Parameter assignment
7.2 Parameterizing via the operator interface
PAC3120 and PAC3220
Equipment Manual, 10/2019,
L1V30425208F-01
73
Current input
Selection
Range
Factory setting
CT PRIMARY
Primary current of the current transformers
1 … 99999 A
50 A
CT SECONDARY
Secondary current of the current transformers
•
1 A
•
5 A
5 A
DISPLAY RANGE:
Freely adjustable
1 … 99999 A
50 A
•
CURRENT DIREC L1
•
CURRENT DIREC L2
•
CURRENT DIREC L3
Inverse evaluation of the current flow direction
separately for each phase.
•
ON: Direction of current flow is inverted.
The device interprets the current flow direc-
tion as opposite to the wiring.
•
OFF: The device interprets the current
flow direction to match the wiring.
OFF
7.2.4
Date/time
Setting the date and time
Selection
Range
Factory setting
DATE
Current date.
The date format is defined in the FORMAT field.
–
FORMAT
•
DD.MM.YYYY
•
YYYY-MM-DD
•
MM/DD/YY
DD.MM.YYYY
TIME
HH:MM:SS
–
TIME ZONE
Time zone, refers to coordinated universal time
(UTC).
−
12:00 … +14:00, in 30-minute intervals
Examples:
•
"
−
06:00" corresponds to UTC-6
•
"+01:00" corresponds to UTC+1
00:00
Содержание SENTRON PAC3120
Страница 1: ...PAC3120 and PAC3220 ...
Страница 2: ......
Страница 8: ...Table of contents 6 PAC3120 and PAC3220 Equipment Manual 10 2019 L1V30425208F 01 ...
Страница 36: ...Description 2 7 Slots for expansion modules 34 PAC3120 and PAC3220 Equipment Manual 10 2019 L1V30425208F 01 ...
Страница 70: ...Operator control 6 1 Device interface 68 PAC3120 and PAC3220 Equipment Manual 10 2019 L1V30425208F 01 ...
Страница 110: ...Technical data 10 2 Labeling 108 PAC3120 and PAC3220 Equipment Manual 10 2019 L1V30425208F 01 ...
Страница 159: ......
Страница 160: ......