Connecting up
4
4.1
Safety when connecting up
Safety notices
When connecting up the device, keep to the safety notices listed below.
Safety extra low voltage
WARNING
Power supply
The device is designed for operation with a directly connectable safety extra-low voltage
(SELV).
General notices
NOTICE
Suitable fusing for the power supply cables
The current on the terminal may not exceed 5 A. Use a fuse, that protects against currents
> 5 A. The fuse must meet the following requirements:
•
In areas where NEC or CEC applies:
–
Suitable for DC (min. 60 V / max. 5 A)
–
Breaking current at least 10 kA
–
Approval according to ANSI/UL 248-1 or CSA C22.2 No. 248.1
–
Classes R, J, L, T or CC
–
Suitable for the protection of DC power supply circuits
•
In other areas:
–
Suitable for DC (min. 60 V / max. 5 A)
–
Breaking current at least 10 kA
–
Approval in compliance with IEC 60127-1 / EN 601127-1
–
Switch off characteristics: B or C for circuit breakers and fuses
–
Suitable for the protection of DC power supply circuits
With 24 VDC devices you do not need to fuse the supply cable if you only use power
sources with a limited power source (LPS) or power sources according to NEC Class 2 for
the power supply of the devices.
Содержание SCALANCE XP-200
Страница 8: ...Introduction SCALANCE XP 200 8 Operating Instructions 05 2016 C79000 G8976 C428 01 ...
Страница 50: ...Installation 3 5 Rack mounting SCALANCE XP 200 50 Operating Instructions 05 2016 C79000 G8976 C428 01 ...
Страница 66: ...Connecting up 4 7 Functional ground SCALANCE XP 200 66 Operating Instructions 05 2016 C79000 G8976 C428 01 ...
Страница 84: ...Dimension drawings SCALANCE XP 200 84 Operating Instructions 05 2016 C79000 G8976 C428 01 ...
Страница 92: ...Approvals SCALANCE XP 200 92 Operating Instructions 05 2016 C79000 G8976 C428 01 ...