10 Calibration
10.3 Calibrating the Alternating Current Measuring Range
204
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
10.3
Calibrating the Alternating Current Measuring Range
Measurement Setup
Fig. 10-4
Measurement Setup for Calibrating the Alternating Current Measuring Range
Measuring Ranges
You can perform the calibration for the following alternating current measuring ranges
•
AC 1 A
•
AC 5 A
Calibration
To calibrate the alternating current measuring ranges, proceed as follows:
✧
Set up the measurement as shown in figure 10-4.
Reference
N
1
Current
Output
2
3
NOTE
Calibration is only possible with symmetrical phases (3 x 120°), see figure 10-4.
NOTE
If you use a testing instrument of the type OMICRON as a reference, then you must connect the connection N
of the current output with the protective ground terminal
of the SICAM MMU.