings of the CPU 1515SP PC2 Figure 13 1 Dimension drawing CPU 1515SP PC2 front view ...

Страница 123: ...Dimension drawings 13 1 CPU 1515SP PC2 CPU 1515SP PC2 F T TF 122 Operating Instructions 09 2018 A5E42603425 AA Figure 13 2 Dimension drawing CPU 1515SP PC2 side view ...

Страница 124: ...onnector and 1x FastCon nect FC connector for PROFINET 6ES7193 6AP40 0AA0 BA 2 RJ45 PROFINET BusAdapter with standard Ethernet socket 6ES7193 6AR00 0AA0 BA Send 1xFC 1x FastConnect connector for ET Connection 6ES7193 6AS00 0AA0 Server module 1 unit 6ES7193 6PA00 0AA0 Strain relief for CPU 1515SP PC2 A5E32291462 SIMATIC IPC Service USB flash drive 8 GB SLC pre installed BIOS MANAGER V3 3 Image Part...

Страница 125: ...es Field Services Technical Support spare parts and training offers Forums For answers and solutions concerning automation technology mySupport Your personal working area in Industry Online Support for messages support queries and configurable documents This information is provided by the Siemens Industry Online Support in the Internet http www siemens com automation service support A 2 Industry M...

Страница 126: ...C2 does not work CPU 1515SP PC2 is not supplied with power Check the power supply Time and or date of the CPU 1515SP PC2 not correct CPU 1515SP PC2 was not con nected for more than 6 weeks Check the settings in Windows USB device is not working USB power supply is overloaded Use an external power supply for the USB device see section Application planning Page 33 ...

Страница 127: ...nsitive to electro static charge EN European standard GbE Gigabit Ethernet GRUB GRUB2DOS GRand Unified Bootloader Boot Manager HMI Human Machine Interface User interface IEC International Electrotechnical Commission IM Interface module The interface module connects the ET 200SP distributed I O system with the IO controller and exchanges data with the I O modules via the backplane bus LAN Local Are...

Страница 128: ...in or work memory of a computer with direct access allow ing read access to data and editing RT Runtime SD Secure Digital card Memory card SELV Safety Extra Low Voltage Safety Extra Low Voltage electrical circuit in which the volt age cannot exceed 30 V AC RMS 42 4 V AC peak or 60 V DC under NORMAL CONDITIONS and CONDITIONS OF A SINGLE FAULT including ground faults in other circuits UL Underwriter...

Страница 129: ...onitor network address etc The data is stored in a configuration file and is used by the operating system to load the corresponding device drivers or assign device parameters Drivers Program sections of the operating system They convert data from the user programs to the specific formats required by the I O devices e g hard disks monitors printers Ethernet Local network bus structure for text and ...

Страница 130: ... hardware Power options The power options can be used to reduce the power consumption of the computer while still keeping it ready for immediate use In Windows via Start Control Panel Hardware and Sound Power Options Restart The restart of the company that is already in operation using for example the Ctrl Alt Del shortcut without switching off the power supply Restore USB stick You use the Restor...

Страница 131: ...erface for hard disk drives and optical drives with serial data transfer SETUP BIOS setup A program used to determine information on the device configuration The device configuration of the CPU 1515SP PC2 is preset Changes must be made whenever a memory expansion new modules or drives are to be activated ...

Страница 132: ... 64 Partitioning 59 remove 64 Characteristics Control cabinet 19 Degree of protection 19 General 19 Interfaces 19 Power supply 19 Pre installations 19 Climatic ambient conditions 75 CoA Certificate of Authenticity 126 Col Certificate of License 126 Commissioning Commissioning procedure 43 Creating the configuration 46 Notes 42 Operator user 44 Procedure 44 Requirements 43 Setting the IP address 46...

Страница 133: ...nctions 54 Operating hours counter 55 Power options 56 Retentive memory NVRAM 55 SIMATIC IPC DiagBase 54 SIMATIC IPC DiagMonitor 54 Temperature monitoring 55 G GbE Gigabit Ethernet 126 Gigabit Ethernet GbE 126 GRand Unified Bootloader GRUB GRUB2DOS 126 GRUB GRUB2DOS GRand Unified Bootloader 126 H HMI Human Machine Interface 126 HMI connection establish 47 HMI devices Updating software 62 Human Mac...

Страница 134: ...ion 28 Installing the CPU 34 Maximum configuration 28 Minimum clearances 32 Mounting rail 31 Required tool 34 Rules 32 Strain relief 41 Uninstalling the CPU 35 USB load 33 Mounting rail Mounting 31 Multi Media Card MMC 126 N Network connection HMI 47 Networks Ethernet 40 PROFIBUS 40 PROFINET 40 New Technology File System NTFS 126 Non Volatile Random Access Memory NVRAM 126 Notes on use 16 Ambient ...

Страница 135: ... SELV 127 Safety information 14 ESD guidelines 15 Repairs 14 Safe operation of a plant 14 Sample configuration 20 Configuration 20 Scope 7 Documentation 7 Scope of delivery 27 CPU 1515SP PC2 27 CPU 1515SP PC2 F 27 CPU 1515SP PC2 T 27 CPU 1515SP PC2 TF 27 Proof of license 27 SD Secure Digital card 127 Secure Digital card SD 127 SELV Safety Extra Low Voltage 127 Sending in the device 63 Shipping con...

Страница 136: ...Filter UWF 127 Universal Serial Bus USB 127 Updates for installing Windows 63 USB Universal Serial Bus 127 Use in industrial environments 70 in mixed areas 70 in residential areas 70 UWF Unified Write Filter 127 W Windows Installing updates 63 Language packs 62 Wiring 37 Block diagram 37 Pin assignment 37 Rules and regulations 36 Z zone 2 explosion proof atmosphere 77 ...

Отзывы: