Ground Current I
N
(Address, see
) This register contains the minimum values and the maximum values of the phase
current I
N
measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Bit
15
14
13
12
11
10
9
8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format
16-bit unsigned integer
Unit
1/10 A for solid and isolated/resonant connection
Range
0 to 9999 for solid connection
0 to 65535 for isolated/resonant connection
Active Power P1 for Phase 1
(Address, see
) This register contains the minimum values and the maximum values of the active
power for phase 1 measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Bit
15
14
13
12
11
10
9
8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format
16-bit signed integer
Unit
1/10 kW for 230-V sensor
1 kW for 3.25/√3 sensor, for 100/√3 sensor, and for 400/√3 sensor
Range
-32768 to 32767
Active Power P2 for Phase 2
(Address, see
) This register contains the minimum values and the maximum values of the active
power for phase 2 measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Refer to
Active Power P1 for Phase 1, Page 154
.
Active Power P3 for Phase 3
(Address, see
) This register contains the minimum values and the maximum values of the active
power for phase 3 measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Refer to
Active Power P1 for Phase 1, Page 154
.
Reactive Power Q1 for Phase 1
(Address, see
) This register contains the minimum values and the maximum values of the reactive
power for phase 1 measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Bit
15
14
13
12
11
10
9
8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format
16-bit signed integer
Unit
1/10 kVAr for 230-V sensor
1 kVAr for 3.25/√3 sensor, for 100/√3 sensor, and for 400/√3 sensor
Range
-32768 to 32767
Modbus Registers
B.8 Register-Type Data – Trailing Pointers
154
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
Содержание SICAM
Страница 8: ...8 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 11: ...Delivery 1 1 Delivery 12 1 SICAM Feeder Condition Monitor Manual 11 E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 92: ...92 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 170: ...170 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...