21 Handling
2017-07-24
Function block "Service functions" contains 4 operating lines that are especially
suited for making function checks:
Operating line 161 permits simulation of the outside temperature
Operating line 162 can be used to energize any of the output relays
Operating line 163 can be used to query any of the actual values of sensors
Operating line 164 can be used to query any of the sensor setpoints or limit
values
If
Er
appears on the display
,
the error can be pinpointed via the error code on
operating line 50.
21.3 Installation
21.3.1 Mounting location
The ideal location for the controller is a dry room, such as the boiler room.
The permissible ambient temperature is 0...50 °C.
When the mounting location is selected, the controller can be fitted as follows:
In a control panel, on an inner wall or on a top hat rail
On a panel front
In a control panel front
In the sloping front of a control desk
21.3.2 Mounting choices
RVP360 can be mounted in one of 3 different ways:
Wall mounting: The base is secured to a flat wall with 3 screws
Rail mounting: The base is snapped on a top hat rail
Flush-panel mounting: The base is fitted in a panel cutout measuring
138 x 92 mm. The thickness of the front panel may be 3 mm maximum
21.3.3 Electrical installation
Local electrical safety regulations must be complied with
The electrical installation must be made by qualified personnel
The cable lengths should be chosen such that there is sufficient space to open
the control panel door
Cable strain relief must be ensured
The cable glands used must be made of plastic
The cables of the measuring circuits carry extra low-voltage
The cables from the controller to the actuating devices and pumps carry mains
voltage
Sensor cables must not be run parallel to mains carrying cables
A defective or apparently damaged unit must immediately be disconnected from
power
Operating lines for
function checks