42/106
Siemens
Basic Documentation RVP360
CE1P2546en
Building Technologies
9 Function block: Space heating
2017-07-24
9.7 Generation of setpoint
All plant types use weather-compensated control systems. The setpoint is generated
via the heating curve as a function of the outside temperature. The temperature
used is the
composite
outside temperature.
OZW30 SYNERGYR central unit
Room temp. setpoint NORMAL
*
Only active with room unit level
Room temp. setpoint REDUCED
s
Heating curve slope
Room temp. setpoint holiday / protection
The impact of the central unit OZW30 is described in chapter 20.1.4 "Interplay with
SYNERGYR central unit OZW30".