RXB39.1 – Room controller 

CM2N3875en_04 

Building Technologies 

 

2013-06-16 

Technical data 

 

 

Power supply 

Operating voltage 

AC 230 V +/-10 % 

 

Rated voltage 

AC 230 V 

 

Frequency 50/60 

Hz 

 

Power consumption with connected field devices 

Max. 12 VA 

 

Internal fuse 

Thermal, non-resetting 

Operating data 

Control algorithm 

PI 

 
Inputs (SELV) 

 

 

Signal inputs D1 … D4 

Quantity 

(for volt-free contacts) 

Contact voltage 

DC 16 V 

 

Contact current 

DC 5 mA 

 

Contact transfer resistance 

Max. 100 

 

 

Contact insulation resistance 

Min. 50 k

 

 

Switch time:  

min. 20ms “ON”, min. 20ms “OFF” 

Measured value input B1

 

Compatible temperature sensors 

LG-Ni 1000 

 

Quantity 2 

 

Measuring range 

0 … 50 °C 

 

Sensor current 

0.5 mA 

 

Resolution 0.1 

 

Measuring error at 25 °C sensor temp. (without cable)  max. 0.5 K 

 
Outputs (SELV) 

 

 

DC 0 … 10 V YC1, YC2, YC3

 

Quantity 

 Resolution 

3 mV 

 

Accuracy 

100 mV 

 

Output current 

Max. 1.5 mA 

Supply output G (SELV) 

Voltage / Max. load 

AC 24 V / Max. 6 VA 

 Relay outputs  

 

 

Q34 (fan release) 

Quantity 

1 (N/O contact) 

 

Relay type 

Monostable 

 

Contact rating with AC voltage 

 

 

Switching voltage 

Max. AC 250 V, min. AC 19 V 

 

Nominal current, resistive/inductive 

Max. AC 5(4) A (cos 

 = 0.6) 

 

Making current 200 ms half-time 

Max. 20 A 

 

Switching current at AC 19 V 

Min. AC 10 mA 

 

Contact rating with DC voltage 

 

 

Switching voltage 

Max. DC 250 V, min. DC 5 V 

 

Switching current at DC 5 V 

Min. DC 100 mA 

 

Switching capacity 

Max. 20 W 

 

Inductive load L/R 

Max. 7 ms 

 

External fuse (essential!) 

Max. 10 A 

Q14 (heater release) 

Quantity 

1 (N/O contact) 

 Relay 

type 

Monostable 

 

Contact rating with AC voltage 

 

 

Max. admissible load (resistive only) 

Max. 1.8 kW 

 

External fuse (essential) 

Max. 10 A 

 

Ports/interfaces 

 

 

Interface to room unit

 

Number of room units connectable 

 

Interface type 

for room unit 

 

for ETS / ACS 

PPS2  
KNX bus 

 

PPS2 baud rate 

4.8 kbit/s 

 

Baud rate on the KNX bus 

9.6 kbit/s 

KNX bus

 

Interface type 

Electrically isolated 

 

Bus current 

5 mA 

 

Baud rate bus 

9.6 kbit/s 

 

Bus topology 

Refer to Engineering, page 6 

 

 
 
 
 
 
 
 

 

Содержание RXB39.1

Страница 1: ...r 4 pipe fan coil systems with or without change over ECM fan support PI control KNX bus communication Integration into the Desigo building automation and control system via PX KNX DC 0 10 V control of valve actuators fan and electric heating coil Volt free relay contacts for release of the fan and the electric heating coil Commissioning with ETS Professional HandyTool or Synco ACS AC 230 V operat...

Страница 2: ... its parameters and by the input output configuration For details refer to the FNC description of functions document CM110788 When RXB controllers are integrated into a building automation and control system or into a Synco system additional functions become available such as time scheduling central control of setpoints etc Applications The following applications are available for the RXB39 1 room...

Страница 3: ...en flashing Startup phase No application selected Loading Download from ACS Room unit QAX34 3 in HandyTool mode OFF No supply voltage Fault Other patterns After switching on the operating voltage the service LED flashes in different patterns for 3 to 5 seconds If other patterns appear during normal operation this indicates an error The programming button is used to identify the room controller in ...

Страница 4: ...erve the warning notes in this data sheet Identification number unique serial number 3 Definitively loaded application Location Options for use of the labeling fields Appl and Loc Handwritten identification of the location and the activated application group All connection terminals are detachable plug in screw terminals To avoid incorrect wiring terminals which can be connected to AC 230 V relay ...

Страница 5: ...it RJ45 tool socket A A A A B B A B The tool socket is a proprietary socket A Siemens connecting cable must be used e g PXA C1 When connected to Ethernet the device on the other end may be damaged The tools ETS and ACS even if connected to a tool socket require an interface RS232 KNX interface ETS USB KNX EIB interface OCI700 ETS ACS The HandyTool is connected to the tool socket of the room contro...

Страница 6: ...on will be inter rupted if the block is removed from the controller the jumpers 19 19 and 21 21 are on the PCB not in the block see terminal diagrams on page 10 Different phases may be connected to the terminals 21 L 23 Q13 and 26 Q33 All AC 230 V conductors must be secured with cable ties The volt free releasing relay output for the fan allows the switching of a load up to AC 250 V 5 4 A The volt...

Страница 7: ...st be mounted in a cabinet or behind a cover that can only be opened removed with a key or a tool Ensure adequate air circulation to dissipate heat generated during operation Easy access is required for service personnel Local installation regulations must be observed Mounting instructions and a drilling template are printed on the controller packaging Commissioning The RXB39 1 room controller is ...

Страница 8: ...A Supply output G SELV Voltage Max load AC 24 V Max 6 VA Relay outputs Q34 fan release Quantity 1 N O contact Relay type Monostable Contact rating with AC voltage Switching voltage Max AC 250 V min AC 19 V Nominal current resistive inductive Max AC 5 4 A cos 0 6 Making current 200 ms half time Max 20 A Switching current at AC 19 V Min AC 10 mA Contact rating with DC voltage Switching voltage Max D...

Страница 9: ... m Housing protection standard Protection standard to EN 60529 IP30 with terminal cover fitted and wall mounted without DIN rail IP20 for all other mounting arrangements Protection class Suitable for use in systems with protection class I or II Ambient conditions Normal operation Class 3K5 to IEC 60721 3 3 Temperature 0 50 C Humidity 85 r h Transport Class 2K3 to IEC 60721 3 2 Temperature 25 65 C ...

Страница 10: ...rminal 0 10 V outputs YC1 11 0 10 V Heating control signal G0 12 Signal ground G 13 AC 24 V max 6 VA YC2 14 0 10 V Cooling control signal heating cooling in case of changeover G0 15 Signal ground YC3 16 0 10 V Fan control signal KNX bus CE 17 KNX bus CE 18 KNX bus Power supply N 19 Neutral conductor L 21 Phase conductor AC 230 V 10 Relay outputs Q13 23 Feed for Q14 Q14 24 Normally open contact max...

Страница 11: ...g heating cooling in case of changeover Q1 Controlled fan Q2 Power controller PWM or modulating e g SEM61 4 SEA45 1 data sheets N5102 N4937 Q3 Electric heating B3 QAX room unit Twisted pair For Q2 1 8 kW max resistive load use additional external fuses of max 10 A to protect the PCB tracks For information on the compatibility of field devices with the RXB39 1 room controller refer to the RX hardwa...

Страница 12: ...uilding Technologies 2013 06 16 Dimensions Dimensions in mm 62 35 3 90 3876M01 1 3 9 110 62 1 3 9 35 3 3876M02 120 152 50 6 161 100 135 80056 Without terminal covers With terminal covers Drilling diagram 2012 2013 Siemens Switzerland Ltd Subject to change ...

Отзывы: