Energy Values
Table 1-9
Mapping for Energy Values
Index
MQTT
Name Q200
(Description)
Name IEC61850 (Name)
1P
3W1I
3W3I
3W2I
4W1I
4W3I
617
WPa_sup
7
MMTN1$ST$SupWh
–
MMTR1$ST
$SupWh$phsA
–
MMTR1$ST$SupWh
$phsA
618
WPb_sup
7
–
–
MMTR1$ST
$SupWh$phsB
–
MMTR1$ST$SupWh
$phsB
619
WPc_sup
7
–
–
MMTR1$ST
$SupWh$phsC
–
MMTR1$ST$SupWh
$phsC
620
WP_sup
–
MMTR1$ST$SupWh
621
WPa_dmd
7
MMTN1$ST$DmdWh
–
MMTR1$ST
$DmdWh$phsA
–
MMTR1$ST
$DmdWh$phsA
622
WPb_dmd
7
–
–
MMTR1$ST
$DmdWh$phsB
–
MMTR1$ST
$DmdWh$phsB
623
WPc_dmd
7
–
–
MMTR1$ST
$DmdWh$phsC
–
MMTR1$ST
$DmdWh$phsC
624
WP_dmd
–
MMTR1$ST$DmdWh
625
WQa_ind
7
MMTN1$ST$SupVArh
–
MMTR1$ST
$SupVArh$phsA
–
MMTR1$ST
$SupVArh$phsA
626
WQb_ind
7
–
–
MMTR1$ST
$SupVArh$phsB
–
MMTR1$ST
$SupVArh$phsB
627
WQc_ind
7
–
–
MMTR1$ST
$SupVArh$phsC
–
MMTR1$ST
$SupVArh$phsC
628
WQ_ind
–
MMTR1$ST$SupVArh
629
WQa_cap
7
MMTN1$ST
$DmdVArh
–
MMTR1$ST
$DmdVArh$phsA
–
MMTR1$ST
$DmdVArh$phsA
630
WQb_cap
7
–
–
MMTR1$ST
$DmdVArh$phsB
–
MMTR1$ST
$DmdVArh$phsB
631
WQc_cap
7
–
–
MMTR1$ST
$DmdVArh$phsC
–
MMTR1$ST
$DmdVArh$phsC
632
WQ_cap
–
MMTR1$ST$DmdVArh
633
WSa
7
MMTN1$ST$TotVAh
–
MMTR1$ST
$TotVAh$phsA
–
MMTR1$ST$TotVAh
$phsA
634
WSb
7
–
–
MMTR1$ST
$TotVAh$phsB
–
MMTR1$ST$TotVAh
$phsB
635
WSc
7
–
–
MMTR1$ST
$TotVAh$phsC
–
MMTR1$ST$TotVAh
$phsC
636
WS
–
MMTR1$ST$TotVAh
637
WP_SUP_TARIFF_1
TOUTariffMMTN1$ST
$SupWh
TOUTariffMMTR1$ST$SupWh
638
WP_DMD_TARIFF_1
TOUTariffMMTN1$ST
$DmdWh
TOUTariffMMTR1$ST$DmdWh
639
WQ_IND_TARIFF_1
TOUTariffMMTN1$ST
$SupVArh
TOUTariffMMTR1$ST$SupVArh
640
WQ_CAP_TARIFF_1
TOUTariffMMTN1$ST
$DmdVArh
TOUTariffMMTR1$ST$DmdVArh
1.10
7
For the phase values, phsA, phsB, or phsC is added but it does not exist in a IEC 61850 LN.
Data-Points Mapping
1.10 Energy Values
28
SICAM, Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97, Manual
E50417-H1040-C621-A2, Edition 01.2020