Diagnostics Using the User Program
10-2
DP/PA Link and Y Link Bus Couplings
A5E00193841-011
10.1
Structure of the slave diagnosis
Influencing factors
The structure of the slave diagnosis depends on whether the IM 157 is in S7
standard operation, in redundant operation on an S7-400H or in DP standard
master operation.
Diagnostic blocks in S7 standard operation and in redundant operation
The table below shows the length of the diagnostic blocks and their start
addresses in the diagnostic frame.
Table 10-1 Length and start addresses of the diagnostic blocks in S7 standard operation and in
redundant operation
Diagnostic block
Length in bytes
Start address in
non-redundant
mode
Start address in
redundant mode
Standard diagnosis
6
0
0
Module diagnosis
31
6
6
Module status
63
37
37
Status message
60
100
100
H Status
8
–
160
Interrupt section
(max. 63*)
(160*)
(168*)
Total length
160
(max. 223*)
168
(max. 231*)
*) Only if interrupts are reported
Diagnostic blocks in DP standard master operation
As of version 4, when the IM 157 is being configured via the device master file,
each diagnostic block (except for the standard diagnosis) can be selected to be
present or not. The sequence of the diagnostic blocks is fixed. The start address of
the individual diagnostic blocks in the diagnostic frame depends on which
diagnostic blocks have been selected.
The table below shows the length of the diagnostic blocks and examples of their
start addresses in the diagnostic frame for certain configurations.
Содержание Simatic 6ES7 157-0AC80-0 A0 Series
Страница 14: ...Contents xiv DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 42: ...Installation 3 12 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 70: ...Commissioning the DP PA Link 6 12 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 162: ...Technical Specifications B 40 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 170: ...Order Numbers and Accessories D 4 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 178: ...Glossary Glossary 8 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 182: ...Index Index 4 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...