Commissioning
6.3 Switching off the charging station
SICHARGE D
76
Operating Instructions, 02/2021, 8EM5907-0AA00-1AA7.01
6.3
Switching off the charging station
To shut down the charging station properly, the charging station first needs to be set to
maintenance mode (ConfigMode) via the Configuration Backend. Active charging processes
are ended, and the circuit breaker disconnects the power lines for charging from the
supplying mains.
Then, the service personnel on location can open the door of the charging station. Supply to
the control system and the display is maintained. If the charging station must be
disconnected from the power supply for further work, e.g. to replace components, this is
done with the reboot command via the Configuration Backend. When the boot screen
appears on the display, the -FC12 fuse in the upper area must be actuated with the door
open. This is necessary to shut down the operating system correctly.
Then follow the five safety rules for working with electrical equipment. Disconnect the
charging station fully from the power via the upstream switching device.