Installing the Device

2.6.1 Connecting AC or DC Power

• Make sure a terminal block is installed in the unused port and that any wires

from the secondary terminal block are properly terminated

• Make sure the first power source is off before connecting (or disconnecting) a

second power source

1. If connecting a secondary power source, make sure the power source currently

connected to the device is disabled (e.g. power cable is unplugged from the wall

receptacle).

2. Insert the appropriate terminal block(s) into the device and tighten both screws.

Power Source

Terminal Block Type

HI

3 POS

LO

5 POS

Figure 2.8

Assembling the Power Terminal Blocks

Note

Torque all terminal connections to 0.6 N·m (5 lbf-in).

3. Connect the power cable to the device as follows:

HI AC/DC Power Supply

a. Connect the Line wire (AC) or

Positive wire (DC) to the positive/

live (+/L) terminal on the terminal

block.

b. Connect the Neutral wire (AC)

or Negative wire (DC) to the

negative/neutral (-/N) terminal on

the terminal block.

 

3

4

5

4

3

5

2

1

     1    

3 POS Terminal Block

RUGGEDCOM RSG908C

Installation Manual, 04/2022, C79000-G8976-1404-11

15

Содержание RUGGEDCOM RSG908C

Страница 1: ...Edition 04 2022 Installation Manual SIMATIC NET Rugged Ethernet Switches RUGGEDCOM RSG908C https www siemens com ruggedcom ...

Страница 2: ...d Ethernet Switches RUGGEDCOM RSG908C Installation Manual Preface Introduction 1 Installing the Device 2 Device Management 3 Communication Ports 4 Technical Specifications 5 Certification 6 04 2022 C79000 G8976 1404 11 ...

Страница 3: ...those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper Use of Siemens Products Note the following WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation If products and components from other manufacturers are used the...

Страница 4: ...us Locations 7 2 4 Mounting the Device 8 2 4 1 Mounting the Device on a DIN Rail 8 2 4 2 Mounting the Device to a Panel 10 2 5 Connecting the Failsafe Alarm Relay 12 2 6 Connecting Power 14 2 6 1 Connecting AC or DC Power 14 2 6 2 Wiring Examples 16 3 Device Management 21 3 1 Connecting to the Device 21 3 2 Configuring the Device 22 4 Communication Ports 23 4 1 Fiber Optic Ethernet Ports 23 4 2 SF...

Страница 5: ...Drawings 28 6 Certification 31 6 1 Approvals 31 6 1 1 CSA 31 6 1 2 CSA Sira 32 6 1 3 European Union EU 33 6 1 4 FCC 33 6 1 5 FDA CDRH 34 6 1 6 ISED 34 6 1 7 TÜV SÜD 34 6 1 8 RRA 34 6 1 9 ISO 35 6 1 10 RoHS 35 6 1 11 Other Approvals 35 6 2 EMC and Environmental Type Tests 36 iv RUGGEDCOM RSG908C Installation Manual 04 2022 C79000 G8976 1404 11 ...

Страница 6: ...Catalog https support industry siemens com cs ww en view 109482309 Time Synchronization Capabilities of RUGGEDCOM Devices https support industry siemens com cs ww en view 109780448 SIMATIC NET Glossary The SIMATIC NET Glossary describes special terms that may be used in this document The glossary is available online via Siemens Industry Online Support SIOS at https support industry siemens com cs ...

Страница 7: ...nconforming goods or services whether claims of the Customer are based in contract including fundamental breach in tort including negligence and strict liability or otherwise For warranty details visit https www siemens com or contact a Siemens customer service representative Training Siemens offers a wide range of educational services ranging from in house training of standard courses on networki...

Страница 8: ... Online Support app by Siemens AG on any Android Apple iOS or Windows mobile device and be able to Access Siemens extensive library of support documentation including FAQs and manuals Submit SRs or check on the status of an existing SR Contact a local Siemens representative from Sales Technical Support Training etc Ask questions or share knowledge with fellow Siemens customers and the support comm...

Страница 9: ...Preface Contacting Siemens viii RUGGEDCOM RSG908C Installation Manual 04 2022 C79000 G8976 1404 11 ...

Страница 10: ...ides a high level of immunity to electromagnetic interference heavy electrical surges extreme temperatures and humidity for reliable operation in harsh environments The device features IP40 degree protection and does not use internal fans for cooling The device supports an extended operating temperature range of 40 to 85 C 40 to 185 F Compact Design The small form factor of the RUGGEDCOM RSG908C a...

Страница 11: ...Conformal coated printed circuit boards Power Supply Fully integrated power supply Dual LO AC DC inputs 88 300 VDC or 85 264 VAC Dual low voltage DC inputs 12 24 or 48 VDC Terminal blocks for reliable maintenance free connections CSA UL 62368 1 safety approved to 85 C 185 F 1 2 Description The RUGGEDCOM RSG908C features various ports controls and indicator LEDs on the front panel for connecting co...

Страница 12: ...r Supply Terminal Blocks Pluggable terminal blocks for connecting one or more power sources For more information refer to Connecting Power Page 14 and Power Supply Specifications Page 25 Chassis Ground Terminal Protects the device from power surges and accumulated static electricity For information about grounding the device refer to Connecting Power Page 14 1 3 Required Tools and Materials The fo...

Страница 13: ...n fully decommissioned For more information refer to the associated Configuration Manual Recycling and Disposal For environmentally friendly recycling and disposal of this device and related accessories contact a facility certified to dispose of waste electrical and electronic equipment Recycling and disposal must be done in accordance with local regulations 4 RUGGEDCOM RSG908C Installation Manual...

Страница 14: ...ation exposure CAUTION Burn hazard risk of personal injury The surface of the device may be hot during operation or as a result of the ambient air temperature Wear appropriate personal protective equipment and use caution when working with or around the device NOTICE This product contains no user serviceable parts Attempted service by unauthorized personnel shall render all warranties null and voi...

Страница 15: ...tion refer to Approvals Page 31 2 Unpack and inspect the device For more information refer to Unpacking the Device Page 6 3 Mount the device For more information refer to Mounting the Device Page 8 4 Connect the failsafe alarm relay For more information refer to Connecting the Failsafe Alarm Relay Page 12 5 Connect power and ground the device For more information refer to Connecting Power Page 14 ...

Страница 16: ... exceeded The equipment shall be used in an area of not more than pollution degree 2 as defined by IEC 60664 1 Transient protection shall be provided that is set at a level not exceeding 140 of the peak rated voltage value at the supply and failsafe relay contacts terminals to the equipment The console ports USB Type B shall be used in a non hazardous area only Pluggable communication modules shal...

Страница 17: ...ained on all open sides of the device to allow for some convectional airflow Forced airflow is not required However any increase in airflow will result in a reduction of ambient temperature and improve the long term reliability of all equipment mounted in the rack space Note For detailed dimensions of the device with either DIN rail or panel hardware installed refer to Dimension Drawings Page 28 2...

Страница 18: ...he DIN rail Note The adapter features a sliding release with a slot at the bottom for a flathead screwdriver 2 2 3 1 1 1 DIN Rail 2 DIN Rail Adapter Figure 2 2 Mounting the Device to a DIN Rail 2 Insert a flathead screwdriver into the slot of the sliding release and move it down 3 Push the device against the bottom of the DIN rail then let go of the sliding release to latch the device RUGGEDCOM RS...

Страница 19: ... Rail Adapter Figure 2 3 Removing the Device from a DIN Rail 2 Swing the bottom of the device away from the DIN rail 3 Lift the device off the DIN rail 2 4 2 Mounting the Device to a Panel For panel installations the RUGGEDCOM RSG908C can be equipped with panel adapters on the top and bottom of the chassis The adapters allow the device to be attached to a panel using screws 10 RUGGEDCOM RSG908C In...

Страница 20: ...nting adapters to the top and bottom of the device using the four M4 screws included with the device 2 1 2 1 1 Screw M4 2 Panel Mount Adapter Figure 2 4 Panel Mount Adapter Assembly 2 Prepare mounting holes in the panel where the device is to be installed RUGGEDCOM RSG908C Installation Manual 04 2022 C79000 G8976 1404 11 11 ...

Страница 21: ... alarm conditions The NO Normally Open contact is closed when the unit is powered and there are no active alarms If the device is not powered or if an active alarm is configured the relay opens the NO contact and closes the NC Normally Closed contact Note Control of the failsafe relay output is configurable through RUGGEDCOM RSG908C One common application for this relay is to signal an alarm if a ...

Страница 22: ...al block into the device and tighten the screws Figure 2 6 Assembling the Failsafe Alarm Relay Terminal Block 2 Connect a failsafe device to the terminal block 3 2 4 1 1 Failsafe Alarm Relay Terminal Block 2 Normally Open 3 Common 4 Normally Closed Figure 2 7 Failsafe Alarm Relay Wiring RUGGEDCOM RSG908C Installation Manual 04 2022 C79000 G8976 1404 11 13 ...

Страница 23: ...quipment an appropriately rated DC circuit breaker must be installed Use minimum 16 gage copper wiring when connecting terminal blocks Equipment must be installed according to applicable local wiring codes and standards 2 6 1 Connecting AC or DC Power The device features dual power supply inputs to allow for redundant connections to separate independent AC or DC power supplies Each power supply te...

Страница 24: ...all receptacle 2 Insert the appropriate terminal block s into the device and tighten both screws Power Source Terminal Block Type HI 3 POS LO 5 POS Figure 2 8 Assembling the Power Terminal Blocks Note Torque all terminal connections to 0 6 N m 5 lbf in 3 Connect the power cable to the device as follows HI AC DC Power Supply a Connect the Line wire AC or Positive wire DC to the positive live L term...

Страница 25: ...ve Terminal 5 Positive Terminal Figure 2 9 Terminal Block Wiring 4 Connect the chassis ground screw to ground Potential Earth It is recommended to terminate the ground connection with an M4 ring or spade lug and then torque to 1 7 N m 15 lbf in 2 1 1 M4 Screw 2 M4 Ring Lug Figure 2 10 Chassis Ground Connection 5 Connect the external power supply to a power source The Power LED on the device will t...

Страница 26: ...2 6 2 Wiring Examples HI Power Supply Configurations Figure 2 11 Single HI AC Power Input Configuration Figure 2 12 Single HI DC Power Input Configuration RUGGEDCOM RSG908C Installation Manual 04 2022 C79000 G8976 1404 11 17 ...

Страница 27: ...Installing the Device 2 6 2 Wiring Examples Figure 2 13 Dual HI AC and DC Power Supplies Figure 2 14 Dual HI DC Power Supplies 18 RUGGEDCOM RSG908C Installation Manual 04 2022 C79000 G8976 1404 11 ...

Страница 28: ... 2 6 2 Wiring Examples LO Power Supply Configurations Figure 2 15 Single LO DC Power Input Configuration Figure 2 16 Dual LO DC Power Input Configuration RUGGEDCOM RSG908C Installation Manual 04 2022 C79000 G8976 1404 11 19 ...

Страница 29: ...Installing the Device 2 6 2 Wiring Examples 20 RUGGEDCOM RSG908C Installation Manual 04 2022 C79000 G8976 1404 11 ...

Страница 30: ...ort to access the boot time control and RUGGEDCOM RSG908C interfaces The console port provides access to RUGGEDCOM RSG908C s console interface Note Console ports are intended to be used only as a temporary connection during initial configuration or troubleshooting Note For Microsoft Windows users the RUGGEDCOM USB Serial Console driver must be installed on the users workstation before connecting v...

Страница 31: ...ttps 192 168 0 1 For more information about available ports refer to Communication Ports Page 23 3 2 Configuring the Device Once the device is installed and connected to the network it must be configured All configuration management is done via the RUGGEDCOM RSG908C interface For more information about configuring the device refer to the RUGGEDCOM ROS Configuration Manual associated with the insta...

Страница 32: ...Transceiver 1000Base SX LX 1 to 4 Fiber Optic 100Base FX Ethernet Ports 4 1 Fiber Optic Ethernet Ports The RUGGEDCOM RSG908C features four fixed Fiber optic Ethernet ports each with an LC Lucent Connector connector Make sure the Transmit Tx and Receive Rx connections of each port are properly connected and matched to establish a proper link Port Types 2 1 RUGGEDCOM RSG908C Installation Manual 04 2...

Страница 33: ... array of SFP transceivers available from Siemens LEDs Each socket features an LED that indicates its link state State Description Green Solid Link established Green Blinking Activity Off No link detected Compatible SFP Transceivers For more information about which SFP transceivers are compatible with the RUGGEDCOM RSG908C as well as instructions for ordering and installation removal refer to the ...

Страница 34: ... 24 VDC 48 VDC 5 A 1 5 kVDC 13 4 W 100 VDC 270 VDC 125 VDC 250 VDC 3 15 A 5 kVDC 15 3 W HI 100 VAC 240 VAC 110 VAC 220 VAC 3 15 A 5 kVDC 15 5 W a Current consumption may vary based on configuration Non Hazardous Environments Input Voltage Power Supply Type Minimum Maximum Nominal Internal Fuse Rating Isolation Maximum Power Consumption a LO 10 VDC 60 VDC 12 VDC 24 VDC 48 VDC 5 A 1 5 kVDC 13 4 W 88...

Страница 35: ...250 VAC 2 A 5 0 kVAC a between coil and contacts 1 0 kVAC a between contacts a 50 to 60 Hz for 1 minute 5 3 Supported Networking Standards The following networking standards are supported by RUGGEDCOM RSG908C Standard 10 Mbps Ports 100 Mbps Ports 1000 Mbps Ports Notes IEEE 802 3x Full Duplex Operation IEEE 802 3z 1000Base LX IEEE 802 3ab 1000Base Tx IEEE 802 1D MAC Bridges IEEE 802 1Q VLAN Virtual...

Страница 36: ...velength nm a Transmit Power dBm Data Rate Mbps Mode Connector Cable μm Transmit Receive Min Max Receiver Sensitivity dBm Receiver Saturation dBm Distance km a Power Budget 100 MM LC 50 125 1308 1308 22 5 14 31 14 2 11 100 MM LC 62 5 125 1308 1308 20 14 31 14 2 11 a Typical 5 5 Operating Environment The RUGGEDCOM RSG908C is rated to operate under the following environmental conditions Ambient Oper...

Страница 37: ...gress Protection IP40 Enclosure Die Cast Aluminum 5 7 Dimension Drawings Note All dimensions are in millimeters unless otherwise stated 90 176 52 162 72 Figure 5 1 Overall Dimensions 28 RUGGEDCOM RSG908C Installation Manual 04 2022 C79000 G8976 1404 11 ...

Страница 38: ...ns 5 7 Dimension Drawings 185 44 163 12 210 9 38 1 225 44 90 Figure 5 2 Panel Mount Dimensions 86 41 90 90 11 162 72 Figure 5 3 DIN Rail Mount Dimensions RUGGEDCOM RSG908C Installation Manual 04 2022 C79000 G8976 1404 11 29 ...

Страница 39: ...Technical Specifications 5 7 Dimension Drawings 30 RUGGEDCOM RSG908C Installation Manual 04 2022 C79000 G8976 1404 11 ...

Страница 40: ...endive Electrical Equipment for Use in Class I Division 2 Hazardous Locations CAN CSA C22 2 No 60079 0 15 Explosive Atmospheres Part 0 Equipment General Requirements CAN CSA C22 2 No 60079 15 16 Electrical Apparatus for Explosive Gas Atmospheres Part 15 Construction Test and Marking of Type of Protection n Electrical Apparatus ANSI UL 62368 1 2014 Information Technology Equipment Safety Part 1 Gen...

Страница 41: ...trical Apparatus for Explosive Gas Atmospheres Part 15 Construction Test and Marking of Type of Protection n Electrical Apparatus 6 1 2 CSA Sira When marked with the following ATEX marking this device is approved for use in Zone 2 hazardous locations under certificate Sira 18ATEX4069X Note For the maximum ambient temperature refer to the hazardous location label affixed to the device II 3 G Ex nA ...

Страница 42: ... the Restriction of Hazardous Substances CISPR 32 EN 55032 Electromagnetic compatibility of multimedia equipment Emission requirements The device is marked with a CE marking and can be used throughout the European community A copy of the CE Declaration of Conformity is available from Siemens Canada Ltd For contact information refer to Contacting Siemens Page vii 6 1 4 FCC This device has been test...

Страница 43: ...ollowing ISED Innovation Science and Economic Development Canada standard CAN ICES 3 A NMB 3 A 6 1 7 TÜV SÜD This device is certified by TÜV SÜD to meet the requirements of the following standards CAN CSA C22 2 NO 62368 1 Information Technology Equipment Safety Part 1 General Requirements Bi National standard with UL 62368 1 UL 62368 1 Information Technology Equipment Safety Part 1 General Require...

Страница 44: ... 10 RoHS This device is declared by Siemens Canada Ltd to meet the requirements of the following RoHS Restriction of Hazardous Substances directives for the restricted use of certain hazardous substances in electrical and electronic equipment China RoHS 2 Administrative Measure on the Control of Pollution Caused by Electronic Information Products A copy of the Material Declaration is available onl...

Страница 45: ... kHz 4 DC Power Ports 4 kV 2 5 kHz 5 kHz 4 AC Power Ports 4 kV 2 5 kHz 5 kHz 4 IEC 61000 4 4 Burst Fast Transient Earth Ground Ports 4 kV 2 5 kHz 5 kHz 4 Signal Ports 4 kV Line to Ground 2 kV Line to Line 4 DC Power Ports 2 kV Line to Ground 1 kV Line to Line 3 IEC 61000 4 5 Surge AC Power Ports 4 kV Line to Ground 2 kV Line to Line 4 Signal Ports 10 V 3 DC Power Ports 10 V 3 AC Power Ports 10 V 3...

Страница 46: ... Ports 2 kV Signal Ports 5 kV Failsafe Relay Output DC Power Ports 5 kV IEC 60255 27 HV Impulse AC Power Ports 5 kV EMC Immunity Type Tests per IEEE 1613 Note RUGGEDCOM products meet Class 1 requirements for copper Ethernet configurations and Class 2 for fiber Ethernet configurations Class 1 allows for temporary communication loss while Class 2 requires error free and interrupted communications Te...

Страница 47: ...Severity Levels Cold Temperature Test Ad 40 C 40 F 16 Hours IEC 60068 2 1 Cold Storage Test Ab 40 C 40 F 16 Hours Dry Heat Test Bd 85 C 185 F 16 Hours IEC 60068 2 2 Dry Heat Storage Test Bd 85 C 185 F 16 Hours IEC 60068 2 30 Humidity Damp Heat Cyclic Test Dd 95 Non Condensing 55 C 131 F 6 Cycles IEC 60068 2 14 Change of Temperature Test Nb 5 Cycles 40 to 85 C 40 to 185 F IEC 60068 2 78 Humidity Da...

Страница 48: ...dustry Online Support service and support https support industry siemens com Industry Mall https mall industry siemens com Siemens Canada Ltd Digital Industries Process Automation 300 Applewood Crescent Concord Ontario L4K 4E5 Canada 2022 Siemens Canada Ltd Subject to change ...