Pulse-shaped disturbance
Tested at
● Symmetric interference
● 0.5 kV (without protective element - only power cable
tested)
● 1 kV (with protective elements)
High-energy current surge according to IEC 61000‑4‑5
The subsequent information applies to the following shielded connection cables to the CFU:
● PROFINET cable
● Fieldbus cable
Coupling (to shield)
● 2 kV (without protective element)
Sinusoidal disturbance
EMC performance of the described components in relation to sinusoidal disturbance variables:
The prerequisite for this is that the system complies with the relevant requirements and
guidelines relating to electrical equipment.
Sinusoidal disturbance variable
Tested at
HF radiation acc. to IEC 61000-4-3
Electromagnetic HF field, amplitude
modulated
● 80 MHz to 1000 MHz / 1.4 GHz to 2 GHz
● 10 V/m
● 80% AM (1 kHz)
HF coupling according to IEC 61000-4-6 ● 0.15 to 80 MHz
● 10 Vrms unmodulated
● 80% AM (1 kHz)
● 150 Ω source impedance
Emission of radio interferences
The following tables show the limits of the emission of electromagnetic fields to which the
described components adhere.
Table 12-8
Emission of electromagnetic interference to EN 55016: limit value class A, group 1
from 30 to 230 MHz
< 40 dB (μV/m)Q
from 230 to 1000 MHz
< 47 dB (μV/m)Q
measured at a distance of 10 m
Table 12-9
Emission of electromagnetic interference to EN 55016: limit value class A, group 1
from 30 to 230 MHz
< 52 dB (µV/m) to 45 dB (µV/m) quasi-peak
from 230 to 1000 MHz
< 52 dB (µV/m) quasi-peak
measured at a distance of 3 m
Technical specifications
12.1 General technical specifications
SIMATIC CFU
Commissioning Manual, 08/2019, A5E39252870-AD
159
Содержание Simatic CFU
Страница 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 34: ...Operation planning 4 9 Use in hazardous areas SIMATIC CFU 34 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 46: ...Operating modes and functions 5 4 Measure frequency SIMATIC CFU 46 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...