Applications
3.1 Transfer control
3KC ATC6500 transfer control device
22
Manual, 05/2019, L1V30538268002A-01
3.1.4.2
Application B: 2S - 1T - PL
SRC1 (kVA) > SRC2 (kVA)
In this application three motor-driven circuit breakers are used. A distinction is made
between prioritized load and non-prioritized load (NPL).
On failure of the prioritized sources (in this case, Source 1), only the prioritized load is
supplied by the secondary source (in this case, Source 2). In normal circumstances (Source
1 available) both sources are supplied by the main network.
The states can be obtained from the table:
Source 1 (SRC1)
Source 2 (SRC2)
Breaker 1 (BRK 1)
Breaker 2 (BRK 2)
Tie breaker (TB)
0
0
Open
Open
Open
0
1
Open
Closed
Open
1
1
Closed
Open
Closed
0 = Infeed source not available
1 = Infeed source available
Note
In this case Source 1 is regarded as the main source. The transfer can be influenced by
modifying the source priority.
See also
Parameterization (Page 155)
Transfer (Page 227)
Содержание SENTRON ATC6500
Страница 1: ...3KC ATC6500 transfer control device ...
Страница 2: ......
Страница 34: ...Applications 3 3 Voltage measurement 3KC ATC6500 transfer control device 32 Manual 05 2019 L1V30538268002A 01 ...
Страница 35: ...3KC ATC6500 transfer control device Manual 05 2019 L1V30538268002A 01 33 Product description 4 User interface ...
Страница 238: ...Transfer 12 2 Transfer sequence 3KC ATC6500 transfer control device 236 Manual 05 2019 L1V30538268002A 01 ...
Страница 242: ...Technical specifications 3KC ATC6500 transfer control device 240 Manual 05 2019 L1V30538268002A 01 ...
Страница 244: ...Dimension drawings 3KC ATC6500 transfer control device 242 Manual 05 2019 L1V30538268002A 01 Ethernet expansion module ...
Страница 248: ...List of abbreviations 3KC ATC6500 transfer control device 246 Manual 05 2019 L1V30538268002A 01 ...
Страница 256: ......