Mounting system
Housing can be snapped onto
mounting rails
Dimensions (W x H x D)
45 x 129 x 160 mm
Weight
approx. 0.32 kg
ambient temperature for approbations
max. 40
°
C
SIMADYN
D
Plant/system
side 24 V DC
Plant/system side
48 V DC
Power supply
voltage (V
V
)
24 V DC
24 V DC
48 V DC
Permissible range
20 V to 30 V DC
18 V to 60 V DC
18 V to 60 V DC
Briefly t<500 ms
1.5 x U
rated
1.5 x V
rated
1.5 x V
rated
Current drain at the
nominal value
55 mA
300 mA
360 mA
The maximun current on connector X3 is 1 A, if this is th power supply for
several interface modules. The maximun current on connector X4 is 2 A,
if this is th power supply for several interface modules.
System/plant
side, 24 V DC
System/plant
side 48 V DC
No.
8
8
Output voltage for 1 signal
for 0 mA output current
(V
V
-0.6 V)
(V
V
-1.2 V)
for 20 mA output current
(V
V
-2.1 V)
(V
V
-2.0 V)
for 30 mA output current
(V
V
-2.7 V)
(V
V
-2.9 V)
Max. output current for 1 signal
System/plant side <20,4 V DC
20 mA
-
Output voltage for 0 signal
0 V
0 V
Max. output current (for 1 signal)
30 mA
1)
30
mA
2)
1)
The binary outputs are continuously short-circuit proof.
General data
ambient
temperature
Power supply
Binary outputs