Operation and Display
4.3 Key Definition
SICAM P37, 3-phase Harmonic Power Meter, User Manual
E50417-H8940-C563-
4
, Release Date
06.2018
29
Key Setting Parameters
1. Key functions at parameter setting mode
Example 19:
This screen shows Device ID display items.
At cyclic display mode, press "
▲
" or "
▼
" to enter key display
mode, press "
" to switch to area B, and press "
▲
" or "
▼
"
to switch to Device ID display items. Device
ID=000000000001.
Example 20:
This screen shows error code display items.
At cyclic display mode, press "
▲
" or "
▼
" to enter key display
mode, and press "
" to switch to area B. Press "
▲
" or "
▼
"
again to switch to error code display items. "E" means fault
prompt, the 7 bits from right to left mean respectively phase A
loss, phase B loss, phase C loss, voltage phase inversion,
phase C reverse, phase B reverse, and phase A reverse. For
example, "E0110001" means phase B and phase C loss and
phase C reverse fault occurs.
Key symbol
▲
▼
Function
a) "
▲
" to switch digit or flip over;
b) "
▼
" to move cursor or flip over.
a) Press "
" and "
" at the same time to enter
setting screen.
b) Press "
" to enter next menu or "confirm" parameter
setting.
c) Press "
" to return to previous menu or "cancel" pa-
rameter setting
1
.
1.Press "
" once after adjusting parameters with "
▲
" and "
▼
" to display "Sure", and press "
" once
again to alter parameters. Pressing "
" immediately after "Sure" appears will cancel current alteration.