RUGGEDCOM RX1100
Installation Guide
Chapter 4
Technical Specifications
Serial Port Specifications
35
Mode
Connector
Type
Cable
Type (μm)
Tx λ (typ.)
(nm)
Tx min.
(dBm)
Tx max.
(dBm)
Rx
Sensitivity
(dBm)
Rx
Saturation
(dBm)
Distance
(typ.) (km)
Power
Budget
(dB)
SM
LC
9/125
1300
-5
0
-35
3
50
30
SM
SC
9/125
1300
0
5
-37
0
90
37
SM
LC
9/125
1300
0
5
-37
0
90
37
MM
LC
50/125
1300
-22.5
-14
-31
-14
2
8.5
Section 4.5
Serial Port Specifications
Baud Rate
Connector
Isolation
RJ45
300 to 230 kbps
DB25
2.5 kV
Section 4.6
IRIG-B Output Specifications
Parameter
Typical Value
Output Current (IS)
40 mA total between two output ports
Output Voltage (VS)
5 Vp-p
Output Impedance (RS)
25 Ω
Section 4.7
Operating Environment
Parameter
Range
Comments
Ambient Operating Temperature
-40 to 85 °C
(-40 to 185 °F)
Measured from a 30 cm (12 in) radius surrounding the center of the
enclosure.
Ambient Relative Humidity
5% to 95%
Non-condensing
Ambient Storage Temperature
-40 to 85 °C
(-40 to 185 °F)