Accessories
4.4 Plug-in and draw-out technology
3VA molded case circuit breakers with IEC certificate
Manual, 03/2019, A5E03603177010-03
301
The cable with pre-assembled USB and tab connectors can also be ordered as an individual
item for installation on molded case circuit breakers prepared for use as draw-out units.
For detailed instructions on how to install the communications interface for the draw-out unit,
please refer to the relevant Operating Instructions
http://support.automation.siemens.com/WW/view/en/80597324
For instructions on how to read out data via remote data transfer, refer to the operating
instructions for the COM100/COM800 breaker data server.
Auxiliary circuit connector
①
Plug-in technology
②
Draw-out technology
Auxiliary circuit connectors are required only if the molded case circuit breaker to be
converted to plug-in or draw-out technology is equipped with internal accessories. Plug-in
units use a different design of auxiliary circuit connector than draw-out units.
The number of auxiliary circuit connectors required depends on the accessories to be
installed in the molded case circuit breaker and ultimately on the number of electrical
connections which need to be brought out of the molded case circuit breaker. Each auxiliary
circuit connector can be used to connect up to four cables. Accordingly, the breaker-end and
socket-end halves of the auxiliary circuit connectors have four screw-type terminals which
are labeled ".1" to ".4".
Содержание SENTRON 3VA1
Страница 1: ......
Страница 2: ......
Страница 662: ...Conversion tables 3VA molded case circuit breakers with IEC certificate 660 Manual 03 2019 A5E03603177010 03 ...
Страница 668: ...Glossary 3VA molded case circuit breakers with IEC certificate 666 Manual 03 2019 A5E03603177010 03 ...
Страница 675: ......
Страница 676: ......