Certification
Industry Canada
39
Section 6.1.5
Industry Canada
This device is declared by Siemens Canada Ltd. to meet the requirements of the following Industry Canada
standard:
• CAN ICES-3 (A)/NMB-3 (A)
Section 6.1.6
Other Approvals
This device meets the requirements of the following additional standards:
•
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric
Power Substations
•
IEC 61850-3
Communication Networks and Systems for Power Utility Automation - Part 3: General Requirements
•
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity for Industrial Environments
Section 6.2
EMC and Environmental Type Tests
The RS416 has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test
Description
Test Levels
Severity Levels
Enclosure Contact
± 8 kV
4
IEC 61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure ports
20 V/m
Note
a
Signal ports
± 4 kV @ 2.5 kHz
Note
a
DC Power ports
± 4 kV
4
AC Power ports
± 4 kV
4
IEC 61000-4-4
Burst (Fast Transient)
Earth
ground ports
± 4 kV
4
Signal ports
2 kV
3
DC Power ports
± 2 kV line-to-earth, ± 1 kV line-to-line
3
IEC 61000-4-5
Surge
AC Power ports
± 4 kV line-to-earth, ± 2 kV line-to-line
4
Signal ports
10 V
3
IEC 61000-4-6
Induced (Conducted) RFI
DC Power ports
10 V
3
Содержание RUGGEDCOM RS416
Страница 4: ...RUGGEDCOM RS416 Installation Guide iv ...
Страница 34: ...RUGGEDCOM RS416 Installation Guide Chapter 3 Communication Ports Connecting Multiple RS485 Devices 26 ...
Страница 40: ...RUGGEDCOM RS416 Installation Guide Chapter 4 Technical Specifications Mechanical Specifications 32 ...
Страница 44: ...RUGGEDCOM RS416 Installation Guide Chapter 5 Dimension Drawings 36 ...
Страница 50: ...RUGGEDCOM RS416 Installation Guide Chapter 6 Certification EMC and Environmental Type Tests 42 ...