RWD44U Controller 

Installation and 

Commissioning Guide 

Document No. 129-408

 

October 5, 2009 

 

 

 

 

Item Number 129-408, Rev. BA 

Function 

RWD44U controllers are intended for HVAC and Refrigeration systems including Heat 
Pumps. They are suitable for 1-, 2-, and 3-stage compressors. 

Input X1 detects the room or space temperature and compares it with the setpoints. 
Depending on the deviation, the controller acts accordingly with its outputs to achieve 
the desired setpoints. 

Function Summary 

 

Controller – Stand-alone controller with four two-position (On/Off) outputs. 

 

Universal input (X1) for the main temperature sensor. 

 

Universal input (X2) for the following auxiliary functions: 

 

On/Off (Standby) 

Setpoint reset 

 

Remote setting unit 

Sensor averaging 

 

Alarm 

Winter/Summer setpoint changeover 

 

Filter alarm 

Sensor select 

 

Digital input (D1) for the following digital functions: 

 

Day/night changeover setpoint 

 

On/Off (Standby) 

 

Alarm 

 

Filter alarm 

 

The RWD44U controller is intended for either DIN rail mounting in a switchboard or 
screw mounting with a protective enclosure. 

 

Desired output configuration and auxiliary function must be entered for initial set-
up. See 

Initial Program Settings (New Controller).

 

Application 

The RWD44U has standard pre-configured applications. There are three main 
configuration loops with combinations of ten auxiliary functions. See Table 1. 

 

Содержание RWD44U

Страница 1: ...X1 for the main temperature sensor Universal input X2 for the following auxiliary functions On Off Standby Setpoint reset Remote setting unit Sensor averaging Alarm Winter Summer setpoint changeover Filter alarm Sensor select Digital input D1 for the following digital functions Day night changeover setpoint On Off Standby Alarm Filter alarm The RWD44U controller is intended for either DIN rail mou...

Страница 2: ...mmissioning Example Two stage compressor with reversing valve on heating and two averaging sensors 35 Table 2 Input Configurations X1 X2 and D1 Applications 10 Through 39 X1 X2 D1 Options Filter Alarm Alarm Day Night Standby x0 Standby Main Standby x1 Remote setpoint Main Remote setpoint x2 Alarm Main Alarm x3 Filter alarm Main Filter alarm x4 Setpoint reset Main Setpoint reset x5 Avg X1 X2 Main M...

Страница 3: ...t cool 0 to 4 096 sec TON Minimum switch on time for Q 0 to 4 096 sec TD Time Delay for next stage ON 0 to 4 096 sec TOFF Minimum switch off time for Q 0 to 4 096 sec PS 3 Auxiliary Control Loop Set up Setpoint reset shift Start point End point and Shift differential Setpoint reset shift Start point End point and Shift differential SUM Summer changeover point Time delay from Winter Summer changeov...

Страница 4: ...Siemens software tool See Software Tool Optional Programming Initial Program Settings New Controller There are five levels of parameter setting PS modes PS1 through PS4 and a setpoint mode Each PS has a set of default parameters which can be changed during commissioning When powered the first time the controller will proceed to PS1 with default application 10 See below for commissioning steps PS 1...

Страница 5: ...differential SD for output stage 1 2 and 3 Sensor range 2 F 1 K Enter min On time for output stage 1 2 and 3 0 to 4 096 s 0 s Enter min Off time for output stage 1 2 and 3 0 to 4 096 s 60 s Enter time delay TD for next stage On 0 to 4 096 s 30 s Enter changeover time delay TD heating cooling demand 0 to 4 096 s 120 s Setpoint Mode Range Type Default Enter SP h1 Sensor range 70 F 21 C Enter SP h2 S...

Страница 6: ...entering any of the setpoint displays the setpoint on display can be adjusted by pushing the SEL λ button Increase value by pressing the button or decrease the value by pressing the button When the required value is reached press the SEL λ button to save the new value Time out For setpoint adjustment during normal operation the controller will exit the setting after 20 seconds and return to the ma...

Страница 7: ...ive unless a parameter has been changed Ensure all outputs are disconnected before changing an application Software Tool Optional Commissioning A software tool for the controller application selection and parameter adjustment is available It is a user friendly Windows 95 or later based software tool The software tool has the following functions Adjusting all available parameters Uploading and down...

Страница 8: ...ations 10 Through 19 C1 C2 H1 H2 X1 X2 S1 PC Cooling stage 1 Cooling stage 2 Heating stage 1 Heating stage 2 Room temperature sensor Auxiliary sensor or a digital input Switch or time clock Personal computer optional for set up only Figure 6 Applications 20 Through 39 CR1 CR2 CR3 RV X1 X2 S1 PC Compressor stage 1 Compressor stage 2 Compressor stage 3 Reversing valve relay Main temperature sensor A...

Страница 9: ...e the ARG62 21 single RWD44U WARNING There must be a minimum of 0 31 inches 8 mm distance from terminations to panel enclosures to avoid electric shock Electrical Installation Notes Standard cables can be used for the controller However when mounting in an environment greatly exposed to EMI use only shielded cables The RWD44U is designed for 24 Vac operating voltage Low voltage must comply with th...

Страница 10: ...duct or company names mentioned herein may be the trademarks of their respective owners 2007 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Document No 129 408 Printed in the USA ...

Отзывы: