![Siemens SDV6 Скачать руководство пользователя страница 14](http://html.mh-extra.com/html/siemens/sdv6/sdv6_instruction-manual_375741014.webp)
Installation
Figure 4: Anchoring type SDV6 distribution circuit breaker
Dimensions in inches (mm)
15.5 kV-
20/25/31.5/40 kA-
1,200/2,000 A
15.5 kV-
31.5/40 kA-
3,000 A
27.6 kV-
20/25 kA-
1,200/2,000 A
38.0 kV-
20/25/31.5/40 kA-
1,200/2,000 A
A
44.0 (1,118)
52.3 (1,328)
52.3 (1,328)
67.2 (1,706)
B
39.9 (1,014)
39.9 (1,014)
39.9 (1,014)
63.5 (1,612)
C
47.9 (1,217)
55.8 (1,417)
55.8 (1,417)
75.2 (1,911)
D
44.1 (1,120)
44.1 (1,120)
44.1 (1,120)
71.5 (1,817)
E
52.8 (1,342)
53.1 (1,348)
53.1 (1,348)
70.9 (1,800)
F
10.8 (274)
12.2 (309)
12.2 (309)
17.9 (454)
G
13.0 (330)
15.7 (400)
15.7 (400)
19.7 (500)
H
28.9 (734)
28.9 (734)
28.9 (734)
44.9 (1,141)
I
15.6 (397)
15.4 (391)
15.4 (391)
24.5 (622)
J
1.8 (45)
1.8 (45)
1.8 (45)
3.8 (97)
K
14.5 (368)
14.5 (368)
14.5 (368)
1.9 (47)
L
3.5 (90)
3.5 (90)
3.5 (90)
7 (180)
M
20.5 (520))
20.5 (520)
20.5 (520)
25.7 (654)
N
11.5 (291)
11.5 (291)
11.5 (291)
15.7 (400)
O
26.4 (670)
34.9 (888)
34.9 (888)
34.9 (888)
P
31.5 (800)
39.7 (1,009)
39.7 (1,009)
39.7 (1,009)
Q
38 (965)
46.3 (1,117)
46.3 (1,117)
46.3 (1,117)
Secondary
conduit
opening
Four 0.875 diameter holes for
0.750 diameter anchor bolts
90°
120°
5
3
1
6
4
2
120°
Rear
Front
O/Door swing
Outer door swing
Protective relay
door swing
M
N
C
A
L
K
D
B
B
F
G
G
A
E
H
I
J
T
Q
14