Technical Data
2.1 Technical Data
SICAM P30 P31 P32, 3-phase Current Power Meter, User Manual
E50417-H8940-C561-
, Release Date
10
2.1
Technical Data
■
Item
Technical Data
Product standard
IEC61557-12:2007
Input connection
3
phase, single phase
Measureme
nt
Current
Rated current I
n
: 1 A, 5 A
Measuring range: 0.015 A ... 6 A
Maximum measuring range: 9 A
Power consumption: < 0.
VA (
VLQJOHSKDVH#$
)
Accuracy: RMS 0.2%
Resolution: 0.001 A
Frequency: 45 Hz ... 65 Hz
Di
git
al sign
al
Binary output (optional)
2 electromagnetic relay output
Normal Open Contact
Contact capacity: AC 250 V /3 A, DC 30 V /3 A
Binary input (optional)
4 dry contact inputs
Opto-coupler isolation, 4,000 V
RMS
Co
mmun
ication
RS-485 port (optional)
Interface type: Twisted Pair, Half Duplex Transmission
Communication rate: 600 bps ... 38,400 bps
Protocol: Modbus-RTU
Environme
nt
Operating temp.
-25
℃
... +60
℃
Operating temp. limit
-35
℃
... +70
℃
Relative humidity
≤
95% (condensation free)
Others
Power supply
AC or DC
Max. input range: 40 V ... 420 V
Power consumption:
≤
W,
VA
Dimension
Overall dimension (mm): 96×96×95
Panel cut out size (mm): 92×92
IP53
Weight
Approx. 450 g