Plant types 6-x
Function block "Plant configuration"
51 Plant
type
5-1
(4-0...6-1)
........................
See the plant diagrams above
Function block "Space heating"
61 Heating limit NORMAL
17.0 °C
.................
°C
--- = function deactivated
Siemens Building Technologies
74 319 0817 0 a
CE1G2546en
28.02.2011
7/12
(ECO day)
(--- / –5.0…25.0)
.................
°C
62 Heating limit REDUCED
5.0 °C
.................
°C
--- = function deactivated
(ECO night)
(--- / –5.0…25.0)
.................
°C
63 Building time constant
20 h
(0…50)
....................
h
10 h = light building construction
20 h = medium building construction
50 h = heavy building construction
64 Quick setback
1
0 = without quick setback
........................
(0 / 1)
1 = with quick setback
........................
65 Room temperature source
A
0 = no room sensor available
........................
(0…3 / A)
1 = room unit connected to terminal A6
........................
2 = room sensor connected to terminal B5
3 = mean value of both devices connected to
terminals A6 and B5 (heating circuit 1)
and / or A6 and B52 (heating circuit 2)
A = automatic selection
66 Type of optimization
0
0 = optimization with room model
........................
(0 / 1)
1 = optimization with room unit / room sensor
........................
(setting 0 only provides optimum start control)
67 Maximum heating up period
0:00 h
.....................
h Maximum forward shift for switching on
(0:00...42:00)
.....................
h before occupancy starts
0:00 = no optimum start control
68 Maximum early shutdown
0:00 h
.....................
h Maximum forward shift for switching off
(0:00...6:00)
.....................
h before occupancy ends
0:00 = no optimum stop control
69 Maximum limitation of room
--.- °C
.................
°C --- = limitation deactivated,
temperature
(--.- / 0.0…35.0)
.................
°C function can only be provided with
room unit / room sensor
70 Influence of room
4
Function can only be provided with
........................
temperature (gain factor)
(0…20)
room unit / room sensor
........................
71 Boost of room temperature
5 °C
.................
°C
setpoint on boost heating
(0…20)
.................
°C