Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
161
9.4.1
P01 - Settings
P01
Designation on ATC
display
Description
Unit
Default
Range
P01.01
LANGUAGE
Language setting
– This parameter is used for setting the lan-
guage of the user interface.
English
English
Italian
French Span-
ish
German
Portuguese
Polish
Russian
P01.02
CLOCK SETTING
Setting of the real-time clock when switching
on the power supply of the ATC
– This parameter determines whether the
real-time clock is to be reset or not after each
startup.
OFF
OFF
ON
P01.03
MODE AT POWER
ON
Operating mode after power on
– This parameter determines which mode the
ATC6500 enters after switching on. It can
either be always switched on in the operating
mode OFF, or in the last operating mode
used before the device was switched off.
Previous OFF mode
previous mode
P01.04
DISPLAY CONTRAST LCD contrast
– This can be used to adjust the contrast of
the LCD display.
%
50
0-100
P01.05
HIGH BACKLIGHT
LEVEL
LCD lighting high
– This parameter sets the bright LCD back-
lighting.
%
100
0-100
P01.06
LOW BACKLIGHT
LEVEL
LCD lighting low
– This parameter sets the dim LCD backlight-
ing.
%
25
0-50
P01.07
LOW BACKLIGHT
DELAY
Delay LCD lighting low
– This allows you to set a delay, after which
the ATC6500 switches to low backlighting.
s
180
5-600
P01.08
DEFAULT PAGE
RETURN
Return Default/Page
– This parameter controls whether the device
switches to a default page defined under
P01.09 if no key is pressed within a specific
time. If this parameter is set to OFF, the
ATC6500 always remains on the last page to
be opened.
s
300
OFF / 10/600
P01.09
DEFAULT PAGE
Selection of default page
– This parameter is used to select a new
default page from the existing display pages
of the ATC6500. In connection with P01.08, a
switch is made to this page after a certain
time.
Configura-
tion
(List with dis-
play pages)
P01.10
MAIN PAGE TITLE
Identification of plant
– You can enter any alphanumeric descrip-
tion of the plant here.
SIEMENS
ATC6500
String 20 chr.
Содержание SENTRON ATC6500
Страница 1: ...3KC ATC6500 transfer control device ...
Страница 2: ......
Страница 34: ...Applications 3 3 Voltage measurement 3KC ATC6500 transfer control device 32 Manual 05 2019 L1V30538268002A 01 ...
Страница 35: ...3KC ATC6500 transfer control device Manual 05 2019 L1V30538268002A 01 33 Product description 4 User interface ...
Страница 238: ...Transfer 12 2 Transfer sequence 3KC ATC6500 transfer control device 236 Manual 05 2019 L1V30538268002A 01 ...
Страница 242: ...Technical specifications 3KC ATC6500 transfer control device 240 Manual 05 2019 L1V30538268002A 01 ...
Страница 244: ...Dimension drawings 3KC ATC6500 transfer control device 242 Manual 05 2019 L1V30538268002A 01 Ethernet expansion module ...
Страница 248: ...List of abbreviations 3KC ATC6500 transfer control device 246 Manual 05 2019 L1V30538268002A 01 ...
Страница 256: ......