Automation Units and Automation Networks
246
SICAM RTUs, SICAM AK 3 User Manual
Edition 07.2016, DC2-028-2.03
6.2.2
SICAM AK 3 as Telecontrol Substation
•
Serial communication with the control system via IEC 60870-5-101
•
The communication to the process takes place with local peripherals or serial communica-
tions protocols (e.g.: MODBUS, …)
The local ethernet ports on CP-2016 or CP-2019 are not used in this application and thus
must be deactivated for security reasons.
The required parameter can be set on the BSE under
Network settings | IP address-
es
•
Mode of Ethernet ports
=
1 IP address (connected ports in switch mode)
•
Own IP address
=
0.0.0.0
•
Subnet mask
=
0.0.0.0
In this configuration both local ethernet interfaces are deactivated.
Substation Zone
Office Zone
Control Center Zone
SICAM AK 3
SICAM AK
SICAM AK
X3
X2
X1
X0
S
M
-2
5
5
1
IEC 60870-5-101
Control Center
IP-address:
172.17.0.22
Subnet mask: 255.255.0.0
Process
PRE2
CP-2016 or CP-2019
Netzwork settings| IP addresses
Own IP address
..........
....................
0.0.0.0
0.0.0.0
Subnet mask
Содержание SICAM AK 3
Страница 8: ...Open Source Software 8 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...
Страница 84: ...Installation 84 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...
Страница 119: ...System Components SICAM RTUs SICAM AK 3 User Manual 119 DC2 028 2 03 Edition 07 2016 2 5 3 2 Block Diagram ...
Страница 142: ...System Components 142 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 2 5 5 2 Block Diagram ...
Страница 159: ...System Components SICAM RTUs SICAM AK 3 User Manual 159 DC2 028 2 03 Edition 07 2016 2 8 1 2 Block Diagram ...
Страница 166: ...System Components 166 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...
Страница 180: ...Prepare Engineering 180 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...
Страница 260: ...Licensing Agreement 260 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 End of document ...