Accessories
4.8 Residual current devices
3VA molded case circuit breakers with IEC certificate
Manual, 03/2019, A5E03603177010-03
441
Terminals
A number of auxiliary contacts which perform different functions are located underneath the
contact hazard protective cover:
Alarm switch
Floating auxiliary contacts for 2 different alarms are provided:
●
TRIP-IND (TRIP INDICATOR)
A tripped signal can be output via this auxiliary switch, e.g. for connection to a warning
lamp. This trip alarm switch operates as soon as the residual current exceeds the set
response current, irrespective of whether the residual current device is in RCD or
MONITORING mode.
Since the relay for the tripped signal (TRIP-IND) is a bistable relay, the relay contact
states remain "stored" even in the event of a power outage. When the power supply
recovers, the indicated relay contact states are those which existed before the power
outage.