6.5
Signaling contact
Information on the signaling contact
• To connect the signaling contact, the device has an M12 interface: B-coded, 5-pin, male.
• The signaling contact is a floating switch that signals error statuses by opening the contact.
The signaling contact must be operated within the range of the operating voltage.
If an error/fault occurs, the signaling contact opens. In normal operation, the signaling
contact is closed.
• To connect the signaling contact, use a copper cable of category 24 AWG or a cable with a
cross-section of ≥ 0.25 mm
2
; see, for example, section "Product overview (Page 17)".
NOTICE
Damage due to voltage being too high
You can load the signaling contact with the operating voltage of the device and a maximum of
100 mA.
Higher voltages or currents can damage the device.
Position and assignment
)$8/7
)
)
Figure 6-3
Position of the signaling contact, for example on the SCALANCE XP208
Pin number
Contact
Assignment
1
F1
Fault contact 1
4
F2
Fault contact 2
Connecting up
6.5 Signaling contact
SCALANCE XP-200
64
Operating Instructions, 03/2021, C79000-G8976-C428-08
Содержание SCALANCE XP208EEC
Страница 10: ...Safety notices SCALANCE XP 200 10 Operating Instructions 03 2021 C79000 G8976 C428 08 ...
Страница 16: ...Recommendations on network security SCALANCE XP 200 16 Operating Instructions 03 2021 C79000 G8976 C428 08 ...
Страница 52: ...Installation 5 5 Rack mounting SCALANCE XP 200 52 Operating Instructions 03 2021 C79000 G8976 C428 08 ...
Страница 70: ...Connecting up 6 7 Functional ground SCALANCE XP 200 70 Operating Instructions 03 2021 C79000 G8976 C428 08 ...
Страница 88: ...Dimension drawings SCALANCE XP 200 88 Operating Instructions 03 2021 C79000 G8976 C428 08 ...