5 Function block: End-user space heating
2017-07-24
5
Function block: End-user space heating
This function block provides settings that the end-user himself can make.
5.1 Operating
lines
Line Function, parameter
Factory setting
(range)
Unit
Heating
circuit
1
Room temperature setpoint for NORMAL heating
20.0 (0…35)
°C
1, 2
2
Room temperature setpoint for REDUCED heating
14.0 (0…35)
°C
1, 2
3
Room temperature setpoint for
holiday/protection mode
10.0 (0…35)
°C
1, 2
4
Weekday, for entering the heating program
1-7 (1…7 / 1-7)
-
1, 2
5
1. 1st heating phase, start of NORMAL heating
06:00 (00:00…24:00)
hh:mm
1, 2
6
1. 1st heating phase, end of NORMAL heating
22:00 (00:00…24:00)
hh:mm
1, 2
7
2. 2nd heating phase, start of NORMAL heating
--:--
(00:00…24:00) hh:mm
1, 2
8
2. 2nd heating phase, end of NORMAL heating
--:--
(00:00…24:00) hh:mm
1, 2
9
3. 3rd heating phase, start of NORMAL heating
--:--
(00:00…24:00) hh:mm
1, 2
10
3. 3rd heating phase, end of NORMAL heating
--:--
(00:00…24:00) hh:mm
1, 2
12
Date of first day
--.--
(01.01…31.12) dd:mm
1, 2
13
Date of last day
--.--
(01.01…31.12) dd:mm
1, 2
14
Heating curve, flow temperature setpoint at an outside
temperature of 15 °C
30 (20…70)
°C
1, 2
15
Heating curve, flow temperature setpoint at an outside
temperature of -5 °C
60 (20…120)
°C
1, 2
In column "Heating circuit" it is indicated for each operating line which heating cir-
cuit can be set and how the setting affects the heating circuits. Meaning:
1 = settings only apply to heating circuit 1
2 = settings only apply to heating circuit 2
1, 2 = settings must be made separately for both heating circuits
1+2 = settings apply to both heating circuits
– = settings or function are independent of the heating circuits
5.2 Setpoints
5.2.1 General
The setpoints for the NORMAL and the REDUCED room temperature and for holi-
day/protection mode are entered directly in °C room temperature. They are inde-
pendent of whether or not the control uses a room sensor.
5.2.2 Frost protection for the building
The lowest valid room temperature setpoint always corresponds to at least the
setpoint for holiday/protection mode (setting on operating line 3), even if lower
setpoints for the NORMAL and the REDUCED room temperature have been en-
tered (settings on operating lines 1 and 2).
If a room sensor is used and the room temperature falls below the setpoint for holi-
day/protection mode, the automatic ECO function – if available – aborts the OFF
mode until the room temperature has risen 1 °C above the setpoint for holi-
day/protection mode.
Note on the operating
line tables