background image

SIMADYN D
Digital Control System

I/O module  EB11

User Manual

Edition 05.95

DK-Nr. 231141

Содержание SIMADYN D EB11

Страница 1: ...SIMADYN D Digital Control System I O module EB11 User Manual Edition 05 95 DK Nr 231141 ...

Страница 2: ...rights are reserved in the event of the grant of a patent or the registration of a utility model or design We have checked the contents of this Manual to ensure that they coincide with the described hardware and software However deviations cannot be completely ruled out so we cannot guarantee complete conformance However the information in this document is regularly checked and the necessary corre...

Страница 3: ... information 1 1 Description 3 2 Module construction 3 3 Notes for the user 3 4 Technical specification 6 5 Connector pin assignments of the EB11 7 6 STRUC L menu of the EB11 module in the master program 8 7 Miscellaneous 9 7 1 Appendices 9 7 1 1 Figures 9 7 1 2 Drawings 9 8 ECB instructions 10 ...

Страница 4: ...Warning information Edition 05 95 Siemens AG Dk Nr 231141 SIMADYN D Hardware User Manual ...

Страница 5: ...t or relationship The sales contract contains the entire obligation of Siemens The warranty contained in the contract between the parties is the sole warranty of Siemens Any statements contained herein do not create new warranties nor modify the existing warranty Warning information W A R N I N G Electrical equipment has components which are at dangerous voltage levels If these instructions are no...

Страница 6: ... labels Warning indicates death severe personal injury or property damage can result if proper precautions are not taken CAUTION For the purpose of this User Manual and product labels Caution indicates that minor personal injury or material damage can result if proper precautions are not taken NOTE For the purpose of this User Manual Note indicates information about the product or the respective p...

Страница 7: ...assigned to which connector The inputs and outputs have a rated voltage of 24 V The inputs load the source with 5 mA and the outputs supply 50 mA 2 Module construction 1 plug in station corresponds to 1 1 3 SPS for standard plug in stations SIMADYN D local bus connection Programmable address decoder PAD with module identification 2 x 2 x 8 bit inputs 2 x 2 x 8 bit outputs switched off on thermal o...

Страница 8: ...e g by short circuit The LED of the appropriate connector turns on The output can be switched back to normal operation after cooling the output element by a few degrees Celsius This reset operation is normally be done by a test program running in the background It is called in time distances like the SIMADYN D monitor Therefore much variable periods can exist between the occurance of overload and ...

Страница 9: ... 40 way one to one connection SE8 6DD 1681 0AJ0 Eight binary inputs or outputs 10 way one to one connection SE4 1 6DD 1681 0AE1 Eight non floating binary inputs or outputs SE5 3 6DD 1681 0AF3 Eight 220 V floating binary inputs SE6 1 6DD 1681 0AG1 Eight floating binary outputs for max 220V SE37 6DD 1681 0DH0 Eight 24 V floating binary outputs SE41 1 6DD 1681 0EB1 Eight floating 48 V binary inputs S...

Страница 10: ...5 0 0 A N15 O 02 A P24 0 2 A from external supply current consumption of conn interf m current consumption of binary outputs BINARY INPUTS QUANTITY 32 INPUT VOLTAGE 24 V rated valu e FOR 0 SIGNAL 1 V to 6 V or binary inputs open FOR 1 SIGNAL 13 V to 33 V INPUT CURRENT AT 1 SIGNAL 5 mA typ DELAY TIME 200 us BINARY OUTPUTS QUANTITY 32 SUPPLY VOLTAGE RATED VALUE 24 V DC RIPPLE 3 6 V DC PERM RANGE 20 ...

Страница 11: ... 16 Output 14 X5 B 16 Output 14 X6 B 17 Output 15 X5 B 17 Output 15 X6 B 18 Output 16 X5 B 18 Output 16 X6 B 19 P external X5 B 19 P external X6 B 20 M external X5 B 20 M external X6 B 21 Output 1 X5 C 21 Output 1 X6 C 22 Output 2 X5 C 22 Output 2 X6 C 23 Output 3 X5 C 23 Output 3 X6 C 24 Output 4 X5 C 24 Output 4 X6 C 25 Output 5 X5 C 25 Output 5 X6 C 26 Output 6 X5 C 26 Output 6 X6 C 27 Output 7...

Страница 12: ... of the EB11 module in the master program EB11 binary I O module 1 L bus ISE 1C N ignore failed message RDYINT Y N X5C 8K binary inputs 1 X5D 8K binary inputs 2 X6C 8K binary inputs 3 X6D 8K binary inputs 4 X5A 8K binary outputs 1 X5B 8K binary outputs 2 X6A 8K binary outputs 3 X6B 8K binary outputs 4 See also description of master program ...

Страница 13: ...5 X 6 EB11 X 1 X 1 X 1 X 1 10 40 10 10 10 b Externe Anschlüsse external connections X 1 X 5 X 6 EB11 40 a Externe Anschlüsse external connections Figure 1 7 1 2 Drawings Block diagram 3GE 465 641 9002 00 SU Dimension drawing front plate and table of connectors used 3GE 465 641 9002 00 MB Location diagram EB11 3GE 465 641 9002 00 AO ...

Страница 14: ...th highly insulating materials e g plastic foils insulated desktops articles of clothing manufactured from man made fibers Boards must only be placed on conductive surfaces When soldering the soldering iron tip must be grounded Boards and components should only be stored and transported in conductive packaging e g metalized plastic boxes metal containers If the packing material is not conductive t...

Страница 15: ...ECB instructions Siemens AG Dk Nr 231141 Edition 05 95 11 SIMADYN D Hardware User Manual ...

Страница 16: ...CB instructions 12 Edition 05 95 Siemens AG Dk Nr 231141 SIMADYN D Hardware User Manual Drives and Standard Products Motors and Drives Systems Group Postfach 3269 D 91050 Erlangen System Based Technology ...