System Components

146

SICAM RTUs, SICAM AK 3 User Manual

Edition 07.2016, DC2-028-2.03

2.6

Migration-Peripheral Elements

Following peripheral elements of the product family SICAM AK can be used in SICAM AK 3, if
required.

 DI-2100

 DI-2110

 DI-2111

 MX-2400

When using these peripheral elements in SICAM AK 3 you need the belonging front panels:

Designation

Item-Number/MLFB

Front panel MX-2400

TC2-083 / 6MF13130CA830AA0

Front panel DI-2100

TC2-095 / 6MF13131CA050AA0

Front panel DI-2110

TC2-096 / 6MF13131CA060AA0

Front panel DI-2111

TC2-097 / 6MF13131CA070AA0

Note

Details about these boards can be found in following documents:

Document name

Item Number

SICAM AK System Description

MC2-021-2

SICAM AK User Manual

DC2-017-2

Содержание SICAM AK 3

Страница 1: ...RTUs SICAM AK 3 User Manual Preface Table of Contents Installation 1 System Components 2 Prepare Engineering 3 Engineering via SICAM TOOLBOX II 4 Service 5 Automation Units and Automation Net works 6 Licensing Agreement A ...

Страница 2: ...ormation provided in this manual is checked at regular intervals and any corrections that might become necessary are included in the next releases Any suggestions for improvement are welcome Subject to change without prior notice Document Label SICRTUs BHBSICAMAK3 ENG_V2 03 Edition 13 07 2016 Copyright Copyright Siemens AG 2016 The reproduction transmission or use of this document or its contents ...

Страница 3: ... for persons who are entrusted with installation operation and service of SICAM AK 3 systems Within this manual there are hints how to obtain information or files via the internet If you have no access please consult your project manager at Siemens Recommendations for Third Party Products Siemens does neither receive liability nor warranty for recommendations which are given or implied by this man...

Страница 4: ...Interoperability DC0 046 2 SICAM RTUs MODBUS Interoperability DC0 073 2 Ax 1703 IEC 60870 5 101 104 Interoperability DA0 046 2 You find current product information on our website www siemens com sicam Further Support For more information please contact our Customer Support Center Phone 49 0 180 524 70 00 Fax 49 0 180 524 24 71 charges depending on provider e mail support ic siemens com The Siemens...

Страница 5: ...y measures are not carried out Warning means that death serious bodily injury or considerable property damage can occur if the appropriate precautionary measures are not carried out Caution means that minor bodily injury or property damage could occur if the appropriate precautionary measures are not carried out Hint is important information about the product the handling of the product or the res...

Страница 6: ...tching components connected to the power supply Even after the supply voltage has been disconnected hazardous voltages can still be pre sent in the equipment capacitor storage Equipment with current transformer circuits must not be operated while open The limit values indicated in the manual or the operating instructions must not be exceed ed that also applies to testing and commissioning Danger C...

Страница 7: ...ct to the Open Source Software portions of the software The Open Source Software is licensed royalty free Insofar as the applicable Open Source Software License Conditions provide for it you can or der the source code of the Open Source Software from your Siemens sales contact against payment of the shipping and handling charges for a period of at least 3 years since purchase of the Product We are...

Страница 8: ...Open Source Software 8 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...

Страница 9: ...on 28 1 2 2 7 Examples for 19 Swing Frame Installation of 2 Board Racks 29 1 2 3 Install Board Rack CM 2844 30 1 2 4 Install Board Rack CM 2846 CM 2843 and CM 2848 32 1 2 4 1 19 Swing Frame Installation 32 1 2 4 2 Rear Panel Assembly 34 1 3 Installation and Removal of Modules 36 1 3 1 Preparations 36 1 3 1 1 Connect and put on Grounding Strap 36 1 3 1 2 Removing Front Panel 37 1 3 2 Installation 3...

Страница 10: ... 70 1 6 1 General 70 1 7 Power Supply 71 1 7 1 General 71 1 7 2 Possible Configurations 71 1 7 3 Install Power Supply 72 1 7 3 1 Installing First Power Supply 72 1 7 3 2 Installing Second Power Supply 73 1 7 4 Wiring of the Power Supply 73 1 8 Wiring Process Peripherals 74 1 8 1 General 74 1 8 2 Fitting Peripheral Cable 74 1 8 3 Removing Peripheral Cable 76 1 8 4 PIN Assignment Peripheral Cable 77...

Страница 11: ... 1 2 6 Optical Interface Multimode Fiber Optics with CM 0847 104 2 4 2 SM 0551 105 2 4 2 1 Block Diagram 105 2 4 2 2 Pin Assignment 106 2 4 2 2 1 Unbalanced Interchange Circuit V 24 V 28 106 2 4 2 2 2 Balanced Interchange Circuit X 24 X 27 106 2 4 2 2 3 Balanced Interface EIA 485 107 2 4 2 2 4 Balanced Interface EIA 422 107 2 4 2 2 5 Optical Interface Multimode Fiber Optics with CM 0821 107 2 4 2 ...

Страница 12: ...5 1 Front Panel 141 2 5 5 2 Block Diagram 142 2 5 5 3 Pin Assignment 143 2 5 5 4 External Circuitry 144 2 5 5 5 I O Assignment 145 2 5 5 5 1 Inputs 145 2 5 5 5 2 Outputs 145 2 6 Migration Peripheral Elements 146 2 7 Submodules 147 2 7 1 Glue Serial Number on Front Panel 147 2 7 2 SM 0570 147 2 7 2 1 Block Diagram 148 2 7 2 2 Connector to Carrier Module 148 2 7 2 3 External Circuitry 149 2 7 3 SM 0...

Страница 13: ...ion LAN WAN via Ethernet TCP IP 171 3 2 2 Logical Connection 172 3 3 Integrated Protocol SNMPv3 173 3 3 1 Download of the SICAM RTUs MIB Files 173 3 3 2 Import of the MIB Files in MIB Browser 173 3 3 3 Display of SNMP Variables in MIB Browser 174 3 4 SD Card 176 3 4 1 SD Card Reader Writer 176 3 5 Loadable Firmwares 177 3 6 Working with the SICAM TOOLBOX II 178 3 6 1 Engineering Procedure 178 3 6 ...

Страница 14: ...94 4 1 9 1 Loading Engineering Data 194 4 1 9 2 Parameter Comparison 195 4 1 9 3 Test Functions 196 4 1 9 3 1 Status Of Spontaneous Data Points 196 4 1 9 3 2 Simulation of Spontaneous Data Points 197 4 1 9 3 3 Check The Connection To Automation Units 197 4 1 9 4 Displaying Decentral Archive DEAR 198 4 2 Automation 199 4 2 1 Create Function Diagram FUD 200 4 2 1 1 Configuring External Signals 200 4...

Страница 15: ... 1 1 Interrogation of Firmware Revision 231 5 5 1 2 Import of Firmware into the SICAM TOOLBOX II 231 5 5 1 3 Loading of Firmware into the Target System 231 5 5 1 3 1 Load Firmware Online 232 5 5 1 3 2 Load Firmware Offline 232 5 5 2 Errors with Loading of Firmware 233 5 6 Remote Maintenance 234 5 6 1 Configuration of Server and Clients 234 6 Automation Units and Automation Networks 235 6 1 Configu...

Страница 16: ...tion of Static Routes 250 6 3 1 General 250 6 3 2 Configuration 250 6 3 3 Example A 251 6 3 4 Example B 252 6 4 Application Configuration of IPSEC VPN 253 6 4 1 SICAM AK 3 as Telecontrol Substation with IPSec VPN via fixed Network254 6 4 2 SICAM AK 3 as Telecontrol Substation with IPSec VPN via GPRS Router and ADSL network 255 6 4 3 SICAM AK 3 as Telecontrol Substation with IPSec VPN via GPRS Netw...

Страница 17: ...ernal Communication Connections 40 1 5 Wiring for the Reception of Time Signals 64 1 6 Wiring Watchdog and Error 70 1 7 Power Supply 71 1 8 Wiring Process Peripherals 74 1 9 Shielding and Protective Earthing 81 1 10 Labeling 82 1 11 Switching the System On and Off 83 This chapter describes the structure of the system SICAM AK 3 how and where it may be in stalled and how the wirings are to be accom...

Страница 18: ...CP 2019 DO 2210 AI 2301 AI 2300 SICAM AK PS 263x DI 2110 SICAM AK PS 263x SICAM AK PS 263x CP 2016 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 DI 2110 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 AI 2301 DI 2110 DI 2110 DI 2110 Mounting rack CM 2844 Master control element Slots for modules Mounting rack CM 2846 Power supply SICAM AK PS 263x SICAM AK PS 263x CP 2016 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 D...

Страница 19: ...on on the dimensions Further information can be found in the SICAM AK 3 System Description 1 1 2 CM 2846 Basic Board Rack 17 Slots The basic board rack CM 2846 has 17 slots for modules and 2 slots for power supplies in double euro format It serves for the equipment of basic modules and peripheral modules It can be used for 19 swing frame installation and rear panel assembly This example shows a bo...

Страница 20: ... section 1 2 2 Space Requirement you can find information on the dimensions Further information can be found in the SICAM AK 3 System Description 1 1 4 CM 2843 Expansion Board Rack 16 Slots The expansion board rack CM 2843 has 16 slots for modules and 2 slots for power supplies in double euro format It serves for the equipment of peripheral modules It can be used for 19 swing frame installation an...

Страница 21: ...nd peripheral modules The board rack is designed for 19 swing frame installation In section 1 2 2 Space Requirement you can find information on the dimensions Further information can be found in the SICAM AK 3 System Description Hint This board rack was primarily designed for the combined use with the SICAM AK basic system element CP 2017 PCCX25 in SICAM AK 3 It enables the installation of the con...

Страница 22: ... 19 swing frame installation but can optionally be expanded for rear panel installation Systems which use a CM 2844 board rack are designed for the rear panel installation Note The system SICAM AK 3 may only be installed horizontally 1 2 2 Space Requirement Certain minimum distances must be observed between board rack and adjacent equipment These minimum distances serve the installation and remova...

Страница 23: ... Edition 07 2016 1 2 2 1 CM 2844 Rear Panel Installation 280 258 266 430 30 Space needed for cabling Cabinet rear panel 3HU AI 2301 SICAM AK PS 263x CP 2016 DI 2110 DO 2210 AI 2300 AI 2301 CP 2019 SICAM AK PS 263x 295 266 415 190 35 282 435 minimum free space 3HU ...

Страница 24: ...r Panel Installation 280 258 266 430 30 Space needed for cabling Cabinet rear panel 3HU SICAM AK PS 263x SICAM AK PS 263x DI 2110 CP 2016 CP 2019 AI 2301 AI 2300 DO 2210 DI 2110 DI 2110 DI 2110 AI 2300 DI 2110 DI 2110 DI 2110 CP 2019 AI 2301 DO 2210 483 266 603 190 35 465 435 minimum free space 3HU ...

Страница 25: ...r Panel Installation 280 258 266 430 30 Space needed for cabling Cabinet rear panel 3HU SICAM AK PS 263x SICAM AK PS 263x DI 2110 CP 2016 CP 2019 AI 2301 AI 2300 DO 2210 DI 2110 DI 2110 DI 2110 AI 2300 DI 2110 DI 2110 DI 2110 CP 2019 AI 2301 DO 2210 483 266 603 190 35 465 435 minimum free space 3HU ...

Страница 26: ...46 CM 2847 CM 2848 19 Swing Frame Installation 280 258 266 430 30 Space needed for cabling Frame 3HU SICAM AK PS 263x SICAM AK PS 263x DI 2110 CP 2016 CP 2019 AI 2301 AI 2300 DO 2210 DI 2110 DI 2110 DI 2110 AI 2300 DI 2110 DI 2110 DI 2110 CP 2019 AI 2301 DO 2210 483 266 190 465 6HU 1HU 2HU 1HU ...

Страница 27: ...allation 280 258 266 430 30 Space needed for cabling Cabinet rear panel 3HU SICAM AK PS 263x SICAM AK PS 263x DI 2110 CP 2016 CP 2019 AI 2301 AI 2300 DO 2210 DI 2110 DI 2110 DI 2110 AI 2300 DI 2110 DI 2110 DI 2110 AI 2301 DO 2210 DI 2110 483 266 603 190 35 465 435 DI 2110 DI 2110 DI 2110 minimum free space 3HU ...

Страница 28: ...9 Swing Frame Installation 280 258 266 430 30 Space needed for cabling Frame 3HU 483 266 190 465 SICAM AK PS 263x SICAM AK PS 263x DI 2110 CP 2016 CP 2019 AI 2301 AI 2300 DO 2210 DI 2110 DI 2110 DI 2110 AI 2300 DI 2110 DI 2110 DI 2110 AI 2301 DO 2210 DI 2110 DI 2110 DI 2110 DI 2110 6HU 1HU 2HU 1HU ...

Страница 29: ...AM AK PS 263x CP 2016 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 DI 2110 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 SICAM AK PS 263x DI 2110 AI 2301 DI 2110 DI 2110 DI 2110 SICAM AK PS 263x DI 2110 DO 2210 AI 2300 AI 2301 DI 2110 DI 2110 DO 2210 AI 2300 SICAM AK PS 263x DI 2110 AI 2301 DI 2110 DI 2110 DI 2110 AI 2300 DI 2110 DI 2110 DI 2110 1HU 3 6HU 6HU 6HU 2HU 1HU 1HU 2HU ...

Страница 30: ...with wall bracket and cable strain relief Proceed as follows remove the wall bracket from the board rack Mark out the drill holes for the wall bracket on the rear panel of the cabinet according to the enclosed drilling diagram DC2 000 1 Drill the holes according to the specifications on the drilling diagram DEVICE EDGE WITHOUT MINIMUM SPACE WALL BRACKET ...

Страница 31: ...d tighten the fastening screws k Rear cover TC2 087 Mounting with conventional screws Mounting with self tapping screws Self tapping screw DIN7500 5x12 Contact washer Rear cover Cabinet rear panel Screw M5x12 or 16 DIN933 or DIN84 Nut M5 Cabinet rear panel Contact washer Rear cover Cabinet rear panel SICAM AK PS 263x CP 2016 DI 2110 DI 2110 CP 2019 DO 2210 AI 2301 AI 2300 SICAM AK PS 263x DI 2110 ...

Страница 32: ... only designed for 19 swing frame installation 1 2 4 1 19 Swing Frame Installation Proceed as follows Determine the position at which the board rack is to be installed please note thereby that a space of 3HU must be maintained above the board rack Screw the board rack to the 19 frame use therefore the M6x16 DIN 85 screws and the washers 6 4 KST DIN 125 at position and the ESD screw M6x14 at positi...

Страница 33: ...eparately EMC earthing strap 140 10 4 5 6 5 TF3 033 6MF13140DA330AA1 EMC earthing strap 300 16 6 5 8 5 TF3 031 6MF13140DA310AA1 Tighten front cover and cable entry panel 4 5 SICAM AK PS 263x SICAM AK PS 263x CP 2016 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 DI 2110 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 AI 2301 DI 2110 DI 2110 DI 2110 Wall bracket TC2 011 SICAM AK PS 263x SICAM AK PS 263x CP 2016 D...

Страница 34: ... fastening kit TC2 702 6MF13130CH020AA0 is necessary for rear panel installation of CM 2846 and CM 2843 Proceed as follows Mark out the drill holes for the wall bracket on the rear panel of the cabinet according to the enclosed assembly instruction C53207 A5703 E421 1A 7431 Drill the holes according to the specifications ...

Страница 35: ...racket and tighten the fastening screws k Cabinet rear panel Mounting with conventional screws Mounting with self tapping screws Self tapping screw DIN7500 5x12 Contact washer Rear cover Cabinet rear panel Screw M5x12 or 16 DIN933 or DIN84 Nut M5 Cabinet rear panel Contact washer Rear cover SICAM AK PS 263x SICAM AK PS 263x CP 2016 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 DI 2110 DI 2110 DO 2210 AI...

Страница 36: ...ap The grounding strap can be connected directly to the board rack The connection point is lo cated on the left side panel of the board rack Designation Item Number MLFB Grounding Strap TF3 133 6MF13140DB330AA0 ACHTUNG HANDHABUNGS VORSCHRIFTEN BEACHTEN ELEKTROSTATISCH GEFÄHRDETE BAUELEMENTE SICAM AK PS 263x SICAM AK PS 263x DI 2110 CP 2016 CP 2019 AI 2301 AI 2300 DO 2210 DI 2110 DI 2110 DI 2110 AI...

Страница 37: ...nsulation plate is included to these boards Further can be ordered with following number Insulation plate double euro format T12 001 6MF13010CA010AA0 Shielding plate holder TC2 099 4 pcs per insulation 6MF13133CA000AA0 There is no reinforced isolation between the peripheral circuits Therefore it is not allowed to protect each circuit within one board separately using various fuses The installation...

Страница 38: ...autonomous modules fail processing and com munication element peripheral element For the removal of a module you will need the unlocking tool TA2 105 This is included in the scope of supply of every board rack and must be inserted in the bracket provided on the board rack during installation Proceed as follows Connect put on grounding strap and remove front panel Position the unlocking tool betwee...

Страница 39: ...8 2 03 Edition 07 2016 Designation Item Number MLFB Extracting Tool for SICAM RTUs boards TA2 105 6MF13110CB050AA0 1 3 4 Mounting Front Panel Proceed as follows Position the front panel Tighten the screws 1 2 3 2 3 Profile rail Unlocking tool Unlocking block ...

Страница 40: ... with the external communication device Modem see section 1 4 5 Communication Cabling Note The following sections show how to built up communication connections with the SICAM AK 3 basic sys tem elements CP 2016 and CP 2019 For examples how to built up these communication connections with a SICAM AK basic system element CP 2017 in a SICAM AK 3 migration board rack CM 2847 look into the SICAM AK Us...

Страница 41: ...take place with the module removed SIM and module are connected by means of 3 connectors and 3 retainer clips The connect ors serve the mechanical and electrical connection of both components The clips provide an additional mechanical hold ACHTUNG HANDHABUNGS VORSCHRIFTEN BEACHTEN ELEKTROSTATISCH GEFÄHRDETE BAUELEMENTE CP 2016 Central processor CP 2019 processing and communication element Serial i...

Страница 42: ...tion Interfaces 4 interfaces are supplied on a BSE Their usage and assignment is as follows During the engineering with SICAM TOOLBOX II these interfaces are assigned to following protocol elements X0 PRE0 X1 PRE1 X2 PRE2 X3 PRE3 SM 2558 SM 0551 CP 2016 CP 2019 CP 2016 with SIM X0 1st on the BSE integrated LAN interface CP 2019 with SIM X1 2nd on the BSE integrated LAN interface X2 1st interface f...

Страница 43: ...ard modems and cables The following kinds of communication are shown Serial Communication Point to Point Traffic Multi Point Traffic Multi Point Traffic via Glass Fiber Optic and Star Connection Analog Dial Up Traffic Dial Up Traffic Dial Up Traffic GSM Serial communication with DMS Digital Multiplex System LAN Communication Ethernet TCP IP Field bus Communication PROFIBUS DP The board racks and t...

Страница 44: ...ard Modem and Cable for Multi Point and Point to Point Traffic Designation Item Number MLFB CE 0700 V 23 dedicated line modem f SICAM RTUs G21 200 6MF11020BC000AA0 Patch cable cat 5 4x2 1 m AWG26 7 2 m 3 m 5 m 10 m for cabinet internal wirings T41 255 6MF13040BC550AA0 T41 251 6MF13040BC510AA0 T41 252 6MF13040BC520AA0 T41 253 6MF13040BC530AA0 T41 254 6MF13040BC540AA0 ...

Страница 45: ...sion Maximal number of CE0700 which can be supplied 1 DCF77 and maximal number of CE 0700 which can be supplied CP 2016 CP 2019 X0 X1 X2 X3 X0 X1 X2 X3 CP 2016 with SM 2551 SM 0551 on SM 2558 or CP 2016 with CP 2019 with SM 2551 or CP 2019 with SM 0551 on SM 2558 Patch cable max 15 m Supply cable TA4 051 HSA50 Power Supply V 24 V 28 X1 PS 4620 CE 0700 24 VDC 100 240 VAC 100 353 VDC HSA 50S24 P CE ...

Страница 46: ...during configuration Fur ther pay attention to the maximal power consumption Accessories for External Power Supply of the Receiver Designation Item Number MLFB PS 4620 Additional power supply 24 60 VDC GA4 620 6MF11110EG200AA0 Power supply cable for modem and DCF77 receiver TA4 051 6MF13110EA510AA0 Power supply 115 230 VAC 100 375 VDC 24 VDC 50 W www mtm power de ...

Страница 47: ...ptics length max 0 5 km FO indoorcable 50 DUP LSOH FO outdoorcable 50 2FIB ARM FO connector ST 50 62 TF7 027 TF7 028 TF7 016 Fiber optics length max 1 5 km FO indoorcable 62 DUP LSOH FO outdoorcable 62 2FIB ARM FO connector ST 50 62 TF7 006 TF7 007 TF7 016 CP 2016 CP 2019 CP 2016 with SM 2551 SM 0551 on SM 2558 or CP 2016 with CP 2019 with SM 2551 or CP 2019 with SM 0551 on SM 2558 Fibre optics ma...

Страница 48: ... 5 1 3 Analog Dial Up Traffic Eurocom 24 Modem with external Power Supply Accessories see SICAM AK 3 System Description CP 2016 CP 2019 CP 2016 with SM 2551 SM 0551 on SM 2558 or CP 2016 with CP 2019 with SM 2551 or CP 2019 with SM 0551 on SM 2558 Power supply Eurocom 24 5 V max 5 m ...

Страница 49: ...User Manual 49 DC2 028 2 03 Edition 07 2016 Cable Circuitry Connection Board Eurocom 24 Modem 1 CTS 2 3 4 5 6 7 8 RTS DSR TXD RXD GND DCD 5VDC DTR 1 2 3 4 5 6 7 8 RTS 5VDC TXD RXD GND DCD DTR Modem Eurocom 9 CP 2016 CP 2019 Screen Screen ...

Страница 50: ...ly Accessories see SICAM AK 3 System Description WESTERMO TD 36 PSTN POWER CP 2016 CP 2019 X0 X1 X2 X3 X0 X1 X2 X3 CP 2016 with SM 2551 SM 0551 on SM 2558 or CP 2016 with CP 2019 with SM 2551 or CP 2019 with SM 0551 on SM 2558 Power supply Westermo TD 36 20 264 VAC 14 300 VDC TD 36 AV 10 30 VAC 10 60 VDC TD 36 LV max 25 m 4 ...

Страница 51: ... Circuitry Connection Board Westermo TD 36 a b CTS DSR RI 1 2 3 4 5 6 7 8 9 TXR TXR 1 1 2 2 3 4 5 6 12 48VDC 12 27VAC TD36LV 20 250VDC 24 240VAC TD36AV 5 6 4 1 8 7 2 3 RTS TXD RXD GND DCD DTR Modem Westermo TD 36 9 1 CTS 2 3 4 5 6 7 8 RTS DSR TXD RXD GND DCD DTR CP 2016 CP 2019 Screen ...

Страница 52: ...nalog GSM ISDN Accessories see SICAM AK 3 System Description WESTERMO IDW 90 ISDN RS 232 CP 2016 CP 2019 X0 X1 X2 X3 X0 X1 X2 X3 Power supply CP 2016 with SM 2551 SM 0551 on SM 2558 or CP 2016 with CP 2019 with SM 2551 or CP 2019 with SM 0551 on SM 2558 Westermo IDW 90 max 25 m 12 48 VAC 12 34 VAC IDW 90 LV ...

Страница 53: ...on Board ISDN Modem GND RXD RI 1 2 3 4 5 6 7 8 9 1 N 2 P 3 4 5 6 12 48VDC 12 34 VAC IDW90LV DSR CTS RTS DCD DTP TXD Modem Westermo IDW 90 1 CTS 2 3 4 5 6 7 8 RTS DSR TXD RXD GND DCD DTR CP 2016 CP 2019 7 8 RX n c RX n c n c n c TX TX 1 2 3 4 5 6 7 8 RX n c RX n c n c n c TX TX Screen Screen Screen Screen ...

Страница 54: ...4 5 1 5 Dial Up Traffic GSM Accessories see SICAM AK 3 System Description CP 2016 CP 2019 X0 X1 X2 X3 X0 X1 X2 X3 Power supply CP 2016 with SM 2551 SM 0551 on SM 2558 or CP 2016 with CP 2019 with SM 2551 or CP 2019 with SM 0551 on SM 2558 GSM Modem max 25 m 8 30 VDC Cinterion MC52i ...

Страница 55: ...tion function of the MC52i GSM modem controlled by SICAM RTUs GND RXD RI 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 U 8 30 VDC H DSR CTS RTS DCD DTR TXD Modem 1 CTS 2 3 4 5 6 7 8 RTS DSR TXD RXD GND DCD DTR CP 2016 CP 2019 GND V IGT_IN PD_IN Screen Screen Screen GND RXD RI 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 U 8 30 VDC H DSR CTS RTS DCD DTR TXD Modem 1 CTS 2 3 4 5 6 7 8 RTS DSR TXD RXD GND DCD DTR CP 2016 CP 2019 GN...

Страница 56: ...16 DC2 028 2 03 1 4 5 1 6 Serial communication with DMS Digital Multiplex System DMS U I A CP 2016 CP 2019 X0 X1 X2 X3 X0 X1 X2 X3 DMS UI A Interface 1 2 CP 2016 with SM 2551 SM 0551 on SM 2558 or CP 2016 with CP 2019 with SM 2551 or CP 2019 with SM 0551 on SM 2558 ...

Страница 57: ...ation SICAM RTUs SICAM AK 3 User Manual 57 DC2 028 2 03 Edition 07 2016 Cable Circuitry Connection Board DMS 1 CTS 2 3 4 5 6 7 8 RTS DSR TXD RXD GND DCD DTR CP 2016 CP 2019 1 2 3 4 5 6 7 25 TXD RXD GND Screen ...

Страница 58: ...M 2868 then you can connect the connection cable patch cable directly l to SICAM AK 3 Accessories see SICAM AK 3 System Description chapter Order Information C P 2016 C P 2019 X0 X1 X2 X3 X0 X1 X2 X3 SICA M T M 1 70 3 AC P C P 60 14 X1 X1 1 X4 X1 2 X 14 X16 X15 X13 W D ER X5 X3 X6 X1 0 SI M 1 P K L K L K P K R X E R x T X S I 3 S I 2 S I 1 S I 0 L O C FB M P R E 3 NC TB NC PWR 2 4 6 0 VDC SYNC PUS...

Страница 59: ...Installation SICAM RTUs SICAM AK 3 User Manual 59 DC2 028 2 03 Edition 07 2016 Cross Over Adapter RJ45 RJ45 Cable Assembly 10 m ...

Страница 60: ...20AA0 T41 253 6MF13040BC530AA0 T41 254 6MF13040BC540AA0 Patch cable Cat 5 4x2x0 5 1 5 m AWG24 3 m 5 m for cabinet external wirings TF5 200 6MF13140FC000AA0 TF5 201 6MF13140FC010AA0 TF5 202 6MF13140FC020AA0 Details for connections over 10 m can be taken from document Configuration Automation Units and Automation Networks Appendix A section Electrical Connection Cable longer than 10 m CP 2016 CP 201...

Страница 61: ...ion PROFIBUS DP For details about this kind of communication see following document SICAM RTUs SM 2558 DPMiA0 PROFIBUS DP Master with external Fieldbus Gateway netHOST DC0 139 2 CP 2019 SICAM AK PS 263x CP 2016 Hilscher netHOST X3 Fieldbus Profibus cable Patch cable CP 2016 with SM 2558 CP 2019 with SM 2558 ...

Страница 62: ...cher netHOST PROFIBUS Master NHST T100 DP DPM Art Nr 1890 410 red Art Nr 1891 410 dark gray www hilscher com Patch cable Cat 5 4x2 AWG26 7 1 m 2 m 3 m 5 m 10 m for cabinet internal wirings T41 255 6MF13040BC550AA0 T41 251 6MF13040BC510AA0 T41 252 6MF13040BC520AA0 T41 253 6MF13040BC530AA0 T41 254 6MF13040BC540AA0 ...

Страница 63: ...eans of cable fastener SICAM AK PS 263x CP 2016 DI 2110 DI 2110 CP 2019 DO 2210 AI 2301 AI 2300 Cable fastener Communication cables cable strain relief E SD EARTH FACILITY SICAM AK PS 263x CP 2016 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 DI 2110 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 SICAM AK PS 263x DI 2110 AI 2301 DI 2110 DI 2110 DI 2110 SICAM AK PS 263x DI 2110 DO 2210 AI 2300 AI 2301 DI 2110 D...

Страница 64: ...SYNC available over which the minute pulse or a serial time signal adjustable via jumper can be transmitted 4 3 2 1 SICAM AK PS 263x CP 2016 CM 2890 PS 4620 24 60VDC DCF77 RG58 OUT SYNC0 X3 2 OUT SYNC0 X3 1 CP 2016 DCF77 rod antenna Supply cable TA4 051 BNC connector RG58 Lightning protection N connector SYNC_GND X100 a4 bk whbu or SYNC_GND X100 c4 bu whye SYNC1 X100 a2 ye whbu or SYNC2 X100 c2 gn...

Страница 65: ...MLFB DCF77 receiver for DIN rail GA0 806 6MF11110AJ060AA0 Cable Designation Item Number MLFB CM 2890 Periphery cable Crimp 5 m 100 pins TC2 890 6MF13131CJ000AA0 Accessories for External Power Supply of the Receiver PS 4620 Additional power supply 24 60 VDC GA4 620 6MF11110EG200AA0 Supply cable for modem TA4 051 6MF13110EA510AA0 ...

Страница 66: ... receiver 1 5 2 1 Wiring for the Receipt of the Minute Pulse The minute pulse is supplied on the screw terminal on the front panel of the GPS164 receiver Accessories see SICAM AK 3 System Description 4 3 2 1 4 SICAM AK PS 263x CP 2016 CM 2890 CP 2016 RG58 24 VDC Ub Ub Lightning protection N connector BNC connector RG58 GPS164 receiver GPS167 antenna converter Power Supply SYNC_GND X100 a4 bk whbu ...

Страница 67: ...s for the SAT STRING must be made with software GPSMON32 as follows Format 7E2 Baud Rate 2400 Serial time signal per second Accessories see SICAM AK 3 System Description 4 3 2 1 4 4 3 2 1 SICAM AK PS 263x CP 2016 CM 2890 RG58 24 VDC SYNC COM 0 Ub Ub CP 2016 Lightning protection N connector BNC connector RG58 GPS164 receiver GPS167 antenna converter Power Supply SYNC1 X100 a2 ye whbu or SYNC2 X100 ...

Страница 68: ...l Edition 07 2016 DC2 028 2 03 Cable circuitry GPS164 CP 2016 GPS164 COM 0 1 2 3 4 5 6 7 8 9 TxD RxD GND X100 CM 2890 100 pol CP 2016 9 pol DSUB male SYNC1 X100 a2 ye whbu or SYNC2 X100 c2 gn whbu SYNC_GND X100 a4 bk whbu or SYNC_GND X100 c4 bu whye ...

Страница 69: ... 19 case for TCP IP networks with integrated HTTP Server The internal refer ence time is derived from a built in GPS receiver of the type GPS167 Accessories see SICAM AK 3 System Description SICAM AK PS 263x CP 2016 CP 2016 Switch Ethernet TCP IP 60870 5 104 Patch cable CP 2016 CP 2019 with SM 2558 LAN time server ...

Страница 70: ... Example Circuitry for External Alarm Annunciation System SICAM AK PS 263x CP 2016 CM 2890 CP 2016 bk rdye ER_NO X100 a24 gn rdgn ER_COM X100 a26 bu rdgn ER_NC X100 c24 bn rdgn ER_COM X100 c26 gn whbk WD_NO X100 a16 bu rdbu WD_COM X100 a18 bn whbk WD_NC X100 c16 ye rdbu WD_COM X100 c18 CP 2016 24 VDC X100 CM 2890 0 VDC WD_COM a 18 bu rdbu WD_NO a 16 gn whbk WD_NC c 16 bn whbk ER_COM a 26 gn rdgn E...

Страница 71: ...ply 110 220 VDC 230 VAC AK 3 GC2 632 6MF11130CG320AA0 H05 VV F 3G 2 5 flexible lead TF5 002 6MF13140FA020AA0 1 7 2 Possible Configurations Board Rack CM 2844 In the basic configuration the board rack is fitted with one power supply This is installed in the left slot A second power supply can be used for redundancy This is installed in the right slot SI CAM AK PS 26 3x CP 201 6 DI 21 10 DI 21 10 CP...

Страница 72: ...ocedure is equal for all board racks Thus it is shown only exemplary with a CM 2844 board rack 1 7 3 1 Installing First Power Supply The first power supply is installed in the left slot It needs to be pushed into the compartment and fastened with screws Then the wiring can be carried out Please refer also to sec tion 1 7 4 Wiring of the Power Supply Note In this case it is possible to install anot...

Страница 73: ...e compartment and fastened with screws Then the wiring can be carried out Please refer also to section 1 7 4 Wiring of the Power Supply 1 7 4 Wiring of the Power Supply The supply can be carried out with single leads of the type H07V K 2 5 or a cable of the type H05VV F3G 2 5 SICAM AK PS 263x SICAM AK PS 263x 1 2 2 Slot for 2 power supply nd PS 2630 X1 PS 2632 P N X1 schwarz Stromversorgung 24 60 ...

Страница 74: ...al Cable Caution The peripheral modules must NOT be installed in the board rack during the fitting of the associated pe ripheral cable The fitting is carried out by engaging the peripheral cable in the seating frame Proceed as follows Insert the peripheral cable into the board rack from below until the point of the grip flap is fixed between profile rail and seating frame In the case of wall mount...

Страница 75: ...n 07 2016 Then swing the peripheral cable forwards up to the stop Thereby the hook of the grip flap must be guided through the unlocking lever Now push the peripheral cable upwards Thereby grip flap and seating frame are finally fixed together ƒ 2 Hook Unlocking lever 3 ...

Страница 76: ...the fitting of the associated pe ripheral cable Push the unlocking lever of the seating frame slightly forwards and hold it in this position Pull the peripheral cable vertically 4 5mm downwards Swing the connector of the peripheral cable to the back ƒ the hook of the grip flap is thereby guided through the unlocking lever and pull it downwards out of the board rack 1 2 Unlocking lever 3 4 ...

Страница 77: ... SYNC_GND 11 wsge bl whye bu b4 no con b4 no con b4 no con b4 no con b4 IN IREF01 b4 12 bl wsge bu whye c4 no con c4 no con c4 no con c4 no con c4 IN IREF01 c4 SYNC_GND 13 wsge ge whye ye a5 IN D08 a5 OUT D05 a5 CB00 a5 IOM0 I O 0 IN V0 IN IREF0 no con IN IC0 a5 IN V04 a5 14 ge wsge ye whye b5 IN D09 b5 OUT D05 b5 CB01 b5 IOM0 I O 1 IN V0 IN IREF0 no con IN IC0 b5 IN V04 b5 15 wsge gn whye gn c5 I...

Страница 78: ...2 no con c12 no con c12 no con c12 IN IREF05 c12 37 wsbr br whbn bn a13 IN D24 a13 OUT D15 a13 CA08 a13 IOM1 I O 0 IN V0 IN IREF0 no con IN IC0 a13 IN V12 a13 38 br wsbr bn whbn b13 IN D25 b13 OUT D15 b13 CA09 b13 IOM1 I O 1 IN V0 IN IREF0 no con IN IC0 b13 IN V12 b13 39 wsbr sw whbn bk c13 IN D26 c13 OUT D16 c13 CA10 c13 IOM1 I O 2 no con IN V0 OUT V0 no con c13 IN V13 c13 40 sw wsbr bk whbn a14 ...

Страница 79: ...O 1 IN V0 IN IREF0 no con IN IC0 b21 IN V20 b21 63 rtge ge rdye ye c21 IN D42 c21 OUT D26 c21 CB18 c21 IOM2 I O 2 no con IN V0 OUT V0 no con c21 IN V21 c21 64 ge rtge ye rdye a22 IN D43 a22 OUT D26 a22 CB19 a22 IOM2 I O 3 no con IN V0 OUT V0 no con a22 IN V21 a22 65 rtge gn rdye gn b22 IN D44 b22 OUT D27 b22 CB20 b22 no con b22 IN IREF10 b22 66 gn rtge gn rdye c22 IN D45 c22 OUT D27 c22 CB21 c22 n...

Страница 80: ...7 b29 OUT D35 b29 CA25 b29 IOM3 I O 1 IN V0 IN IREF0 no con IN IC0 b29 IN V28 b29 87 rtbr br rdbn bn c29 IN D58 c29 OUT D36 c29 CA26 c29 IOM3 I O 2 no con IN V0 OUT V0 no con c29 IN V29 c29 88 br rtbr bn rdbn a30 IN D59 a30 OUT D36 a30 CA27 a30 IOM3 I O 3 no con IN V0 OUT V0 no con a30 IN V29 a30 89 rtbr sw rdbn bk b30 IN D60 b30 OUT D37 b30 CA28 b30 no con b30 IN IREF14 b30 90 sw rtbr bk rdbn c30...

Страница 81: ...t rack entry and then grounded on a large surface screening rail installed for this purpose 1 9 2 Protective Earthing Grounding When installing a SICAM AK 3 system attention is to be paid that the cabinet or rack used features a proper protective earthing grounding That means that all electrical conducting parts must be connected large surface and as short as possible with the existing grounding s...

Страница 82: ...K 3 system is to be labeled according to Standard The following labels are provided Region and Component Number Plant Designation Equipment Identification SICAM AK PS 263x SICAM AK PS 263x DI 2110 CP 2016 CP 2019 AI 2301 AI 2300 DO 2210 DI 2110 A B ABC R K 72 mm 72 mm Equipment identification Plant designation Region number Component number ...

Страница 83: ...ration of the error display as soon as all system elements have concluded the startup refer to section 5 2 Checks And System Dis plays This is also applicable analogously if only parts of the system are switched off and switched on again 1 11 2 Switching Off The switching off of the system takes place by disconnecting the voltage on all system parts With redundant power supply pay attention to ent...

Страница 84: ...Installation 84 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...

Страница 85: ...m Elements 90 2 3 Protocol Elements 98 2 4 Peripheral Elements 111 2 5 Migration Peripheral Elements 146 2 6 Submodules 147 2 7 Bus Interface Modules 158 This chapter describes the mechanical design of the modules of the system SICAM AK 3 connector pin assignments lighted display as well as block diagrams and external circuitries ...

Страница 86: ... on the front side of the housing The voltage output 5 V is galvanically insulated and protected against continued short circuit and is monitored on failure The power supplies can be connected in parallel to increase the operation reliability redun dancy 2 1 1 1 Front View PS 2630 PS 2632 SICAM AK PS 2630 RY X1 S N SICAM AK PS 2632 RY X1 L N S N ...

Страница 87: ... Filter Fuse Inrush reverse protection short protection Booster Holdup Caps VDCin VDCout 5V 24A galvanical insulation X99 T1 SVCC Booster Control OR ing Primary Control Secondary Control PIC Synchonous rectification main DC DC caps Main DC DC Main DC DC Control SVCC PVCC PVCC PVCC PVCC SVCC Auxiliary Supply V_Sense V_Sense ADR0 ADR1 ADR2 RxD TxD ...

Страница 88: ...t Filter Fuse Inrush Bridge Booster PFC Holdup Caps VACin Vout 5V 24A galvanical insulation X99 T1 SVCC Booster PFC Control OR ing Primary Control Secondary Control PIC Synchonous rectification main DC DC caps Main DC DC Main DC DC Control SVCC PVCC PVCC PVCC PVCC SVCC Auxiliary Supply V_Sense V_Sense ADR0 ADR1 ADR2 RxD TxD ...

Страница 89: ... supply connector X1 is assigned according to the following table PS 2630 PS 2632 Pin Signal Pin Signal 1 1 L 2 2 N 3 PE 3 PE The abbreviations have the following meaning Power Supply 24 to 60 VDC Power Supply 24 to 60 VDC L Power Supply 110 to 220 VDC 230 VAC N Power Supply 110 to 220 VDC 230 VAC PE Protective earth ...

Страница 90: ... ER1 OH X2 RTX X2 ACT2 ER2 LED display for protocol element 2 and 3 OH X3 meaning dependent on the installed protocol element RTX X3 see chapter Service section Operation And Display Elements ACT3 ER3 RES Reset SD SD Card SD Card in front panel CP 2016 AK3 Security not visible X4 USB interface X0 Interface protocol element 0 X1 Interface protocol element 1 X2 Interface protocol element 2 X3 Interf...

Страница 91: ...RE0 CP 2016 PRE1 PRE2 PRE3 PWR_GOOD X100 X99 OVER UNDER VOLTAGE Backplane PPC440EP Submodule SM 25xx optional Error X0 Watchdog Time sync Ax PE Bus external Ethernet switch X1 X2 X3 USB X4 SD Card Reset Engineering tool Status Alarm LEDs DC DC DC DC 5V 5V Node Bus HSL Bus internal SYS IO internal HSL Bus external FPGA CPLD Memory 3V3 GND 2V5 1V25 1V2 Ax PE Bus internal ...

Страница 92: ...17 a18 WD_COM b18 c18 WD_COM a19 b19 c19 a20 b20 c20 a21 b21 c21 a22 b22 c22 a23 b23 c23 a24 ER_NO b24 c24 ER_NC a25 b25 c25 a26 ER_COM b26 c26 ER_COM a27 b27 c27 a28 b28 c28 a29 b29 c29 a30 b30 c30 a31 b31 c31 a32 b32 c32 The abbreviations have the following meaning SYNC1 Synchronization input for 32 V SYNC2 Synchronization input for 33 V to 72 V SYNC_GND Ground for Synchronization input WD_NO Wa...

Страница 93: ...D 7 DCD 8 DTR The abbreviations have the following meaning TX Transmit data differential RX Receive data differential CTS Clear to Send RTS Request to send DSR Data Set Ready TXD Transmit data RXD Receive data GND Ground DCD Data Carrier Detect DTR Data Terminal Ready Engineering plug USB mini B X4 Pin Signal 1 VBUS Power Supply Host Device 2 D Data 3 D Data 4 NC not connected 5 GND Ground ...

Страница 94: ...s 94 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 2 2 1 4 LED Display Details about the meaning of the LEDs can be found in chapter Service section Operation And Display Elements Basic System Elements ...

Страница 95: ...lement 2 and 3 OH X3 meaning dependent on the installed protocol element RTX X3 see chapter Service section Operation And Display Elements ACT3 ER3 RES Reset X0 Interface protocol element 0 X1 Interface protocol element 1 X2 Interface protocol element 2 X3 Interface protocol element 3 S N Serial number SI2 Position for label with serial number of protocol element 2 SI3 Position for label with seri...

Страница 96: ...pends on the equipped SM 25xx PRE0 CP 2019 PRE1 PRE2 PRE3 PWR_GOOD Backplane X100 PPC440EP Submodule SM 25xx optional X0 Ax PE Bus external Ethernet switch X1 X2 X3 Reset Status Alarm LEDs DC DC DC DC 5V 5V Node Bus HSL Bus internal SYS IO internal HSL Bus external FPGA CPLD Memory 3V3 GND 2V5 1V25 1V2 Ax PE Bus internal OVER UNDER VOLTAGE ...

Страница 97: ...X3 Pin Ethernet V 28 RS232 1 TX CTS 2 TX RTS 3 RX DSR 4 TXD 5 RXD 6 RX GND 7 DCD 8 DTR The abbreviations have the following meaning TX Transmit data differential RX Receive data differential CTS Clear to Send RTS Request to send DSR Data Set Ready TXD Transmit data RXD Receive data GND Ground DCD Data Carrier Detect DTR Data Terminal Ready ...

Страница 98: ... 98 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 2 2 2 4 LED Displays Details about the meaning of the LEDs can be found in chapter Service section Operation And Display Elements Basic System Elements ...

Страница 99: ...ith up to 4 serial interfaces by equipping serial interface modules and the appropriate connection board This function can also be used in SICAM AK 3 when the SICAM AK 3 migration board rack CM 2847 is used CP 2017 has no RJ45 communication interfaces on the front panel These interfaces are sup plied on the additional required connection board CM 2838 Further it is necessary to mount one patch plu...

Страница 100: ...l element itself have neither a front panel nor LEDs to display status and functions Therefore they use the LEDs and front panel of the basic system elements The meaning of these LED displays is described there CP 2019 CP 2016 CP 2016 SIM CP 2019 SIM LEDs for local PRE Front panel CP 2016 LEDs for SIM Interfaces for local PRE Interfaces for SIM Front panel CP 2019 LEDs for local PRE LEDs for SIM I...

Страница 101: ...llable serial interface module SIM for CP 2016 and CP 2019 2 4 1 1 Block Diagram X0 X1 X2 X3 SM 2551 5 V 3 3 V local ethernet interfaces electical serial interfaces PRE2 PRE3 Basic system element PowerSupply galvanic insulation XC164 CPU Basic system Supplementary system element BUS XC164 CPU Basic system ...

Страница 102: ...ment depends on the operation mode of the supported protocols You find the information thereto in the SICAM AK 3 System Description chapter System Components and Technical Data section Protocol Elements 2 4 1 2 1 Unbalanced Interchange Circuit V 24 V 28 V 23 dedicated line VFT channel V 28 asynchronous 2 4 1 2 2 Balanced Interchange Circuit X 24 X 27 V 11 isochronous Pulse is transmitted Pulse is ...

Страница 103: ... SICAM AK 3 User Manual 103 DC2 028 2 03 Edition 07 2016 2 4 1 2 3 Balanced Interface EIA 485 V 11 asynchronous 2 4 1 2 4 Balanced Interface EIA 422 V 11 asynchronous 2 4 1 2 5 Optical Interface Multimode Fiber Optics with CM 0821 ...

Страница 104: ...8 2 03 2 4 1 2 6 Optical Interface Multimode Fiber Optics with CM 0847 RJ45 plug 8 pole RS232 V 24 electrical interface Pin Signal Meaning 1 not connected 2 not connected 3 5V 5V Versorgung 4 RxD Receive Data 5 TxD Transmit Data 6 GND Ground 7 not connected 8 not connected Legend ...

Страница 105: ...SIM installable on SM 2558 2 4 2 1 Block Diagram X0 X1 X2 X3 SM 2558 ZBG BUS 5 V ARM Cortex A9 Crypto Chip Ethernet PHY SM 0551 optional local ethernet interface electrical ethernet interface Basic system element Power Supply galvanic insulation XC164 CPU Basic system local ethernet interface optional serial interface PRE2 ...

Страница 106: ... depends on the operation mode of the supported protocols You find the information thereto in the SICAM AK 3 System Description chapter System Components and Technical Data section Protocol Elements 2 4 2 2 1 Unbalanced Interchange Circuit V 24 V 28 V 23 dedicated line VFT channel V 28 asynchronous 2 4 2 2 2 Balanced Interchange Circuit X 24 X 27 V 11 isochronous Pulse is transmitted Pulse is rece...

Страница 107: ... SICAM AK 3 User Manual 107 DC2 028 2 03 Edition 07 2016 2 4 2 2 3 Balanced Interface EIA 485 V 11 asynchronous 2 4 2 2 4 Balanced Interface EIA 422 V 11 asynchronous 2 4 2 2 5 Optical Interface Multimode Fiber Optics with CM 0821 ...

Страница 108: ...8 2 03 2 4 2 2 6 Optical Interface Multimode Fiber Optics with CM 0847 RJ45 plug 8 pole RS232 V 24 electrical interface Pin Signal Meaning 1 not connected 2 not connected 3 5V 5V Versorgung 4 RxD Receive Data 5 TxD Transmit Data 6 GND Ground 7 not connected 8 not connected Legend ...

Страница 109: ...odule SIM for CP 2016 and CP 2019 2 4 3 1 Block Diagram X0 X1 X2 X3 SM 2558 ZBG BUS 5 V ARM Cortex A9 Crypto Chip Ethernet PHY SM 0551 optional local ethernet interface electrical ethernet interface PRE3 Basic system element Power Supply galvanic insulation XC164 CPU Basic system local ethernet interface optional serial interface ...

Страница 110: ...rnet Interface RJ45 socket connector X3 on CP 2016 and CP 2019 Pin Signal Meaning 1 TxD Transmit Data 2 TxD Transmit Data 3 RxD Receive Data 4 not used 5 not used 6 RxD Receive Data 7 not used 8 not used 2 4 3 2 2 Serial Interface The serial interface X2 is provided by means of an attachable SM 0551 refer to 2 4 2 SM 0551 ...

Страница 111: ...ddress The peripheral element is coupled to the basic system element via the Ax 1703 peripheral bus The address of the peripheral element on the Ax 1703 peripheral bus is determined in SICAM TOOLBOX II when defining the Ax 1703 peripheral bus configuration This address is then set by means of the PBA switch ñ on the peripheral element ...

Страница 112: ...14 D15 D16 D17 D18 D19 D20 D21 D22 D23 D24 D25 D26 D27 D28 D29 D30 D31 D32 D33 D34 D35 D36 D37 D38 D39 D40 D41 D42 D43 D44 D45 D46 D47 D48 D49 D50 D51 D52 D53 D54 D55 D56 D57 D58 D59 D60 D61 D62 D63 DI 2114 RY S N ER D00 D01 D02 D03 D04 D05 D06 D07 D08 D09 D10 D11 D12 D13 D14 D15 D16 D17 D18 D19 D20 D21 D22 D23 D24 D25 D26 D27 D28 D29 D30 D31 D32 D33 D34 D35 D36 D37 D38 D39 D40 D41 D42 D43 D44 D45...

Страница 113: ...13010CA010AA0 Insulation plate holder TC2 099 4 pieces per insulation plate 6MF13133CA000AA0 There is no reinforced isolation between the peripheral circuits Therefore it is not allowed to protect each circuit within one board separately using various fuses AX peripheral bus X99 IN_D00 galvanical insulation Group 0 IN_D07 PM_0 COM_0 IN_D56 Group 7 IN_D63 PM_7 COM_7 Gr 1 Gr 6 Gr 2 Gr 3 Gr 4 Gr 5 X1...

Страница 114: ...3 2 5 2 3 Pin Assignment A 96 pin male connector according to DIN 41612 type C is used The peripheral connector s pin assignment is described in the following table The DI X2 column refers to the male connector of the peripheral connectors The abbreviations have the following meaning ...

Страница 115: ...example of the assignment of inputs and or outputs as well as their external circuitry Rules which must be considered for the assignment of the inputs and or outputs can be found in the following section double point information D00 D01 double point information D02 D03 A double point information occupies two binary inputs The order is important V V V V V V Zn Nr DI2100_EBE WMF ...

Страница 116: ...HW pin Data Point Single point information IN D00 IN D01 IN D63 Single point information D00 Single point information D01 Single point information D63 Double point information IN D00 IN D01 IN D02 IN D03 IN D62 IN D63 Double point information D00 D01 Double point information D02 D03 Double point information D62 D63 Integrated totals IN D00 IN D01 IN D63 Integrated total D00 Integrated total D01 In...

Страница 117: ... CB01 DI D34 D35 command CB02 CB03 DI D62 D63 command CB30 CB31 Double information to double command 2 pole DI D00 D01 command CA00 CB01 DI D02 D03 command CA02 CB03 DI D30 D31 command CA30 CB31 Predefined assignment to PCCO27 assigning commands in groups Type Predefined assignment Single information to single command 1 pole 1 5 pole SI D00 command CA00 SI D01 command CB00 SI D02 command CA01 SI D...

Страница 118: ...3 2 5 3 DO 2201 BISO25 2 5 3 1 Front Panel DO 2201 Board ready Error binary outputs 0 39 S N Serial number D0 2201 RY S N ER D00 D01 D02 D03 D04 D05 D06 D07 D08 D09 D10 D11 D12 D13 D14 D15 D16 D17 D18 D19 D20 D21 D22 D23 D24 D25 D26 D27 D28 D29 D30 D31 D32 D33 D34 D35 D36 D37 D38 D39 ...

Страница 119: ...System Components SICAM RTUs SICAM AK 3 User Manual 119 DC2 028 2 03 Edition 07 2016 2 5 3 2 Block Diagram ...

Страница 120: ...2 5 3 3 Pin Assignment A 96 pin male connector according to DIN 41612 type C is used The peripheral connector s pin assignment is described in the following table The DO 2201 X2 column refers to the male connector of the peripheral connectors The abbreviations have the following meaning ...

Страница 121: ...System Components SICAM RTUs SICAM AK 3 User Manual 121 DC2 028 2 03 Edition 07 2016 2 5 3 4 External Circuitry 1 pole output load on the plus pole DO 2201 EXT U EXT U OUT D00 OUT D00 OUT D39 OUT D39 ...

Страница 122: ...System Components 122 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 1 pole output load on the minus pole DO 2201 EXT U EXT U OUT D00 OUT D00 OUT D39 OUT D39 ...

Страница 123: ...System Components SICAM RTUs SICAM AK 3 User Manual 123 DC2 028 2 03 Edition 07 2016 2 pole output DO 2201 EXT U EXT U OUT D38 OUT D38 OUT D39 OUT D39 OUT D00 OUT D00 OUT D01 OUT D01 ...

Страница 124: ...ry information D10 Binary information D12 4 OUT D13 OUT D14 Binary information D13 Binary information D14 5 OUT D15 OUT D17 Binary information D15 Binary information D17 6 OUT D18 OUT D19 Binary information D18 Binary information D19 7 OUT D20 OUT D22 Binary information D20 Binary information D22 8 OUT D23 OUT D24 Binary information D23 Binary information D24 9 OUT D25 OUT D27 Binary information D...

Страница 125: ...0 Output relay 1 Error X3 Position for label with serial number of submodule SM 2506 S N Serial number D0 2210 RY S N IOM ER C00 C01 C02 C03 C04 C05 C06 C07 C08 C09 C10 C11 C12 C13 C14 C15 C16 C17 C18 C19 C20 C21 C22 C23 C24 C25 C26 C27 C28 C29 C30 C31 GRA GRB OR0 OR1 CE D0 2211 RY S N ER C00 C01 C02 C03 C04 C05 C06 C07 C08 C09 C10 C11 C12 C13 C14 C15 C16 C17 C18 C19 C20 C21 C22 C23 C24 C25 C26 C2...

Страница 126: ...e insulation plate is included to this board Further can be ordered with following number Insulation plate double Euro format T12 001 6MF13010CA010AA0 Insulation plate holder TC2 099 4 pieces per insulation plate 6MF13133CA000AA0 There is no reinforced isolation between the peripheral circuits Therefore it is not allowed to protect each circuit within one board separately using various fuses ...

Страница 127: ...6 2 5 4 3 Pin Assignment A 96 pin male connector according to DIN 41612 type C is used The peripheral connector s pin assignment is described in the following table The DO X2 column refers to the male connector of the peripheral connectors The abbreviations have the following meaning ...

Страница 128: ... 4 External Circuitry 32 2 pole commands measuring in the minus circuit Note The fused circuit with output relay OR0 must be used before the fused circuit with output relay OR1 U C00 C31 OR0 ext Uext COMA COMB CA00 CB00 GRA GRB CA31 CB31 VR OA0 OA1 DO 2210 A B B A position A only OR1 OA2 OA3 ...

Страница 129: ...6 32 2 pole commands measuring in the plus circuit Note The fused circuit with output relay OR0 must be used before the fused circuit with output relay OR1 U C00 C31 ext COMA COMB CA00 CB00 GRA GRB CA31 CB31 VR ref inverted Uext DO 2210 A B B A position B only OR0 OA0 OA1 OR1 OA2 OA3 ...

Страница 130: ...mmands relay common return on minus pole with 2 rail system Note The fused circuit with output relay OR0 must be used before the fused circuit with output relay OR1 U C00 C31 ext Uext COMA COMB CA00 0 CB00 GRA GRB CA31 CB31 VR ref inverted DO 2210 A B B A with 2 rail system OR0 OA0 OA1 OR1 OA2 OA3 ...

Страница 131: ...ands relay common return on minus pole with 1 rail system Note The fused circuit with output relay OR0 must be used before the fused circuit with output relay OR1 U C00 C31 ext Uext COMA COMB CA00 0 CB00 GRA GRB CA31 CB31 VR Ref invertiert DO 2210 A B B A mit 1 Schienen System OR0 OA0 OA1 OR1 OA2 OA3 ...

Страница 132: ... 2 03 64 1 pole commands relay common return on plus pole with 2 rail system Note The fused circuit with output relay OR0 must be used before the fused circuit with output relay OR1 U C00 C31 ext Uext COMA COMB CA00 CB00 GRA GRB CA31 CB31 VR DO 2210 A B B A OR0 OA0 OA1 OR1 OA2 OA3 ...

Страница 133: ... pole commands relay common return on plus pole with 1 rail system Note The fused circuit with output relay OR0 must be used before the fused circuit with output relay OR1 U C00 C31 ext Uext COMA COMB CA00 CB00 GRA GRB CA31 CB31 VR DO 2210 A B B A with 1 rail system OR0 OA0 OA1 OR1 OA2 OA3 ...

Страница 134: ...8 2 03 64 1 pole commands relay common return on minus pole Note The fused circuit with output relay OR0 must be used before the fused circuit with output relay OR1 U C00 C31 ext Uext COMA COMB CA00 0 CB00 GRA GRB CA31 CB31 VR ref inverted DO 2210 A B B A OR0 OA0 OA1 OR1 OA2 OA3 ...

Страница 135: ...dition 07 2016 64 1 pole commands relay common return on plus pole Note The fused circuit with output relay OR0 must be used before the fused circuit with output relay OR1 U C00 C31 ext Uext COMA COMB CA00 CB00 GRA GRB CA31 CB31 VR DO 2210 A B B A OR0 OA0 OA1 OR1 OA2 OA3 ...

Страница 136: ...ircuit each and measur ing in the minus circuit Note The fused circuit with output relay OR0 must be used before the fused circuit with output relay OR1 U C00 C30 ext Uext COMA COMB CA00 CB00 GRA GRB CA30 CB30 VR C01 CA01 CB01 C31 CA31 CB31 DO 2210 A B B A OR0 OA0 OA1 OR1 OA2 OA3 2 pole output circuit 1 pole output circuit Uext position A only ...

Страница 137: ... each and measur ing in the plus circuit Note The fused circuit with output relay OR0 must be used before the fused circuit with output relay OR1 U C00 C30 ext Uext COMA COMB CA00 CB00 GRA GRB CA30 CB30 VR C01 CA01 CB01 C31 CA31 CB31 DO 2210 A B B A OR0 OA0 OA1 OR1 OA2 OA3 2 pole output circuit 1 pole output circuit Uext position B only ref inverted ...

Страница 138: ...33 Command CB31 RI SI D63 Single command 2 pole CA00 CB00 CA01 CB01 CA30 CB30 CA31 CB31 Command CA00 CB00 RI SI D00 Command CA01 CB01 RI SI D01 Command CA30 CB30 RI SI D30 Command CA31 CB31 RI SI D31 Double command 1 pole and 1 pole CA00 CA01 CA02 CA03 CA30 CA31 Command CA00 CA01 RI DI D00 D01 Command CA02 CA03 RI DI D02 D03 Command CA30 CA31 RI DI D30 D31 CB00 CB01 CB02 CB03 CB30 CB31 Command CB0...

Страница 139: ...00 CSI SI D00 Command CA01 CB01 CSI SI D02 Command CA30 CB30 CSI SI D60 Command CA31 CB31 CSI SI D62 Double command 1 pole and 1 pole CA00 CB00 CA01 CB01 CA30 CB30 CA31 CB31 Command CA00 CB00 CSI DI D00 D01 Command CA01 CB01 CSI DI D02 D03 Command CA30 CB30 CSI DI D60 D61 Command CA31 CB31 CSI DI D62 D63 Double command 2 pole CA00 CB00 CA01 CB01 CA02 CB02 CA03 CB03 CA04 CB04 CA05 CB05 CA28 CB28 CA...

Страница 140: ... CB01 DI D34 D35 command CB02 CB03 DI D62 D63 command CB30 CB31 Double information to double command 2 pole DI D00 D01 command CA00 CB01 DI D02 D03 command CA02 CB03 DI D30 D31 command CA30 CB31 Assignment BISX26 to PCCO27 assigning commands in groups Type Assignment Single information to single command 1 pole 1 5 pole SI D00 command CA00 SI D01 command CB00 SI D02 command CA01 SI D03 command CB01...

Страница 141: ...f submodule IOM0 X8 Position for label with serial number of submodule IOM1 X9 Position for label with serial number of submodule IOM2 X10 Position for label with serial number of submodule IOM3 S N Serial number AI 2300 RY S N ER V00 V01 V02 V03 V04 V05 V06 V07 V08 V09 V10 V11 V12 V13 V14 V15 V16 V17 V18 V19 V20 V21 V22 V23 IOM3 IOM2 IOM1 IOM0 AI 2302 RY S N ER V00 V01 V02 V03 V04 V05 V06 V07 V08...

Страница 142: ...System Components 142 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 2 5 5 2 Block Diagram ...

Страница 143: ...16 2 5 5 3 Pin Assignment A 96 pin male connector according to DIN 41612 type C is used The peripheral connector s pin assignment is described in the following table The AI X2 column refers to the male connector of the peripheral connector The abbreviations have the following meaning ...

Страница 144: ...x Pt100 see section 2 7 3 3 External Circuitry SM 0572 Analog Output Extension 2x 20 mA 1 VDC 10 VDC see section 2 7 4 3 External Circuitry SM 0574 Count Pulse Input Extension 2x 24 60 VDC see section 2 7 5 3 External Circuitry IN V00 IN V00 IN V01 IN V01 IN V02 IN V02 IN V03 IN V03 IN V04 IN V04 IN V05 IN V05 IN V06 IN V06 IN V07 IN V07 IN V08 IN V08 IN V09 IN V09 IN V10 IN V10 IN V11 IN V11 IN V...

Страница 145: ...x I O 2 IOMx I O 3 IOMx I O 4 IOMx I O 5 IOMx I O 6 IOMx I O 7 Measured value IOMx I O 0 3 Measured value IOMx I O 4 7 Optional integrated totals via SM 0574 5 kHz 24 60 VDC IOMx I O 0 IOMx I O 1 IOMx I O 4 IOMx I O 5 Measured value IOMx I O 0 1 Measured value IOMx I O 4 5 x 0 3 2 5 5 5 2 Outputs HW Pin Data Point Optional setpoint values via SM 0572 20 mA 10 mA 5 mA 1 V 10 V IOMx I O 2 IOMx I O 3...

Страница 146: ...n using these peripheral elements in SICAM AK 3 you need the belonging front panels Designation Item Number MLFB Front panel MX 2400 TC2 083 6MF13130CA830AA0 Front panel DI 2100 TC2 095 6MF13131CA050AA0 Front panel DI 2110 TC2 096 6MF13131CA060AA0 Front panel DI 2111 TC2 097 6MF13131CA070AA0 Note Details about these boards can be found in following documents Document name Item Number SICAM AK Syst...

Страница 147: ...ach submodule in stalled on a peripheral element must be glued on the front panel of the carrier mod ule The label with the serial number is part of the submodule The label must be glued as shown in this example 2 7 2 SM 0570 The SM 0570 submodule analog input extension 2x 20 mA provides two analog inputs carrier module internal interface SM 0570 2 analog inputs ...

Страница 148: ...2 Connector to Carrier Module The pin assignment of the connector is described as follows Pin Alias Signal Pin Alias Signal 1 I O 0 IN V0 2 I O 1 IN V0 3 I O 2 4 I O 3 5 6 7 I O 4 IN V1 8 I O 5 IN V1 9 I O 6 10 I O 7 The abbreviations have the following meaning IN V0 IN V0 analog input 0 IN V1 IN V1 analog input 1 ...

Страница 149: ...3 External Circuitry Current Input 2 7 3 SM 0571 The SM 0571 submodule analog input extension 2xPt100 provides 2 resistance thermome ter inputs for Pt100 or Ni100 I O 0 AI 2300 IN V00 IN V00 IN V01 IN V01 SM 0570 A D I O 1 I O 4 I O 5 carrier module internal interface SM 0571 2 analog inputs ...

Страница 150: ...e pin assignment of the connector is described as follows Pin Alias Signal Pin Alias Signal 1 I O 0 IN IREF0 2 I O 1 IN IREF0 3 I O 2 IN V0 4 I O 3 IN V0 5 6 7 I O 4 IN V1 8 I O 5 IN V1 9 I O 6 IN IREF1 10 I O 7 IN IREF1 The abbreviations have the following meaning IN IREFx reference current IN Vx measuring circuit voltage x number of input 0 1 ...

Страница 151: ...ology Connecting Resistance Thermometers in 3 Wire Technology I O 1 SICAM RTUs Pt100 Ni100 IN IREF0 IN V0 IN V0 SM 0571 IN IREF0 Pt100 Ni100 IN IREF1 IN V1 IN V1 IN IREF1 I O 3 I O 2 I O 0 I O 7 I O 5 I O 4 I O 6 SM 0571 Pt100 Ni100 Pt100 Ni100 IN IREF0 IN V0 IN V0 IN IREF0 IN IREF1 IN V1 IN V1 IN IREF1 I O 1 I O 3 I O 2 I O 0 I O 7 I O 5 I O 4 I O 6 SICAM RTUs ...

Страница 152: ...e Technology 2 7 4 SM 0572 The SM 0572 submodule analog output extension 2x 20 mA 1 V 10 V provides two ana log outputs Pt100 Ni100 Pt100 Ni100 SM 0571 I O 1 IN IREF0 IN V0 IN V0 IN IREF0 IN IREF1 IN V1 IN V1 IN IREF1 I O 3 I O 2 I O 0 I O 7 I O 5 I O 4 I O 6 SICAM RTUs carrier module internal interface SM 0572 2 analog outputs ...

Страница 153: ...nector to Carrier Module The pin assignment of the connector is described as follows Pin Alias Signal Pin Alias Signal 1 I O 0 2 I O 1 3 I O 2 OUT V0 4 I O 3 OUT V0 5 6 7 I O 4 8 I O 5 9 I O 6 OUT V1 10 I O 7 OUT V1 The abbreviations have the following meaning OUT V0 OUT V0 analog output 0 OUT V1 OUT V1 analog output 1 ...

Страница 154: ...16 DC2 028 2 03 2 7 4 3 External Circuitry Current Output Voltage Output SICAM RTUs OUT V0 OUT V0 OUT V1 OUT V1 SM 0572 500 max 500 max R L R L I O 2 I O 3 I O 6 I O 7 Ω Ω SICAM RTUs OUT V0 OUT V0 OUT V1 OUT V1 I O 2 R L R L 1 k min 1 k min I O 3 I O 6 I O 7 SM 0572 Ω Ω ...

Страница 155: ...put extension 2x 24 60 VDC provides 2 pulse in puts can be used as 2 counter inputs or 1 counter input plus 1 control input in order to drive up to 2 counters pulse counting It is used for modular extension of peripheral modules carrier module internal interface SM 0574 2 pulse inputs 2 counter inputs or 1 counter input 1 control input ...

Страница 156: ...ule The pin assignment of the connector is described as follows Pin Alias Signal Pin Alias Signal 1 I O 0 IN IC0 2 I O 1 IN IC0 3 I O 2 4 I O 3 5 6 7 I O 4 IN IC1 8 I O 5 IN IC1 9 I O 6 10 I O 7 The abbreviations have the following meaning IN IC0 IN IC0 pulse input 0 counter input IN IC1 IN IC1 pulse input 1 counter input or control input ...

Страница 157: ...onents SICAM RTUs SICAM AK 3 User Manual 157 DC2 028 2 03 Edition 07 2016 2 7 5 3 External Circuitry Count pulse input SICAM RTUs SM 0574 I O 0 I O 1 IN IC0 I O 4 I O 5 IN IC0 IN IC1 IN IC1 5 9 3 7 8 9 5 9 3 7 8 9 ...

Страница 158: ...AM AK 3 User Manual Edition 07 2016 DC2 028 2 03 2 8 Bus Interface Modules 2 8 1 CM 0843 The bus interface module CM 0843 serves for the electrical connection of up to 4 remotely in stalled SICAM TM peripheral elements 2 8 1 1 Front Panel ...

Страница 159: ...System Components SICAM RTUs SICAM AK 3 User Manual 159 DC2 028 2 03 Edition 07 2016 2 8 1 2 Block Diagram ...

Страница 160: ...onents 160 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 2 8 1 3 Pin Assignment and Display The pin assignment of the connector is described as follows The abbreviations have the following meaning ...

Страница 161: ...system element and bus interfaces or peripheral elements is set up may be maximum 3 m long each The DIN rails of all CM 0843 and all PE 6410 must have the same ground potential SICAM AK PS 263x CP 2016 DI 2110 DI 2110 CP 2019 DO 2210 AI 2301 AI 2300 1 4 CM 0843 Ax 1703 peripheral bus electrical 16 Mbps patch cable length up to 3 m max 8 I O modules Ax 1703 peripheral bus electrical 16 Mbps USB cab...

Страница 162: ... The bus interface module CM 0842 serves for the optical connection of up to 4 remotely in stalled SICAM TM peripheral elements 2 8 2 1 Front Panel 2 8 2 2 Configuration Switch S1 Note In SICAM AK 3 the Ax 1703 peripheral bus is operated exclusively with 16 Mbps The bit rate must be set accordingly ...

Страница 163: ... 2 8 2 3 Pin Assignment and Display The pin assignment of the connector is described as follows The abbreviations have the following meaning Note The address bits of the segments A0_2 A1_2 and A2_2 are not used in SICAM AK 3 The settings of A0 A1 and A2 are not effective in SICAM AK 3 ...

Страница 164: ...263x CP 2016 DI 2110 DI 2110 CP 2019 DO 2210 AI 2301 AI 2300 SIC AM 17 03 SIC AM 17 03 Ax 1703 peripheral bus electrical 16 Mbps patch cable length up to 3 m Ax 1703 peripheral bus electrical 16 Mbps USB cable length up to 3 m Ax 1703 peripheral bus optical 16 Mbps optical fibre length up to 200 m max 8 I O modules 1 4 CM 0842 CM 0843 1 4 PS 663x PS 663x PE 6410 PE 6411 12 9 1 15 7 16 8 ...

Страница 165: ...element and bus interfaces or peripheral elements is set up may be maximum 3 m long each The DIN rails of all CM 0842 must have the same ground potential 16 Peripheral Elements optically connected SICAM AK PS 263x CP 2016 DI 2110 DI 2110 CP 2019 DO 2210 AI 2301 AI 2300 SICAM 1 70 3 SICAM 1 70 3 Ax 1703 peripheral bus electrical 16 Mbps patch cable length up to 3 m Ax 1703 peripheral bus optical 16...

Страница 166: ...System Components 166 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...

Страница 167: ... TOOLBOX II 168 3 2 Connect Engineering PC with a Target System 170 3 3 Integrated Protocol SNMPv3 173 3 4 SD Card 176 3 5 Loadable Firmwares 177 3 6 Working with the SICAM TOOLBOX II 178 This chapter describes with which methods the system SICAM AK 3 can be parameterized and programmed and which tools are designed for that ...

Страница 168: ...and Maintenance Computer OPM II Object Oriented Process Data Manager CAEx plus Tool for the creation of an application program as function diagram FUD structured text ST sequential function chart SF Alternatively an existing and compatible instruction list IL can be stored in the SICAM TOOLBOX II The toolsets are also available as Light version With this version the engineering is limited to maxim...

Страница 169: ...the installation of the SICAM TOOLBOX II the following preconditions are required DVD or BlueRay drive must be existing C drive must exist Administrator rights for operating system Windows read and write rights to the file sys tem and the Windows Registry No other SICAM TOOLBOX II version may be installed NTFS partition Minimum 5 GB free hard disk memory Minimum 2 GB installed main memory Supporte...

Страница 170: ...onnection The following connection options are available Directly via the USB interface on the master control element Remote operation LAN WAN via Ethernet TCP IP 3 2 1 1 Directly via the USB Interface SICAM TOOLBOX II PC and SICAM AK 3 are connected direct via the USB cable Designation Item Number MLFB CM 0825 TC0 825 6MF13130AJ250AA0 SICAM AK PS 263x CP 2016 DI 2110 DI 2110 CP 2019 DO 2210 AI 23...

Страница 171: ... remote operation the SICAM TOOLBOX II is not connected directly to SICAM AK 3 with a local connection but with TCP IP over a network interface SICAM AK PS 263x CP 2016 DI 2110 DI 2110 CP 2019 D O 2210 AI 2301 A I 2300 Zone A SICAM TOOLBOX II SICAM AK 3 LAN WAN Ethernet TCP IP Zone B TOOLBOX II Revision License Pak Version 5 Siemens AG X0 X1 ...

Страница 172: ...nection with a remote automation unit that one which can be accessed via a local au tomation unit thereby a continuous remote communication according to IEC 60870 5 101 or 104 is required SICAM AK PS 263x CP 2016 D I 2110 D I 2110 C P 2019 DO 2210 AI 2301 AI 2300 SICAM AK PS 263x CP 2016 D I 2110 D I 2110 C P 2019 DO 2210 AI 2301 AI 2300 TOOLBOX II Revision License Pak Version 5 Siemens AG TOOLBOX...

Страница 173: ...the download you get the file SICAMRTUs_SNMP_MIB_V03 00 00 zip Save this file on the computer where the MIB browser is installed Then open the file and start the therein contained file SICAMRTUs_SNMP_MIB_V03 00 00 exe by means of double click Now the SICAM CMIC MIB files will be stored automatically on your computer The default path is C siemens SICAMRTUs_SNMB_MIB_V03 00 00 MIB Files 3 3 2 Import ...

Страница 174: ...gineering 174 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 SICAM 230 250 SCALA 3 3 3 Display of SNMP Variables in MIB Browser Example 1 SNMP Variable plant Example 2 SNMP Variable classInternal ...

Страница 175: ...Prepare Engineering SICAM RTUs SICAM AK 3 User Manual 175 DC2 028 2 03 Edition 07 2016 Example 3 SNMP Variable sysUpTime Example 4 SNMP Variable ipInReceives ...

Страница 176: ...095 6MF12131GA050AA0 3 4 1 SD Card Reader Writer For archiving purposes the engineering data and firmwares stored on the SD card can be read with a standard commercial chip card reader and be stored on a PC On the other hand in particular for the initialization of a target system the data can be written from a PC to the SD card The driver software required for the use of the chip card reader must ...

Страница 177: ...ur system via the internet under www siemens com sicam Examples System Element Item Number Designation CPCX26 Central pro cessing communication SC2 016 1 CPCX26 Revision history SC2 016 1 XX 53 CPCX26 TB II update PCCX26 Periphery interfac ing control communication SC2 019 1 PCCX26 Revision history SC2 019 1 XX 53 PCCX26 TB II update ETA4 Ethernet interface IEC 60870 5 104 SC0 581 1 ETA4 Revision ...

Страница 178: ...ASCII format 3 6 1 Engineering Procedure The setting of parameters is only possible independent from the target system offline Firmwares for the system elements and application programs must be imported into the SICAM TOOLBOX II Engineering data maintained with the SICAM TOOLBOX II is stored in a data base on the hard disk of the engineering PC By means of loading processes the engineering data ca...

Страница 179: ...t All Programs SICAM TOOLBOX II or via the Toolbox shortcut on the desktop The tools most frequently needed Load Parameters CAEx plus etc can be started also di rectly from the central engineering tool OPM II The detailed instructions for the work with the tools of the SICAM TOOLBOX II reside in the SICAM TOOLBOX II Online Help and in the CAEx plus Online Help Note The SICAM TOOLBOX II Online Help...

Страница 180: ...Prepare Engineering 180 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...

Страница 181: ...2 03 Edition 07 2016 4 Engineering via SICAM TOOLBOX II Contents 4 1 Telecontrol 182 4 2 Automation 199 This chapter is a guideline for the work with the SICAM TOOLBOX II You find the details for the engineering in the SICAM TOOLBOX II Online Help ...

Страница 182: ...es Assign process images to data points Settings for configured process signals Routing of send data and receive data Bulk edit Edit great amounts of image parameters Transfer parameters Translate parameters for the target system SD Card Write and read application data Import Export Generate and read backups of the application data Documentation Formatted spreadsheets for printing Hardware configu...

Страница 183: ...col elements peripheral elements define customer process technical plant with wizard configure plant configure AU with modules set telecontrol parameters translate parameters parameters to target system configure plant export backup import document HW configuration document parameters assembly technical documentation plant manage ment data distri bution center data distri bution center project tec...

Страница 184: ... be changed at any optional time You find the details thereto in the SICAM TOOLBOX II Online Help chapter SICAM TOOLBOX II Presets and chapter Administration of SICAM TOOLBOX II 4 1 1 1 Users and Rights The following user types are predefined and can be selected Type admin Type profi Type standard For each user type different rights are predefined As user type admin you can freely assign new user ...

Страница 185: ...nto the SICAM TOOLBOX II is protected for each user by means of an individ ual password The preset password is equal to the predefined user type Hints The preset password must be changed after the first login 4 1 1 3 Language The language Deutsch or English can be selected 4 1 2 Entrance into the Project 4 1 2 1 Logon With the initial start of a tool of the SICAM TOOLBOX II you must enter a user n...

Страница 186: ...an be used Empty password possible logon to the project without password Hints The preset password must be changed after the first login 4 1 3 Plant Configuration A plant is configured according to different views Project technique System technique Process technique The configuration data is in each case specifically parameterized for the different views With the initial creation of a plant you mu...

Страница 187: ...mwares Further information about this can be found in section 5 5 1 2 Import of Firmware into the SICAM TOOLBOX II 4 1 5 Parameterization of the Telecontrol Functionality The entire parameterization for the telecontrol function can be performed in the SICAM TOOLBOX II with the tool OPM II You find the detailed instruction thereto in the SICAM TOOLBOX II Online Help chapter OPM II The description o...

Страница 188: ...orresponding settings are rejected in the system technique The changed hardware configuration must be converted with the tool OPM II menu Destination systems SICAM RTUs transformer and subsequently transmitted to the target system with the tool Load parameters to become effective During startup the target system checks if the mechanically installed I O modules match the parameterization Exceptions...

Страница 189: ...ized archiving Redundancy 4 1 5 2 1 Communication The protocol is determined by configuring a protocol element suitable for the existing applica tion and its parameterization 4 1 5 2 2 Periphery The peripheral functions are defined by means of configuring the peripheral element the I O modules suitable for the present application as well as their parameters Below the level Ax peripheral bus the co...

Страница 190: ...e system elements can be opened centrally via the menu item Tools Images 4 1 5 3 2 Types Types form the template for the structure of a process technical plant They serve for the sim plification with engineering of large quantities of objects parameters and values Types of the following type categories can be defined below the levels User types Link types Info types Parameter types A type is defin...

Страница 191: ...systems can be set The signals of the libraries include as first link a so called common link LNK_ADR There reside parameters example longtext LAN station that include references to other links of the same signal or are source of formulas A reference causes that upon changes of an entry in the common link the change takes place automatically in the link of the specific target system Message addres...

Страница 192: ... 6 Transform Parameters Before loading into the target system the process technical parameters of the plant must be transformed This can be carried out with the tool OPM II through selection of the menu Destination systems SICAM RTUs SICAM RTUs Transformer System technical parameters are automatically transformed when saved You find the details thereto in the SICAM TOOLBOX II Online Help chapter O...

Страница 193: ...s The output takes place as a table with adjustable layout optionally as preview on the screen or to a printer The documentation extends over the HW pins of the respective peripheral elements and con tains Slot and module type System technical address of each pins within the message Process technical address of each pins within the message Common information of a pin long text Assignment of the pi...

Страница 194: ...ce as a spreadsheet optionally as preview on the screen or to a printer 4 1 9 Commissioning an Test For commissioning and test of the projected settings the following functions are available online Load engineering data Parameter comparison Test functions Diagnosis see section 5 3 Diagnosis For these functions the engineering PC must be connected with the target system see 3 2 Connect Engineering ...

Страница 195: ...nconditional all parameters are loaded into the target system can be applied locally or remotely Initialize all parameters are deleted in the target system and all parameters newly transferred can be applied only with the locally connected automation unit is used for the first loading of an automation unit or of a basic system element You find the details thereto in the SICAM TOOLBOX II Online Hel...

Страница 196: ...ta be simultaneously logged Change of state of inputs outputs Communication from and to protocol elements Data traffic from and to the application program Data traffic from and to special functions for example set counters set time By means of triggering a General Interrogation all spontaneous input signals can be simulta neously logged at any arbitrary time You find the instruction for this test ...

Страница 197: ...nge Warning The manual controlling of outputs with the plant running can lead to damage to persons and machines Ensure that aggregates in the control area of the command output and those subsequent aggregates in the process chain are protected and that persons in the vicinity are warned You find the instruction for this test function in the SICAM TOOLBOX II Online Help chapter Service Programs sec...

Страница 198: ... select a file and click on the button Display archives to display the respective rec ords Note The data records of the decentral archive are registered in configurable files The files are stored on the SD card The record of data points is therefore only possible with equipped SD card You can save the displayed records of DEAR in a file Format csv on the engineering PC You find the information the...

Страница 199: ...ion program Load program code Transfer application program into the target system Perform startup Initialize application program in the target system Test function diagram Test application program online Documentation Prepare application program for printing Fundamental Procedure of the Programming CAEx plus Online Test OPM II CAEx plus CAEx plus CAEx plus OPM II OPM II configure external signals ...

Страница 200: ...I or via the web browser the Signal List can be alternatively generated with the tool OPM II imported from a local parameterization see thereto section 4 1 7 Import Export and Backup of Engineering Data The signals of the process technical plant can be used by CAEx plus after the transformation refer to section 4 1 6 Transform Parameters The structure of the project tree automatically adapts to th...

Страница 201: ...ction Diagram Editor Example You find the description of the editor in the CAEx plus Online Help chapter Editors Additional Information can be found in the SICAM TOOLBOX II Online Help chapter CAEx plus You find the most important characteristic values limits for the creation of the open closed loop control function in the SICAM AK 3 System Description chapter Technical Specifica tions of the Modu...

Страница 202: ... Via the menu Tools Error state viewer the indication display of the code generation can be activated There common indications as for instance information on occupied memory space for code and variables as well as detected errors are recorded in detail Error State Viewer Example The exact description of this tool is included in the SICAM TOOLBOX II CAEx plus Online Help chapter Target System Conne...

Страница 203: ...In the project hierarchy of the tool CAEx plus by selecting each level the function Print can be executed by means of pop up menu The print operation is started on the default printer of the PC You find the instruction thereto in the CAEx plus Online Help chapter Basics section De fault Operating Elements section Commands of the Pop Up Menus section Print in Pro ject Management Additional informat...

Страница 204: ...ld be destroyed as a result You find the technical description thereto in the manual SICAM RTUs Common Functions System and Basic System Elements chapter Automation section Open Closed Loop Con trol Function Loading of Application Program Reload You find the instruction for the operation in the SICAM TOOLBOX II Online Help chapter Service Programs section Parameter Loader Note Instead of a functio...

Страница 205: ...me archive Display status information Read and write simulate variables Oscilloscope Oscilloscope functions serve for the chronological representation of analog values and binary values during the Offline Simulation of the function diagram You find exact details thereto in the CAEx plus Online Help chapter Additional Products section Logic Analysis with Oscilloscope Functions The technical descrip...

Страница 206: ...Engineering via SICAM TOOLBOX II 206 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 CAEx plus Online Test Example CAEx plus Oscilloscope Example ...

Страница 207: ...nosis 219 5 4 Maintenance of the Hardware 227 5 5 Firmware Update 230 5 6 Remote Maintenance 234 6 1 Configuration of Automation Units 236 This chapter describes the internal checks and displays of the system SICAM AK 3 which di agnosis options are available what is to be considered with the exchange of modules and how functional updates can be loaded into the system ...

Страница 208: ...yellow Ready Power supply ready Temperature 95 C Temperature sensor defective V Call timeout module not called by the master control unit 5 1 2 Basic System Elements LEDs on the front panel refer to 2 2 Basic System Elements display various states The ar rangement of the LEDs comprises System display elements Display of operating and error states of the system Function display elements Display of ...

Страница 209: ... card SF RUN STOP TEST KILL Startup HLT yellow Halt Firmware shut down Module shut down only valid for CP 2019 with Safety Firmware Display elements of the local Ethernet protocol elements Name Color Function LED Meaning LK X0 yellow PRE0 Link Protocol element 0 physical connection to switch remote station PK X0 yellow PRE0 Packet Protocol element 0 activity on trans mit receive direction ACT0 yel...

Страница 210: ...tion ACT2 yellow PRE2 Active Protocol element 2 interface active redun dancy ER2 yellow PRE2 Error Protocol element 2 Error on interface Communication failure all connections faulty Communication fault at least one connection faulty OH X3 yellow PRE3 Link Protocol element 3 message is sent to switch remote station RTX X3 yellow PRE3 Packet Protocol element 3 activity on trans mit receive direction...

Страница 211: ...ent 2 activity on trans mit receive direction ACT2 yellow PRE2 Port 0 Active Protocol element 2 interface active redun dancy ER2 yellow PRE2 Port 0 Error Protocol element 2 Error on interface OH X3 yellow PRE3 Port 1 Link Protocol element 3 physical connection to switch remote station RTX X3 yellow PRE3 Port 1 Pack et Protocol element 3 activity on trans mit receive direction ACT3 yellow PRE3 Port...

Страница 212: ...ror internal error external error warning module failure failure Startup Function Display Elements Name Color Function LED Meaning D00 D63 yellow Digital inputs Digital outputs I O activated C00 C31 yellow Digital out puts command relay I O activated I00 I31 yellow Digital inputs I O activated V00 V23 yellow Analog in puts Analog outputs I O activated GRA yellow Group A Command group A activated G...

Страница 213: ...ormed 5 2 1 Basic System Elements Startup step RY ER W BBD INT ACT EXT CPY HLT Error Power up or Reset Module defect Check code memory flash PROM PROM error code Module is shutdown Startup is aborted Check data memory RAM with address error check RAM error data Module is shutdown Startup is aborted Check of checksums of all param eter and firmware files on the flash card V Checksum error on the fl...

Страница 214: ...r the parameterized configuration corresponds with the physical configuration processing and communication elements 1 protocol elements peripheral elements Configuration error The incorrectly configured or defective sys tem element is not operational Loading of the parameters to the lower level protocol and peripher al elements Too little memory on the protocol element or peripheral element Firmwa...

Страница 215: ...aster control element Error startup continued RY ER W BBD INT ACT EXT CPY HLT Note No flash card present 1 x x x x SICAM TOOLBOX II diagnosis install flash card initialize automation unit Checksum error on the flash card x x x x SICAM TOOLBOX II diagnosis initialize automa tion unit or load firmware acc to diagnosis Firmware code incomplete 1 x x x x SICAM TOOLBOX II diagnosis load firmware automa...

Страница 216: ... control element Note Firmware shut down means that all functions with exception of those which are necessary for the communication with the engineering tool via direct connection are stopped In this state the watchdog of the modules terminates and all outputs are terminated By means of the lighted display this state can not be identified clearly This state can be finished by means of power on or ...

Страница 217: ...error in addition the system LED ER lights up on the basic system element Action after startup ERx Error Setup of the communication con nection communication failure communication fault Communication established in addition the system LED ER lights up on the basic system element Error startup aborted ERx Note Module defect Exchange system element PROM error code Exchange system element RAM error d...

Страница 218: ...Startup is aborted Check of the parameter contents Parameter error Diagnosis information is set Startup concluded without error Startup concluded with error in addition the system LED ER lights up on the basic system element Error startup aborted RY ER Note Module defect Exchange system element PROM error code Exchange system element RAM error data Exchange system element Too little memory SICAM T...

Страница 219: ... plus compiler engineering via SICAM TOOLBOX II Logging in the Error state viewer Supervision by the ASCII Compiler during startup engineering via web browser Logging in the PLC diagnosis Supervision online by the firmware of the master control element Logging in the online diagnosis Operator errors Are largely limited due to plausibility checks or queries by the SICAM TOOLBOX II Note Naturally al...

Страница 220: ...CAM AK P S 26 3x SI C AM AK P S 26 3x CP 2 016 DI 2110 D O 22 10 A I 2 300 CP 201 9 A I 23 01 D I 211 0 DI 21 10 DO 2 210 A I 230 0 C P 201 9 A I 2 301 A I 230 1 DI 2110 DI 2 110 DI 21 10 TOOLBOX II Revision License P ak Version 5 SiemensA G Ethernet TCP IP SICAM TOOLBOX II SICA M AK P S 263 x SICA M AK P S 263 x CP 20 16 DI 2 110 DO 221 0 A I 230 0 CP 2 019 A I 230 1 DI 2 110 DI 211 0 DO 22 10 A ...

Страница 221: ... sion 5 Si emens AG SICAM AK P S 2 63x CP 2 016 DI 2110 DI 21 10 C P 20 19 DO 22 10 A I 230 1 A I 23 00 SI C AM AK P S 26 3x Ethernet TCP IP Ethernet TCP IP SICAM AK P S 2 63x CP 2 016 DI 2110 DI 21 10 C P 20 19 DO 22 10 A I 230 1 A I 23 00 SI C AM AK P S 26 3x SICAM AK P S 2 63x SICAM AK P S 2 63x CP 201 6 D I 211 0 DO 2 210 A I 2 300 C P 201 9 A I 23 01 D I 211 0 DI 2 110 DO 2 21 0 A I 23 00 C P...

Страница 222: ...y are no longer present Network overview diagnostic The error messages of all automation units in the network are output in a report window with the function Network overview diagnostic sum information AU overview diagnostic The error messages of all automation units in the network are output in a report window with the function AU overview diagnostic sum information for each system element able t...

Страница 223: ...sses A failure Signals that an automation unit is no longer available B module failure Signals that the internal communication with a module is no longer possible I internal error Error that is unambiguously allocatable to the respective module in hardware or firmware e g checksum error in the parameter memory E external error Is detected by means of supervision of sensors and actuators e g live z...

Страница 224: ...e diagnosis functions in the manual SICAM RTUs Common Functions System and Basic System Elements chapter System Services section Diagnosis 5 3 4 System Performance Information about the system performance of a selected automation unit can be interrogated online with the tool Service Function Online Display equipped system elements Read serial numbers Display delete data flow routing Shut down sele...

Страница 225: ...ncorrect input Manually via the pop up menu Early error detection in the function diagram All editing errors can be displayed at any time You find the exact details in the CAEx plus Online Help chapter Editors section FBD Edi tor section Operation in FBD Editor Errors with Engineering Errors that can occur on the function diagram engineering are displayed centrally in the Error state viewer of CAE...

Страница 226: ...the Error state viewer of CAEx plus It concerns thereby notifications of the target system connection the code generator the control panel the online applications the Open Operating System the target system integration into the project management the openPLC You find the exact details in the CAEx plus Online Help chapter Target System Connection section Program Messages for Target System Connectio...

Страница 227: ...parameterized anew after loading the firmware 5 4 1 2 SD Card SICAM AK 3 accesses with each startup the SD card and checks it The following cases lead to errors with the SD card SD card not available SD card defective Wrong type of SD card SD card empty SD card not formatted Checksum error with firmware codes Checksum error with parameter files Upon startup with erroneous SD card the supplementary...

Страница 228: ...n a de energized state You find the detailed instruction for the replacement of modules in section Installation and Removal of Modules You find further technical information on module replacement in the manual SICAM RTUs Common Functions System and Basic System Elements chapter System Services section Data Storage on Flash Card 5 4 2 1 Master control element After removing the master control eleme...

Страница 229: ...ation element this performs a startup 5 4 2 3 Serial Interface Module For the replacement of a serial interface module first the basic system element carrier mod ule must be removed from the board rack For this please consider the previously mentioned consequences for the system After the insertion of the basic system element this performs a startup 5 4 2 4 Peripheral Elements After the removal of...

Страница 230: ...e s and Toolbox update s from internet under www siemens com sicam 2 Import firmware code s and Toolbox update s into the SICAM TOOLBOX II 3 Load firmware s into the target system Procedure for the Update of System Elements The SICAM TOOLBOX II contains after its installation all current firmware revisions based on the date of issue of the installed version interrogate firm ware revision new firmw...

Страница 231: ...tion Master Data Update An additional option provides the tool Live Update You find the information thereto in the SICAM TOOLBOX II Online Help chapter Service Programs section Live Update 5 5 1 3 Loading of Firmware into the Target System Firmware codes that are existing in the SICAM TOOLBOX II can be loaded with the tool Load Firmware into the connected target systems The loading of the firmware...

Страница 232: ... card and a running firmware must be present on the master control element of the target system Further you need the appropriate access right for the engineering tool You find the instructions for the tool Load Firmware in the SICAM TOOLBOX II Online Help chapter Service Programs section Load Firmware 5 5 1 3 2 Load Firmware Offline Thereto a SD card reader writer must be connected on the SICAM TO...

Страница 233: ...procedure Failure defect shutdown of the engineering PC Abortion due to hardware error Abortion or excessively long fault of the communication connection between engineering PC and SICAM AK Further technical information can be found in the manual SICAM RTUs Common Functions System and Basic System Elements chapter System Services sections Loading Opera tion and Firmware Shutdown Note A master cont...

Страница 234: ...rver and Clients Install on the webserver Microsoft Windows with Terminal Services Web Access After wards install on this server the SICAM TOOLBOX II On the clients an installation is not required the access to the webserver takes place via the Microsoft Internet Explorer as of version 5 0 You find a detailed description of the configuration in the SICAM TOOLBOX II Online Help chapter web engineer...

Страница 235: ... Configuration of the local Ethernet Interfaces 244 6 3 Application Configuration of Static Routes 250 6 4 Application Configuration of IPSEC VPN 253 This chapter describes the recommended configurations for the system SICAM AK 3 It shows illustrations of configurations information about used cable types and cable length and lists the used modules and cables with order numbers ...

Страница 236: ...max 16 peripheral elements can be connected The Ax PE bus can be driven by one of the CPUs M CPU C1 C16 CPU Default M CPU Necessary modules and cables Designation Item Number MLFB Basic unit SICAM AK 3 CP 2016 Master control element CP 2016 CPCX26 BC2 016 6MF10130CA160AA0 CP 2019 Processing and communication element CP 2019 PCCX26 BC2 019 6MF10132CA100AA0 CP 2016 SICAM AK PS 263x CP 2016 DI 2110 D...

Страница 237: ... unit SICAM AK 3 CP 2016 Master control element CP 2016 CPCX26 BC2 016 6MF10130CA160AA0 CP 2019 Processing and communication element CP 2019 PCCX26 BC2 019 6MF10132CA100AA0 Cable Patch cable CAT5 4x2 AWG26 7 T41 255 1m 6MF13040BC550AA0 T41 251 2m 6MF13040BC510AA0 T41 252 3m 6MF13040BC520AA0 Peripheral elements SICAM AK 3 CM 2843 SICAM AK 3 expansion board rack GC2 843 6MF11130CJ430AA0 SICAM AK PS ...

Страница 238: ... socket connector X4 C1 Ax In configurations with optical remoted SICAM TM peripheral elements PE 1000µm fiber cables cannot be used SICAM AK PS 263x SICAM AK P S 263x CP 2016 DI 2110 DO 2210 AI 2300 CP 2019 A I 2301 DI 2110 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 A I 2301 DI 2110 DI 2110 DI 2110 CP 2016 CP 2019 1 peripheral element 1 Peripherieelement PE 6411 PS 663x 2 2 2 SICAM 170 3 SICAM 170 3...

Страница 239: ... 6MF10130CA160AA0 CP 2019 Processing and communication element CP 2019 PCCX26 BC2 019 6MF10132CA100AA0 Cable Patch cable CAT5 4x2 AWG26 7 T41 255 1m 6MF13040BC550AA0 T41 251 2m 6MF13040BC510AA0 T41 252 3m 6MF13040BC520AA0 Bus Interface Modules CM 0842 Ax 1703 bus interface 4x FO GA0 842 6MF11110AJ420AA0 Cable FO INDOORCABLE 200 DUP BREAK ROUND FO CONNECTOR ODLP 200 2 pcs per connection TF7 035 TF7...

Страница 240: ...heral elements PE 1000µm fiber cables cannot be used SICAM AK PS 263x SICAM AK PS 263x CP 2016 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 DI 2110 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 AI 2301 DI 2110 DI 2110 DI 2110 CP 2016 CP 2019 PE 6411 PS 663x 2 2 2 2 S ICAM 1 703 S ICAM 1 703 ON OFF S1 1 S ICAM 1 703 S ICAM 1 703 ON OFF S1 ON OFF S1 Bus Interface Modules CM 0842 Ax 1703 Peripheral bus electric...

Страница 241: ...n Item Number MLFB SICAM AK 3 Basic unit CP 2016 Master control element CP 2016 CPCX26 BC2 016 6MF10130CA160AA0 CP 2019 Processing and communication element CP 2019 PCCX26 BC2 019 6MF10132CA100AA0 Cable Patch cable CAT5 4x2 AWG26 7 T41 255 1m 6MF13040BC550AA0 T41 251 2m 6MF13040BC510AA0 T41 252 3m 6MF13040BC520AA0 Bus Interface Mod ule CM 0842 Ax 1703 bus interface 4x FO GA0 842 6MF11110AJ420AA0 C...

Страница 242: ...ot 1 ð socket connector X4 C1 Ax SICAM AK PS 263x SICAM AK PS 263x CP 2016 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 DI 2110 DI 2110 DO 2210 AI 2300 CP 2019 AI 2301 AI 2301 DI 2110 DI 2110 DI 2110 CP 2016 CP 2019 PE 6410 PS 663x PE 6411 PS 663x 3 3 3 2 2 SICAM 1 703 SICAM 1 703 ON OFF S1 1 1 SICAM AK 3 base unit I O modules max 8 Ax 1703 peripheral bus electrical 16 Mbps patch cable length up to 3 m...

Страница 243: ...t CP 2016 CPCX26 BC2 016 6MF10130CA160AA0 CP 2019 Processing and communication element CP 2019 PCCX26 BC2 019 6MF10132CA100AA0 Cable Patch cable CAT5 4x2 AWG26 7 T41 255 1m 6MF13040BC550AA0 T41 251 2m 6MF13040BC510AA0 T41 252 3m 6MF13040BC520AA0 Bus Interface Modules CM 0843 Ax 1703 Businterface electrical GA0 843 6MF11110AJ430AA0 CM 0842 Ax 1703 bus interface 4x FO GA0 842 6MF11110AJ420AA0 Cable ...

Страница 244: ...rom BC2 016 A from 6MF10130CA160AA0CC 2 CP 2019 from BC2 019 A from 6MF10132CA100AA0CC 2 CP 2016 BC2 016 6MF10130CA160AA0BB 1 CP 2019 BC2 019 6MF10132CA100AA0BB 1 You can find the MAC addresses form module version CC upwards on a separate label on plug X99 If parameter Network settings IP addresses Mode of Ethernet ports is set to value 1 IP address connected ports in switch mode then the first MA...

Страница 245: ...al ethernet ports on CP 2016 or CP 2019 are not used in this application and thus must be deactivated for security reasons The required parameter can be set on the BSE under Netzwork settings IP adresses Mode of Ethernet ports 1 IP address connected ports in switch mode Own IP address 0 0 0 0 Subnet mask 0 0 0 0 Automation Zone SICAM AK 3 SICAM AK SICAM AK X3 X2 X1 X0 SM 25xx Process CP 2016 or CP...

Страница 246: ...pplication and thus must be deactivated for security reasons The required parameter can be set on the BSE under Network settings IP address es Mode of Ethernet ports 1 IP address connected ports in switch mode Own IP address 0 0 0 0 Subnet mask 0 0 0 0 In this configuration both local ethernet interfaces are deactivated Substation Zone Office Zone Control Center Zone SICAM AK 3 SICAM AK SICAM AK X...

Страница 247: ...e subnet data exchange between subnets only via SICAM AK 3 application function 1 default router Parameter Network settings IP address Mode of Ethernet ports 2 IP addresses independent ports Note In case of IP address 0 0 0 0 the corresponding port is deactivated Both Ethernet interfaces X0 X1 have the same MAC address Substation Zone Office Zone Control Center Zone Router SICAM AK 3 S I C A MA K ...

Страница 248: ... 3 is used as switch between control system and external system Features of the Ethernet Ports 1 IP address 1 subnet mask 1 default router Parameter Network settings IP address Mode of Ethernet ports 1 IP address connected ports in switch mode Substation Zone Office Zone Control Center Zone Router SICAM AK 3 S I C A MA K S I C A M A K X3 X2 X1 X0 SM 25xx Control Center IP address 172 16 0 4 Subnet...

Страница 249: ...grated switch it is pos sible to reach the local SICAM AK 3 and further SICAM RTUs components via the Control Center Zone It depends on the network configuration which can be reached Features of the Ethernet Ports 1 IP address 1 subnet mask 1 default router Parameter Network settings IP address Mode of Ethernet ports 1 IP address connected ports in switch mode Substation Zone Office Zone Control C...

Страница 250: ... of static routes Source IP address P P Destination IP address P P Gateway IP address P P Subnet mask P P Interfaces X0 X1 X0 X1 6 3 2 Configuration Activation of the static routes Parameter Network settings IP address advanced parameters Enable static routes YES Definition of the routing table Parameter Network settings IP address advanced parameters static routes Number of lines x max 10 Mode of...

Страница 251: ...ess Subnet mask 172 16 50 100 255 0 255 255 Cisco Router 255 255 Gateway IP address Route 0 IP address Subnet mask 192 168 94 250 255 0 IP address Subnet mask 172 16 51 100 255 0 255 255 Control Center A 255 255 Destination IP address Route 0 IP address Subnet mask 172 16 50 1 255 0 CP 2016 or CP 2019 Master Modul 1 IP Addresse 192 168 94 1 255 255 255 0 192 168 94 250 Mode der Ethernet Ports Own ...

Страница 252: ...ss Subnet mask 172 16 50 100 255 0 255 255 Cisco Router 255 255 Gateway IP address Route 0 IP address Subnet mask 192 168 94 250 255 0 IP address Subnet mask 172 16 51 100 255 0 255 255 Control Center A 255 255 Destination IP address Route 0 IP address Subnet mask 172 16 50 1 255 0 CP 2016 or CP 2019 Master Modul 2 IP addresses 255 255 255 0 168 94 250 Mode of ethernet ports 192 Subnet mask Defaul...

Страница 253: ...cation pro cess pre shared key The used key pre shared key can be set by means of an engineering tool e g SICAM TOOLBOX II It is securely stored in SICAM TOOLBOX II and SICAM AK 3 Hint IPSec can only be used in SICAM AK 3 when engineering is done by means of SICAM TOOLBOX II Features Communication with the control system via IEC 60870 104 Ethernet Interface X0 or X1 can be set with parameter 1 IP ...

Страница 254: ...N Tunnel IPSec VPN Tunnel IPSec VPN Tunnel 2 redundant router Cisco 1941 HSRP 2 redundant router Cisco 1941 HSRP IP security Remote Site 2 IP Address 192 168 1 152 IP security Remote Site 2 Subnet IP Address Subnet mask 122 33 0 0 255 255 255 0 IP security Remote Site 1 IP Address 192 168 1 151 IP security Remote Site 1 Subnet IP Address Subnet mask 172 17 0 0 255 255 248 0 IP address 122 33 0 254...

Страница 255: ...Address 50 50 50 83 IP security Remote Site 2 Subnet IP Address Subnet mask 122 33 0 0 255 255 255 0 IP security Remote Site 1 IP Address 40 40 40 83 IP security Remote Site 1 Subnet IP Address Subnet mask 172 17 0 0 255 255 248 0 IP address 122 33 0 254 Control system or SICAM AK 3 IP address 122 33 0 2 Subnet mask 255 255 255 0 IP address 172 17 0 254 Control system or SICAM AK 3 IP address 172 ...

Страница 256: ...PN Tunnel GPRS Modem Siemens Scalance M874 2 2 5G Router static IP address 90 90 90 81 GPRS VPN IPSec VPN tunnel remote gateway IP address 192 168 1 151 IP address 172 17 0 254 Control system IP address 172 17 0 22 Subnet mask 255 255 248 0 IPSec VPN tunnel remote PEER subnet IPSec VPN tunnel remote PEER subnet mask 172 17 0 0 255 255 248 0 GPRS Modem Siemens Scalance M874 2 2 5G Router static IP ...

Страница 257: ...es contact against payment of the shipping and handling charges for a period of at least 3 years since purchase of the Product We are liable for this Product including the Open Source Software contained in it pursuant to the license conditions applicable to the Product Any liability for the Open Source Software beyond the program flow intended for this Product is explicitly excluded Furthermore an...

Страница 258: ...ptions Product Family SICAM RTUs Product Version General Infomation Click on Search Click on SICAM RTUs OSS Extractor in the result list to start the download When the download is finished you will get the file SICAMOSS zip Unzip this file and save the therein contained file SICAMOSS exe in the root path of the SD card from which you want to readout the license agreement ...

Страница 259: ...dow by press ing any key Now you can find on the SD card the folder OSS with several subfolders One single folder for each firmware which uses open source components Within these subfolders are again folders for each used firmware revision These folders contain the corresponding license data Path for ReadmeOSS SD Card OSS Firmwarename Firmwarenumber Revision ReadmOSS htm E g SD Card OSS ETA4 02 01...

Страница 260: ...Licensing Agreement 260 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 End of document ...

Отзывы: