switched off. For diagnostic messages which refer to individual channels, only the
corresponding digital input is affected.
Diagnostics
message
Error
code
Assignment
Meaning
Solution
Wire break
6
H
Digital input
Impedance of encoder circuitry is too
high
Use a different encoder type or
modify the wiring, for example,
using cables with a larger cross-
section
Wire break between the module and
sensor
Connect the cable
Channel not connected (open)
• Disable diagnostics
• Connect encoder contacts
with a 15 kΩ to 18 kΩ resistor
1
Parameter as‐
signment error
10
H
Module
• Parameter assignment does not
match the terminal block used
• Incorrect parameter assignment
• Correct the parameter assign‐
ment
• Check terminal block
2
Supply voltage
missing
11
H
Module
Missing or insufficient supply voltage
L+
• Check wiring of the supply
voltage L+ on the terminal
block
• Check the terminal block type
Channel/compo‐
nent temporarily
unavailable
1F
H
Module
Update of the firmware is being per‐
formed or has been canceled.
The module does not import any
process values during this time.
• Restart firmware update
• Wait for firmware update
Hardware inter‐
rupt lost
16
H
Module
Error is reported because the events
occur faster than they can be pro‐
cessed in the system
Module is faulty
100
H
Module
Internal module error has occurred
Replace I/O module
Retentive memo‐
ry in carrier mod‐
ule defective
154
H
Module
A memory block fault on the support
module was detected during start-up
Replace carrier module
Retentive memo‐
ry in the terminal
block defective
155
H
Module
A memory block fault on the terminal
block was detected during start-up
Replace terminal block
1
47 kΩ resistors can be used provided that the following supplementary conditions are complied with: Only singular structure
of the IO modules (no IO redundancy); the process cables are shielded; no certification required according to the following
standards: NE21 or Power Station 6100-6-5.
2
Only the terminal blocks (TB 45 ...) are suitable for use of IO modules in IO redundancy.
A.4
Maintenance events
Maintenance events
A maintenance event is generated whenever maintenance is required. The MT LED lights up on
the module.
Parameters, diagnostics messages and address space
A.4 Maintenance events
DI 8x24...125VDC HA
38
Equipment Manual, 10/2021, A5E39288633-AD
Содержание SIMATIC 6DL1131-6DF00-0EK0
Страница 6: ...Security information DI 8x24 125VDC HA 6 Equipment Manual 10 2021 A5E39288633 AD ...
Страница 8: ...Preface DI 8x24 125VDC HA 8 Equipment Manual 10 2021 A5E39288633 AD ...
Страница 10: ...2D Matrix code QR code EAN code DI 8x24 125VDC HA 10 Equipment Manual 10 2021 A5E39288633 AD ...
Страница 14: ...Product overview 4 3 Terminal blocks DI 8x24 125VDC HA 14 Equipment Manual 10 2021 A5E39288633 AD ...