Technical data
12.2 Configuration of main connections
3VL molded-case circuit breakers
150
System Manual, 03/2009, 110 0110 - 02 DS 01
12.2
Configuration of main connections
Main conductor connection for SENTRON VL fixed-mounted version
Terminals for cable
Table 12- 9 Terminals
VL160X/
VL160
VL250
VL400
VL400
VL630
VL800
VL1250
Conductor cross
section
Cu / Al (mm
2
)
multi-core
Finely-
stranded
16-70
16-50
25-185
25-120
50-300
50-240
50-120
50-95
50-240
50-185
50-185
50-150
50-185
50-150
Cable connection
option
1
1
1
2
2
3
4
Tightening torque
for securing
conductor
Nm
16
25-35
50-70
[mm²]
6
9
14
25-35
50-185
[mm²]
14
31
50-120
150-300
[mm²]
31
56
31
34
42
42
Tool (hex wrench)
4
8
12
8
8
8
8
Tightening torque
Securing terminals
Nm
-
14
15
15
15
15
24
Tool
(Allen key)
1)
-
4
6
6
6
8
8
1)
For the fixing screws for the connection pieces
Box terminals
Table 12- 10 Box terminals
Type of cable
VL160X/VL160
VL250
VL400
Solid/stranded
mm
2
2,5-70
25-185
50-300
Finely stranded with
end sleeve
mm
2
2,5-50
25-120
50-240
Busbar dimensions
W x H x D
mm
12 x 10 x 19
17 x 10 x 24
25 x 10 x 28
Tightening torque
Nm
4 (2,5 ... 10 mm
2
)
8 (16 ... 70 mm
2
)
12
25
Tool (Allen key)
4
5
8
Содержание SENTRON 3VL series
Страница 2: ......
Страница 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 40: ...System overview 4 2 Key data 3VL molded case circuit breakers 40 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Страница 359: ......