Connecting up
4.4 54 VDC power supply
SCALANCE XP-200
58
Operating Instructions, 05/2016, C79000-G8976-C428-01
4.4
54 VDC power supply
Notes on the power supply
WARNING
Incorrect power supply
Never operate the PoE variants of the device device with AC voltage or DC voltage higher
than 60 VDC.
Information on the power supply
●
Make sure that among other things the external power supply unit meets the following
basic requirements:
–
The output voltage (PoE voltage) is a safety extra-low voltage (SELV).
–
The output voltage (PoE voltage) meets the isolation requirements according to IEEE
802.3at (in other words 1500 VAC or 2250 VDC) to ground, to touchable conductive
parts and (if they exist) other secondary voltages.
–
Fuse the output voltage (PoE voltage) externally, see the section "Safety when
connecting up (Page 51)".
●
Select a suitable power of the external power supply unit, so that the power supply to the
power consumers is ensured, see the section "Power over Ethernet (PoE) (Page 41)".
●
For the cable supplying the power supply, use a cable with a length of max. 3 m.
●
To connect the power supply, use a copper cable of category 18 AWG or a cable with a
cross-section
≥
0.75 mm², see e.g. the section "Product overview (Page 17)".
●
To connect to the power supply, the device has two M12 interfaces: A-coded, 4-pin, male.
●
The power supply can be connected redundantly. Both inputs are isolated. There is no
distribution of load. The power supply unit with the higher output voltage supplies the
device alone.
●
The power supply is connected over a high resistance with the enclosure to allow an
ungrounded set up. The two power inputs are non-floating.
●
To connect the functional ground, use a copper cable of category 18 AWG or a cable with
a cross-section
≥
0.75 mm².
Содержание SCALANCE XP-200
Страница 8: ...Introduction SCALANCE XP 200 8 Operating Instructions 05 2016 C79000 G8976 C428 01 ...
Страница 50: ...Installation 3 5 Rack mounting SCALANCE XP 200 50 Operating Instructions 05 2016 C79000 G8976 C428 01 ...
Страница 66: ...Connecting up 4 7 Functional ground SCALANCE XP 200 66 Operating Instructions 05 2016 C79000 G8976 C428 01 ...
Страница 84: ...Dimension drawings SCALANCE XP 200 84 Operating Instructions 05 2016 C79000 G8976 C428 01 ...
Страница 92: ...Approvals SCALANCE XP 200 92 Operating Instructions 05 2016 C79000 G8976 C428 01 ...